| 2020-01-06 13:28:01 | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 19051525 |
| | ADD: 719 N. SAPODILLA AVE. |
| | CONT: TBD/ TO BE DETERMINED |
| | TEL: NONE |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION. |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: MONDAY JAN.6TH/2020 |
| | ACTION: DENIED |
| | |
| | 4X FEE / NOTICE!!!!! FLORIDA STATUTE 553.80(2)(B) |
| | WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS? |
| | DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN |
| | ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING |
| | CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS |
| | REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO |
| | CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY |
| | NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, |
| | EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY, |
| | ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL, |
| | MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER |
| | REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING |
| | COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL |
| | GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH |
| | REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION, |
| | A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE |
| | PERMIT FEE ATTRIBUTED TO PLANS REVIEW. |
| | |
| | |
| | 1) SHEET G DRAWING INDEX & PROJECT INFO: |
| | |
| | 1A)(1) PLEASE CORRECT THE SHEET G THE DRAWING INDEX |
| | WITH SURVEY SHEET LISTED 005G AS SHOWN IN THE INDEX OR |
| | REMOVE THE SHEET NUMBER WITH A REVISION. |
| | 1ST ROUND OF COMMENTS. PLEASE NOTE THE DRAWING INDEX |
| | THERE SHOULD BE A SURVEY SHEET 005G BETWEEN SHEET 004 G |
| | STANDARD ABBREVIATIONS & SYMBOLS SHEET AND CIVIL COVER |
| | SHEET 100C. MISSING DOCUMENT. 107.2.1.2 ADDITIONAL |
| | INFORMATION IS REQUIRED. |
| | |
| | 1A)(2) NEW COMMENT. A SURVEY IS REQUIRED TO DETERMINE |
| | THE EXISTING BUILDING AND LOCATION OF LOT LINES, ALL |
| | LOT LINES, NOT JUST THE ADJOINING LOT 713. THERE ARE |
| | MANY REQUIREMENTS THAT WILL NEED TO SEE HOW FAR THE |
| | BUILDING IS FROM THE PROPERTY LINE. EXTERIOR FIRE |
| | RATING OF WALLS, REAR EGRESS FROM THE BUILDING AND |
| | CANOPY, EGRESS COURT REQUIREMENTS, THESE AND OTHER |
| | REQUIREMENTS CANNOT BE DETERMINED UNTIL A SURVEY IS |
| | SUBMITTED SHOWING THE DISTANCE FROM THE BUILDING TO THE |
| | PROPERTY LINE IN ALL DIRECTIONS. PLEASE NOTE THE SURVEY |
| | SUBMITTED SHEET 103 ENGINEERING PLAN IS FOR |
| | TOPOGRAPHICAL USE AND SANITARY USE ONLY. NOTE THIS |
| | SURVEY ALSO INDICATES THE PROPERTY AS ONE LARGE LOT NOT |
| | 2 ADJOINING LOTS WHICH IS INCORRECT. THE SURVEY BY ENG |
| | ENUITY GROUP INC. HAS AN ELECTRONIC SIGNATURE AND SEAL |
| | 12/11/2019 BY ADAM SWANEY. APPARENTLY THE SHEET WAS |
| | PRINTED ON A PAPER COPY WAS UPLOADED, THERE IS NO |
| | ELECTRONIC SIGNATURE NOR SEAL ON THIS SHEET |
| | OR THERE WAS NEVER A ELECTRONIC SIGNATURE & SEAL. |
| | |
| | 1B) THIS REVIEW WILL NEED TO BE FAILED SINCE THERE IS |
| | NO UNITY OF TITLE FILED WITH THE CLERK OF THE COURTS |
| | OFFICE. THE REQUEST TO HAVE THE UNITY OF TITLE AFTER |
| | THE PERMIT IS ISSUED WILL NEED TO BE DECIDED ON BY THE |
| | BUILDING OFFICIAL ROBERT BROWN AND THE DIRECTOR OF THE |
| | CRA, STIPULATIONS WILL ALSO NEED TO BE AGREED UPON AND |
| | BEFORE THE ISSUANCE OF A CERTIFICATE OF COMPLETION |
| | SINCE THIS PERMIT IS FOR A SHELL ONLY. |
| | |
| | 1ST ROUND OF COMMENTS. WHEN VIEWING THIS PROJECT IN THE |
| | PALM BEACH COUNTY PROPERTY APPRAISERS WEBSITE THE |
| | PROJECT COMPRISES OF 2 LOTS 719 AND 713 N. SAPODILLA |
| | AVE. PLEASE NOTE WITHOUT A UNITY OF TITLE THE CANOPY |
| | CANNOT BE BUILT SINCE IT PASSES OVER PROPERTY LINES OF |
| | 2 ADJOINING LOTS. |
| | CREATION OR EXTENSION OF NONCONFORMITY. 2017 EXISTING |
| | BUILDING CODE LEVEL II 701.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. CREATION OR EXTENSION OF |
| | NONCONFORMITY. ALL NEW WORK, RE-CONFIGURATION SHALL NOT |
| | CREATE OR EXTEND ANY NONCONFORMITY IN THE EXISTING |
| | BUILDING TO WHICH THE RE-CONFIGURATION OF SPACE IS |
| | BEING MADE WITH REGARD TO ACCESSIBILITY, STRUCTURAL |
| | STRENGTH, FIRE SAFETY, MEANS OF EGRESS, OR THE CAPACITY |
| | OF MECHANICAL, PLUMBING, OR ELECTRICAL SYSTEMS. |
| | |
| | UNITY OF TITLE. THE PROPOSED BUILDING STRUCTURE |
| | TRANSGRESSES LEGAL BOUNDARY LINES BETWEEN THE LOTS |
| | WHICH COMBINE TO FORM 'THE SITE'. A 'UNITY OF TITLE' |
| | SHALL BE |
| | RECORDED AT THE COUNTY COURTHOUSE. SUBMIT A COPY OF THE |
| | RECORDED 'UNITY OF TITLE' DOCUMENT SO THAT FBC TABLE |
| | 601 BOUNDARY LINE REQUIREMENTS MAY BE DEEMED NOT |
| | APPLICABLE. |
| | SEE WEBSITE FOR APPLICATION: |
| | HTTP://WWW.WPB.ORG/ENGINEERING/ENG_FORMS.PHP |
| | "APPLICATION FOR UNITY OF TITLE" |
| | HTTP://WWW.WPB.ORG/ENGINEERING/UPLOADS/2010-10-12-14-45 |
| | -38-UNITYOFTITLE3.PDF |
| | VINCENT J NOEL |
| | SURVEYOR/REAL ESTATE SUPERVISOR |
| | ENGINEERING SERVICES DEPARTMENT |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH, FL 33401 |
| | PHONE: 494-1040 EXT: 1096 |
| | FAX: 494-1116 |
| | E-MAIL: [email protected] |
| | OR |
| | MANUEL JULIAN GONZALEZ |
| | ENGINEERING PROJECT COORDINATOR |
| | ENGINEERING SERVICES DEPARTMENT |
| | 401 CLEMATIS STREET, 4TH FLOOR |
| | WEST PALM BEACH, FL 33401 |
| | (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402) |
| | MAIN PHONE: (561) 822-1200 |
| | DIRECT: (561) 494-1085 |
| | FAX: (561) 494-1116 |
| | MOBILE: (561) 644-7301 |
| | EMAIL: [email protected] |
| | WWW.WPB.ORG/ENGINEERING |
| | |
| | 1C) COMPLIED. NO HISTORIC EXEMPTIONS ARE BEING TAKEN. |
| | |
| | 1D) 2ND ROUND OF COMMENTS. USING THE SHEET 103C |
| | ENGINEERING PLAN THE DESIGNER OF RECORD DOES SHOW UNDER |
| | THE PROPOSED OUTDOOR COVERED PATIO THE 2 REQUIRED |
| | EXITS. THERE IS ONLY 1 EXIT WHICH IS AN ACCESSIBLE |
| | EXIT. AS NOTED IN THE 1ST REVIEW IF 2 EXITS ARE |
| | REQUIRED, THEN 2 ACCESSIBLE EXITS TO THE PUBLIC WAY |
| | WOULD BE REQUIRED. THE 2ND MEANS OF EGRESS DROPS YOU |
| | OFF BEHIND THE COVERED PATIO INTO A GRASSED AREA. THIS |
| | MEANS OF EGRESS NEEDS TO BE EXTENDED TO THE PUBLIC WAY. |
| | THE 2ND ISSUE WITH THIS MEANS OF EGRESS, A SURVEY WITH |
| | MEASUREMENTS FROM THE BUILDING ARE NOT SHOWN. IS THERE |
| | AN ALLEY BEHIND THIS LOT OR ANOTHER LOT? IT CANNOT BE |
| | DETERMINED IF THE EXIT DISCHARGE FROM UNDER THE COVERED |
| | OUTDOOR PATIO TO THE PROPERTY LINE FOR THE EGRESS COURT |
| | WILL REQUIRE 1 HOUR RATED WALLS AT THE PROPERTY LINE, |
| | SEE 2017 FBC-B SECTION 1028.4.2. |
| | |
| | 1ST ROUND OF COMMENTS. PLEASE NOTE THE TABLE SHOWING |
| | THE OCCUPANT LOAD FOR THE BUILDING AS A TOTAL 145 |
| | OCCUPANTS. PLEASE NOTE THAT THE COVERED OUTDOOR PATIO |
| | IS ALREADY OUTSIDE OF THE BUILDING AND A SEPARATE COUNT |
| | SHOULD BE TAKEN FOR THIS OUTDOOR SEATING. A SEPARATE |
| | PERMIT SHOULD BE APPLIED FOR THE CANOPY. PLEASE ALSO |
| | NOTE THE OCCUPANT LOAD UNDER THE OUTDOOR CANOPY IS |
| | STATED AT 77 REQUIRING 2 EXITS. |
| | PLEASE NOTE THE CURRENT EXIT FROM THE PATIO EXITS ONTO |
| | THE GRASS, NOT AN ACCESSIBLE EXIT. 2017 |
| | FBC-ACCESSIBILITY CODE SECTION 207.1 MEANS OF EGRESS |
| | SHALL COMPLY WITH SECTION 1003.2.13 OF THE |
| | INTERNATIONAL BUILDING CODE (2000 EDITION AND 2001 |
| | SUPPLEMENT) OR SECTION 1007 OF THE INTERNATIONAL |
| | BUILDING CODE (2003 EDITION). |
| | |
| | 2003 IBC-B 1007.1 WHERE MORE THAN ONE MEANS OF EGRESS |
| | IS REQUIRED BY SECTIONS 1014.1 OR 1018.1 FROM ANY |
| | ACCESSIBLE SPACE, EACH ACCESSIBLE PORTION OF THE SPACE |
| | SHALL BE SERVED BY NOT LESS THAN TWO MEANS OF EGRESS. |
| | |
| | |
| | 1E) COMPLIED. |
| | |
| | 2) LIFE SAFETY SHEET LS1: |
| | |
| | 2A)(1) SEMI-COMPLIED SEE COMMENT (1D), REQUIRES 2 |
| | ACCESSIBLE MEANS OF EGRESS TO THE PUBLIC WAY. |
| | 1ST ROUND OF COMMENTS. WITHIN THE BUILDING THE PLANS |
| | SHOW 2 REQUIRED EXITS. UNDER THE COVERED OUTDOOR PATIO |
| | THE WITH AN OCCUPANT LOAD OF 77 BUT ONLY ONE MEANS OF |
| | EGRESS, YOU CAN?T REENTER THE BUILDING FOR THE 2ND |
| | MEANS OF EGRESS, PLEASE SHOW COMPLIANCE WITH THE 2017 |
| | FBC-B TABLE 1006.2.1 MAXIMUM OCCUPANT LOAD WITH ONE |
| | EXIT. |
| | |
| | 2A)(2) NEW COMMENT. SHEET 002 PROJECT INFO STATES THERE |
| | IS 90 SEATS ON THE EXTERIOR PATIO, THE LIFE SAFETY |
| | SHEET 1ST FLOOR INDICATES 100 SEATS WHEN YOU COUNT THE |
| | SEATS 110 SEATS ON THE PATIO. WHERE THE 2 PATIO EXITS |
| | ARE IN A GREY BOX AND STATING FUTURE ASSEMBLY |
| | CONCENTRATED, THIS AREA IS PART OF THE EGRESS PATH AND |
| | NOT HAVE OCCUPANTS BLOCKING THE EGRESS PATH. PLEASE |
| | REVIEW: WHERE PERSONS ARE ADMITTED TO THE BUILDING AT |
| | TIMES WHEN SEATS ARE NOT AVAILABLE, SUCH PERSONS SHALL |
| | BE ALLOWED TO WAIT IN A LOBBY OR SIMILAR SPACE, |
| | PROVIDED SUCH LOBBY OR SIMILAR SPACE SHALL NOT ENCROACH |
| | UPON THE MINIMUM WIDTH OR REQUIRED CAPACITY OF THE |
| | MEANS OF EGRESS. 2017 FBC-B 1029.4. |
| | |
| | 2B) 2ND REQUEST. THE RESPONSE SHEET INDICATES THE |
| | OUTDOOR CANOPY IS TO BE UNDER SEPARATE PERMIT BUT ON |
| | SHEETS 315A, 320A & 321A NOTE # 10 MENTIONS THE OUTDOOR |
| | CANOPY NEW FIXED FABRIC SHED AWNING AND SHOP DRAWINGS |
| | TO BE SIGNED AND SEALED BY A FLORIDA REGISTERED |
| | ENGINEER. NOWHERE DOES THE STATEMENT ON ANY OF THE |
| | PLANS INDICATE UNDER SEPARATE PERMIT. |
| | 1ST ROUND OF COMMENTS. IS THE COVERED OUTDOOR PERMIT |
| | SUPPOSED TO BE PART OF THIS PERMIT PACKAGE OR UNDER A |
| | SEPARATE PACKAGE. THERE IS NO DESIGN INFORMATION FOR |
| | THIS PORTION OF WORK. IS THE SAME CONTRACTOR FOR THE |
| | BUILDING AS THE COVERED OUTDOOR DINING AREA. 107.2.1.2. |
| | ADDITIONAL INFORMATION REQUIRED. |
| | |
| | 2C) 2ND REQUEST. THE RESPONSE SHEET INDICATES THE |
| | OUTDOOR CANOPY IS TO BE UNDER SEPARATE PERMIT BUT ON |
| | SHEETS 320A & 321A NOTE # 10 MENTIONS THE OUTDOOR |
| | CANOPY NEW FIXED FABRIC SHED AWNING AND SHOP DRAWINGS |
| | TO BE SIGNED AND SEALED BY A FLORIDA REGISTERED |
| | ENGINEER. NOWHERE DOES THE STATEMENT ON ANY OF THE |
| | PLANS INDICATE UNDER SEPARATE PERMIT. |
| | 1ST ROUND OF COMMENTS. THE COVERED OUTDOOR DINING AREA. |
| | THERE IS NO INFORMATION FOR THIS AREA OF WORK. WILL |
| | THERE BE PLASTIC WIND BREAKS ADDED TO THE CANOPY FOR |
| | RAIN AND HEAT IN THE WINTER? 107.2.1.2. ADDITIONAL |
| | INFORMATION REQUIRED. |
| | |
| | 2D) COMPLIED. MEZZANINE LEVEL IS 1/3RD THE FLOOR AREA |
| | ALLOWED BY SECTION 505.2.1 |
| | |
| | 2E) 2ND REQUEST. THE PLANS LIFE SAFETY 1ST FLOOR AND |
| | MEZZANINE LEVEL STATE YES FIRE EXTINGUISHERS ON THE |
| | PLAN BUT DO NOT PLACE THEM IN THE BUILDING SHOWING CODE |
| | COMPLIANCE. |
| | 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION 107.2.1. W.P.B. |
| | ADMINISTRATIVE CODE/2017. CONSTRUCTION DOCUMENTS SHALL |
| | BE SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE |
| | AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT |
| | IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS |
| | DETERMINED BY THE BUILDING OFFICIAL. |
| | 1ST ROUND OF COMMENTS. THE PLANS UNDER THE HEADING OF |
| | FIRE PROTECTION SYSTEMS ALSO INDICATES PORTABLE FIRE |
| | EXTINGUISHERS BUT NONE ARE SHOWN ON THE FLOOR PLAN OR |
| | COMPLIANCE WITH 2017 FBC-B 906.1. |
| | |
| | 2F) NEW COMMENT. THE 1ST FLOOR LIFE SAFETY PLAN SHOWS 1 |
| | ACCESSIBLE SEAT AT WHAT APPEARS TO BE THE BAR, PLEASE |
| | SHOW COMPLIANCE WITH THE 2017 FBC-ACCESSIBLITY CODE |
| | SECTION. 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND |
| | WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34 INCHES |
| | MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. |
| | |
| | 2G) NEW COMMENT. THE 1ST FLOOR PLAN HAS A TOTAL OF 153 |
| | SEATS ON THE 1ST FLOOR. 153 XO.O5= 7.65 OR 8 ACCESSIBLE |
| | SEATS REQUIRED. THE PLAN ONLY SHOWS 6 PLEASE UPDATE THE |
| | PLANS. 2017 ACCESSIBILITY CODE 226.1 WHERE DINING |
| | SURFACES ARE PROVIDED FOR THE CONSUMPTION OF FOOD OR |
| | DRINK, AT LEAST 5 PERCENT OF THE SEATING SPACES AND |
| | STANDING SPACES AT THE DINING SURFACES SHALL COMPLY |
| | WITH 902. |
| | |
| | 3) SHEET LS 2 THE MEZZANINE PLAN. |
| | |
| | 3A-B) COMPLIED. |
| | |
| | 4) COMPLIED. ROOF HATCH 16 SQ. FT. OF OPENING. |
| | |
| | 5-7) COMPLIED. |
| | |
| | 8) 2ND REQUEST. PERMIT 19051529 IF THIS PERMIT IS FOR |
| | THE SCREENING PROPERTY LINE WALL OR IS IT FOR SCREENING |
| | WALL ON THE ROOF TOP FOR THE A/C UNITS. THE RESPONSE |
| | COMMENTS SOUND AS IF IT IS FOR THE ROOF TOP SCREENING |
| | OF THE A/C EQUIPMENT WHICH WOULD BE PART OF THE MAIN |
| | BUILDING PERMIT? A SEPARATE PERMIT IS REQUIRED FOR PLAN |
| | SHEET A326 TRASH ENCLOSURE AND PRECAST CONCRETE WALL |
| | SYSTEM. 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 9) PROVISO: SHEET 328 A ROOF DETAILS, DETAIL 3. 2017 |
| | FBC-B TABLE 1510.10. BOTTOM OF HORIZONTAL FRAMING |
| | MEMBER ALLOWS FOR THE WIDTH OF THE A/C UNIT TO BE 24 |
| | -36 INCHES WIDE. |
| | |
| | 10) COMPLIED. |
| | |
| | 11) COMPLIED, ASCE 7-10. |
| | |
| | 12) 2ND REQUEST. SHEET 400S. S1 UNDER THE HEADING OF |
| | SHALLOW FOUNDATION MENTIONS A SOILS REPORT BY |
| | GEOTECHNICAL MATERIAL TESTING INSPECTION SERVICES DATED |
| | 01/18/2018, PLEASE SUBMIT THE REPORT FOR ITS FINDINGS. |
| | 2017 FBC-B 1803.5.2 QUESTIONABLE SOIL. WHERE THE |
| | CLASSIFICATION, STRENGTH OR COMPRESSIBILITY OF THE SOIL |
| | IS IN DOUBT OR WHERE A LOAD-BEARING VALUE SUPERIOR TO |
| | THAT SPECIFIED IN THIS CODE IS CLAIMED, THE BUILDING |
| | OFFICIAL SHALL BE PERMITTED TO REQUIRE THAT A |
| | GEOTECHNICAL INVESTIGATION BE CONDUCTED. |
| | PLEASE SUBMIT EITHER IF IN PAPER AN ORIGINAL SIGNED AND |
| | SEALED REPORT. IF ELECTRONICALLY THE REPORT WILL NEED |
| | TO BE SIGNED AND SEALED ELECTRONICALLY. |
| | |
| | 13) PROVISO: THIS PROJECT HAS BOLTED STEEL CONNECTIONS |
| | AS WELL AS WELDED STEEL CONNECTIONS. THE CONTRACTOR IS |
| | REQUIRED TO PROVIDE WELD PROCEDURE SPECIFICATIONS & |
| | WELDER OPERATOR PERFORMANCE QUALIFICATION RECORDS IN |
| | ACCORDANCE WITH THE REFERENCED STANDARDS AT TIME OF |
| | INSPECTION. IN ACCORDANCE WITH THE AMERICAN WELDING |
| | SOCIETY. |
| | 2017 FBC-B 2204.1 WELDING |
| | 2017 FBC-B 2204.2 BOLTING. |
| | IF THERE IS ANY QUESTIONS IN REGARDS TO THESE |
| | REQUIREMENTS PLEASE CONTACT THE CHIEF BUILDING |
| | INSPECTOR KEN CONRAD AT 561-805-6666. THANK YOU. |
| | |
| | 14) PROVISO/ DEFERRED SUBMITTALS. 2017 FBC-B 1609.1.2 |
| | PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS & |
| | CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS, |
| | ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 NOV. 01/ |
| | 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES. |
| | (B) WINDOWS & MULLIONS |
| | (C) PANEL WALLS: STOREFRONTS, WALL LOUVERS, EFIS |
| | SYSTEMS, |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP |
| | VENTILATORS |
| | (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C |
| | STANDS |
| | |
| | 15A) PROVISO/ DEFERRED SUBMITTALS. W. P. B. 107.3.4.1 |
| | PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED |
| | BY THE DCA RULE 9N-03 SHALL BE REVIEWED AND APPROVED IN |
| | WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| | FOR JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE |
| | ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING |
| | ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC.. |
| | |
| | 15B) PROVISO/ DEFERRED SUBMITTALS. DELEGATED |
| | ENGINEERING. 61G15-30.003 ENGINEERING DOCUMENT |
| | CLASSIFICATION. FL 61G-15-30.006 (3) THE DELEGATED |
| | ENGINEER SHALL FORWARD THE DELEGATED ENGINEERING |
| | DOCUMENTS TO THE ENGINEER OF RECORD FOR REVIEW. |
| | |
| | 15C)PROVISO: 107.3.4.2 DEFERRED SUBMITTALS. FOR THE |
| | PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS ARE |
| | DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE NOT |
| | SUBMITTED AT THE TIME OF THE APPLICATION AND THAT ARE |
| | TO BE SUBMITTED TO THE BUILDING OFFICIAL WITHIN A |
| | SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL |
| | HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE |
| | REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE |
| | SHALL LIST THE DEFERRED SUBMITTALS ON THE CONSTRUCTION |
| | DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL. |
| | |
| | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN |
| | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD |
| | THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL |
| | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED |
| | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING |
| | OFFICIAL. |
| | |
| | 16) PROVISO/ DEFERRED SUBMITTALS. PLEASE IDENTIFY ON |
| | THE PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF |
| | RECORD AND BEFORE SUBMISSION TO THE BUILDING |
| | DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE |
| | IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING, |
| | MULLION SIZE, LENGTH IF UNREINFORCED OR REINFORCED |
| | INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE |
| | PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B 1405.13.1 |
| | INSTALLATION. WINDOWS AND DOORS SHALL BE INSTALLED IN |
| | ACCORDANCE WITH APPROVED MANUFACTURER?S INSTRUCTIONS. |
| | FASTENER SIZE AND SPACING SHALL BE PROVIDED IN SUCH |
| | INSTRUCTIONS AND SHALL BE CALCULATED BASED ON MAXIMUM |
| | LOADS AND SPACING USED IN THE TESTS. |
| | |
| | 17A) PROVISO/ DEFERRED SUBMITTALS. ROOFING PRODUCT |
| | APPROVALS: FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY ALL |
| | ROOFING SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES FOR |
| | ROOF ZONE # 1. REVIEW THE PRODUCT APPROVAL LIMITATIONS, |
| | IF ENHANCED FASTENING IS ALLOWED FOR ROOF ZONES 2 & 3. |
| | FASTENER DENSITIES SHALL BE INCREASED FOR BOTH |
| | INSULATION & THE BASE SHEET AS CALCULATED IN COMPLIANCE |
| | WITH ROOFING APPLICATION STANDARDS RAS 117. CALCULATION |
| | PREPARED, SIGNED AND |
| | SEALED BY A FLORIDA REGISTERED PROFESSIONAL ENGINEER OR |
| | REGISTERED ARCHITECT. 1609.6.4.4.1 COMPONENTS & |
| | CLADDING. |
| | |
| | 17B) PROVISO/ DEFERRED SUBMITTALS. 107.2.1.2 FOR ROOF |
| | ASSEMBLIES REQUIRED BY THE CODE, THE CONSTRUCTION |
| | DOCUMENTS SHALL ILLUSTRATE, DESCRIBE AND DELINEATE THE |
| | TYPE OF ROOFING SYSTEM, MATERIALS, VENTING, FASTENING |
| | REQUIREMENTS, FLASHING REQUIREMENTS AND WIND RESISTANCE |
| | RATING THAT ARE REQUIRED TO BE INSTALLED. PRODUCT |
| | EVALUATION AND INSTALLATION SHALL INDICATE COMPLIANCE |
| | WITH THE WIND CRITERIA REQUIRED FOR THE SPECIFIC SITE. |
| | |
| | 18) IMPACT FEES - DIGITAL SUBMITTALS: |
| | PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE |
| | DIGITALLY VIA PROJECT DOX UPON NOTIFICATION BY THIS |
| | OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST |
| | FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE |
| | OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL |
| | IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME |
| | THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM |
| | CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS |
| | TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON |
| | APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO |
| | YOUR PROJECT OR EMAIL IT TO [email protected] . |
| | PALM BEACH COUNTY IMPACT FEE OFFICE IS LOCATED AT 2300 |
| | N. JOG RD. ROOM?S 2W01-2W14 WEST PALM BEACH, FL. |
| | |
| | 19) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | JAMES A. WITMER BN, PX, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL |
| | |