Plan Review Details - Permit 19051482
Plan Review Stops For Permit 19051482
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2020-01-22 Cont ID  
Sent By pvalenti Date 2020-01-22 Time 14:35 Rev Time 0.00
Received By pvalenti Date 2020-01-22 Time 12:43 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-11-14 Cont ID  
Sent By jwitmer Date 2019-11-14 Time 17:22 Rev Time 0.00
Received By jwitmer Date 2019-11-14 Time 16:12 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-06-19 Cont ID  
Sent By jwitmer Date 2019-06-19 Time 09:29 Rev Time 0.00
Received By jwitmer Date 2019-06-19 Time 06:29 Sent To  
Notes
2019-06-19 09:20:272017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19051482
 ADD: 2823 N AUSTRALIAN AVE. / URBAN YOUTH IMPACT
 CONT: BLACKBURN BUILDING CO.
 TEL: 561-762-7848
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. JUNE 19, 2019
 ACTION: DENIED
  
 1) THE LIFE SAFETY SHEET 003-LS-1.0:
 1A) UNDER THE HEADING OF OCCUPANCY: BUSINESS IS LISTED
 FIRST AND EDUCATION AS AN ACCESSORY USE. THE PLANS
 INDICATE THIS BUILDING IS FOR URBAN YOUTH IMPACT. WHAT
 AGE GROUP WILL THIS FACILITY BE USED FOR EDUCATIONAL
 PURPOSES? PLEASE DEFINE THE PURPOSE OR USE OF THESE
 ROOMS. SEE THE 2017 FBC-B SECTIONS:
  
 304.1 BUSINESS GROUP B OCCUPANCY:
  
 EDUCATIONAL OCCUPANCIES FOR STUDENTS ABOVE THE 12TH
 GRADE.
  
 TRAINING AND SKILL DEVELOPMENT NOT IN A SCHOOL OR
 ACADEMIC PROGRAM (THIS SHALL INCLUDE, BUT NOT BE
 LIMITED TO, TUTORING CENTERS, MARTIAL ARTS STUDIOS,
 GYMNASTICS AND SIMILAR USES REGARDLESS OF THE AGES
 SERVED, AND WHERE NOT CLASSIFIED AS A GROUP A
 OCCUPANCY).
  
 305.1 EDUCATIONAL GROUP E. EDUCATIONAL GROUP E
 OCCUPANCY INCLUDES, AMONG OTHERS, THE USE OF A BUILDING
 OR STRUCTURE, OR A PORTION THEREOF, BY SIX OR MORE
 PERSONS AT ANY ONE TIME FOR EDUCATIONAL PURPOSES
 THROUGH THE 12TH GRADE.
 1B) PLEASE PROVIDE ADDITIONAL INFORMATION. UNDER THE
 CODE ANALYSIS, OCCUPANCY BUSINESS, LIFE SAFETY
 OCCUPANCY: 19 WHEREAS DEPICTED ON THE PLAN THE
 CLASSROOMS ARE 385 SQ. FT. / 20 =19 +1 = 20. PLEASE
 REVIEW TABLE 1004.1.2 OF THE 2017 FBC-B. FOR EDUCATION
 / CLASSROOMS THE OCCUPANT FACTOR LOAD IS 20 NET.
 385/ 20=19.25, YOU ROUND DOWN TO THE NEXT FULL NUMBER
 THERE ARE NO PORTIONS OF AN OCCUPANT SO THE ALLOWABLE
 OCCUPANT LOAD WOULD BE 19 OCCUPANTS. PLEASE CORRECT THE
 PLANS.
 YOU MAY BE REQUIRED TO USE 2 COLUMNS FOR SHOWING THE
 ALLOWABLE OCCUPANT LOAD, ONE UNDER THE FLORIDA BUILDING
 CODE AND ONE FOR THE HEALTH DEPARTMENT, WE HAVE SEEN
 THIS IN THE PAST FOR DAY CARE CENTERS.
 1C) THE TEACHING KITCHEN SHOWS THE OCCUPANT LOAD FACTOR
 AS 35 SF/OCC. THE 2017 FBC-B TABLE 1004.1.2 FOR SHOPS
 AND OTHER VOCATIONAL ROOM AREAS USES AN OCCUPANT LOAD
 FACTOR OF 50 NET.
 YOU MAY BE REQUIRED TO USE 2 COLUMNS FOR SHOWING THE
 ALLOWABLE OCCUPANT LOAD, ONE UNDER THE FLORIDA BUILDING
 CODE AND ONE FOR THE HEALTH DEPARTMENT, WE HAVE SEEN
 THIS IN THE PAST FOR DAY CARE CENTERS.
 1D) OCCUPANT LOADS ARE NOT STATED FOR STORAGE AREAS
 110A. PLEASE USE A FACTOR OF 300 SF/OCC. FOR THIS ROOM.
 FBC-B TABLE 1004.1.2.
 1E) THE EXIT ACCESS DOOR TO THE LEFT SIDE OF THE PAGE
 INDICATES 86 OCCUPANTS ARE GOING INTO THE CORRIDOR
 119A. THIS CORRIDOR IS ALSO TAKING AN ADDITIONAL 129
 OCCUPANTS FOR EXITING PURPOSES FOR THE AUDITORIUM OR A
 TOTAL OCCUPANT LOAD OF 215 OCCUPANTS. GOING THROUGH THE
 EXIT DOOR BEFORE THE EXIT STAIRWAY A OCCUPANT LOAD IS
 POSTED AS 172 OCCUPANTS GOING THROUGH THIS DOORWAY. IT
 WOULD APPEAR43 OCCUPANTS ARE NOT ACCOUNTED FOR. PLEASE
 SHOW WHERE THESE OCCUPANTS ARE EXITING. THE PLANS DO
 NOT SHOW WHERE THESE 43 OCCUPANTS ARE EXITING BUT THE
 CORRIDOR AT THE TOP OF THE AUDITORIUM AND EXIT ACCESS
 DOOR TO THE LEFT OF THE AUDITORIUM THE REMAINDER OF THE
 OCCUPANT EXITING FROM THE AUDITORIUM 129 + 43 OCCUPANTS
 NOT SHOWN EXITING MATCH THE 172 OCCUPANTS TRAVELING
 THROUGH THIS DOOR, PLEASE SHOW THE MISSING 43
 OCCUPANTS. 107.2.1.2 ADDITIONAL INFORMATION IS
 REQUIRED.
 1F) THE LIFE SAFETY PLAN SHOWS THAT FOR EVERY EXIT
 ACCESS AND EXIT DOOR YOU CAN TAKE 180 OCCUPANTS THROUGH
 THE DOOR OR 36/0.2= 180 OCCUPANTS. PLEASE TAKE NOTE
 THAT THE CLEAR WIDTH OF A 3 FOOT DOOR (SHEET 004-A-1.0
 DOOR SCHEDULE) IS NOT 36 INCHES. WITH THE DOOR
 THICKNESS AND HINGE YOU WOULD TAKE OF 2 INCHES OR THE
 REMAINING CLEAR AREA OF 34 INCHES FOR A 3 FOOT WIDE
 DOOR. 34 INCHES/ 0.2= 170 OCCUPANTS. IT WOULD APPEAR
 SOME OF THE OCCUPANT LOADS SHOULD SHIFT TO OTHER EXITS
 OR EXIT ACCESS DOORS. FBC-B 1005.3.2.
 2) THE PRESSURES FOUND ON SHEET 009-S0.1 FOR THE WALL &
 ROOF ZONES BOTH STATE THE PRESSURES ARE ALLOWABLE(
 NOMINAL) NOT THE VULT. THE PRESSURES ARE HIGH FOR A
 BUILDING WITH MEAN ROOF HEIGHT OF 20 FEET AND EXPOSURE
 C. THE DESIGNER OF RECORD CAN DESIGN TO THE HIGHER
 STANDARD, BUT CONFIRMING THAT THE STATED PRESSURES ARE
 IN VASD. 107.2.1.2 ADDITIONAL INFORMATION REQUIRED.
 THANK YOU.
 3) SHEET 009-S0.1 WIND DESIGN LIST THE 2014 FBC-B ASCE
 7-10. PLEASE UPDATE THE CODE VERSION. YES THE 2014 &
 2017 FBC-B BOTH USE THE ASCE 7-10 STANDARD.
 4) FOR THE STRUCTURAL STEEL WORK TO BE COMPLETED ON THE
 STRUCTURAL ROOF DECK AND BAR JOIST PLEASE PROVIDE THE
 FOLLOWING INFORMATION AT TIME OF INSPECTION:
 WELDED OR BOLTED CONNECTIONS. THE CONTRACTOR IS
 REQUIRED TO PROVIDE WELD PROCEDURE SPECIFICATIONS &
 WELDER OPERATOR PERFORMANCE QUALIFICATION RECORDS IN
 ACCORDANCE WITH THE REFERENCED STANDARDS AT TIME OF
 INSPECTION. IN ACCORDANCE WITH THE AMERICAN WELDING
 SOCIETY.
 2017 FBC-B 2204.1 WELDING
 2017 FBC-B 2204.2 BOLTING.
 5) 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS ,MULLIONS
 (B) WINDOWS & MULLIONS
 (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP
 VENTILATION, INTAKE OR EXHAUST, NEW CURBS
  
 6) 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF
 THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL.
  
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 7) IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE
 PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF
 RECORD AND BEFORE SUBMISSION TO THE BUILDING
 DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE
 IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING,
 MULLION SIZE, LENGTH IF UNREINFORCED OR REINFORCED
 INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE
 PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B 1405.13.1
 INSTALLATION. WINDOWS AND DOORS SHALL BE INSTALLED IN
 ACCORDANCE WITH APPROVED MANUFACTURER?S INSTRUCTIONS.
 FASTENER SIZE AND SPACING SHALL BE PROVIDED IN SUCH
 INSTRUCTIONS AND SHALL BE CALCULATED BASED ON MAXIMUM
 LOADS AND SPACING USED IN THE TESTS.
  
 8) ROOFING: FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY
 ALL ROOFING SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES
 FOR ROOF ZONE # 1. REVIEW THE PRODUCT APPROVAL
 LIMITATIONS, IF ENHANCED FASTENING IS ALLOWED FOR ROOF
 ZONES 2 & 3. FASTENER DENSITIES SHALL BE INCREASED FOR
 BOTH INSULATION & THE BASE SHEET AS CALCULATED IN
 COMPLIANCE WITH ROOFING APPLICATION STANDARDS RAS 117.
 CALCULATION PREPARED, SIGNED AND
 SEALED BY A FLORIDA REGISTERED PROFESSIONAL ENGINEER OR
 REGISTERED ARCHITECT. 1609.6.4.4.1 COMPONENTS &
 CLADDING.
  
 9) SHEET 006-A-3.0 THE ROOFTOP SHEET SHOWS NEW
 MECHANICAL EQUIPMENT ON THE ROOF BUT NO ACCESS TO THE
 ROOF TOP TO SERVICE THE UNITS.
 2017 FBC-B 1509.6.4 EQUIPMENT AND APPLIANCES ON ROOFS
 OR ELEVATED STRUCTURES.
 WHERE EQUIPMENT AND APPLIANCES REQUIRING ACCESS ARE
 INSTALLED ON ROOFS OR ELEVATED STRUCTURES AT A HEIGHT
 EXCEEDING 16 FEET (4877 MM), SUCH ACCESS SHALL BE
 PROVIDED BY A PERMANENT APPROVED MEANS OF ACCESS, THE
 EXTENT OF WHICH SHALL BE FROM GRADE OR FLOOR LEVEL TO
 THE EQUIPMENT AND APPLIANCES? LEVEL SERVICE SPACE. SUCH
 ACCESS SHALL NOT REQUIRE CLIMBING OVER OBSTRUCTIONS
 GREATER THAN 30 INCHES HIGH OR WALKING ON ROOFS HAVING
 A SLOPE GREATER THAN 4 UNITS VERTICAL IN 12 UNITS
 HORIZONTAL (33-PERCENT SLOPE).
 PERMANENT LADDERS INSTALLED TO PROVIDE THE REQUIRED
 ACCESS SHALL COMPLY WITH THE FOLLOWING MINIMUM DESIGN
 CRITERIA:
 1. THE SIDE RAILING SHALL EXTEND ABOVE THE PARAPET OR
 ROOF EDGE NOT LESS THAN 30 INCHES (762 MM).
 2. LADDERS SHALL HAVE RUNG SPACING NOT TO EXCEED 14
 INCHES (356 MM) ON CENTER.
 3. LADDERS SHALL HAVE A TOE SPACING NOT LESS THAN
 6-INCHES (152 MM) DEEP.
 4. THERE SHALL BE A MINIMUM OF 18 INCHES (457 MM)
 BETWEEN RAILS.
 5. RUNGS SHALL HAVE A MINIMUM 0.75-INCH (19 MM)
 DIAMETER AND BE CAPABLE OF WITHSTANDING A 300-POUND
 (136.1 KG) LOAD.
 6. LADDERS OVER 30 FEET (9144 MM) IN HEIGHT SHALL BE
 PROVIDED WITH OFFSET SECTIONS AND LANDINGS CAPABLE OF
 WITHSTANDING 100 POUNDS PER SQUARE FOOT (488.2 KG/M2).
 7. LADDERS SHALL BE PROTECTED AGAINST CORROSION BY
 APPROVED MEANS. CATWALKS INSTALLED TO PROVIDE THE
 REQUIRED ACCESS SHALL BE NOT LESS THAN 24-INCHES (610
 MM) WIDE AND SHALL HAVE RAILINGS AS REQUIRED FOR
 SERVICE PLATFORMS.
  
 10) IN VIEWING THE P. B. C. GEO MAPS THE 2ND STORY
 BUILDING THE NEW A/C UNITS ARE GOING TO BE INSTALLED ON
 DOES NOT HAVE A ELEVATED PARAPET. CERTAIN UNITS WILL BE
 WITHIN 10 FEET OF THE EDGE OF THE ROOF. SHOW COMPLIANCE
 WITH THE 2017 FBC-B SECTION:
 1013.7 ROOF ACCESS. GUARDS SHALL BE PROVIDED WHERE THE
 ROOF HATCH OPENING IS LOCATED WITHIN 10 FEET OF A ROOF
 EDGE OR OPEN SIDE OF A WALKING SURFACE AND SUCH EDGE OR
 OPEN SIDE IS LOCATED MORE THAN 30 INCHES ABOVE THE
 FLOOR, ROOF OR GRADE BELOW. THE GUARD SHALL BE
 CONSTRUCTED SO AS TO PREVENT THE PASSAGE OF A SPHERE 21
 INCHES (533 MM) IN DIAMETER.
  
 11) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-11-04 Cont ID  
Sent By jleahy Date 2019-11-04 Time 09:39 Rev Time 0.00
Received By jleahy Date 2019-11-04 Time 09:39 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2019-06-25 Cont ID  
Sent By jleahy Date 2019-06-25 Time 11:20 Rev Time 0.00
Received By jleahy Date 2019-06-25 Time 08:00 Sent To  
Notes
***NONE***

Review Stop E-LOWVOLT ELECTRICAL LOW VOLTAGE
Rev No 1 Status P Date 2019-06-25 Cont ID  
Sent By jleahy Date 2019-06-25 Time 11:20 Rev Time 0.00
Received By jleahy Date 2019-06-25 Time 11:20 Sent To  
Notes
2019-06-25 11:21:24DATA, TV, AND TELEPHONE ONLY JLEAHY

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-10-31 Cont ID  
Sent By pleduc Date 2019-10-31 Time   Rev Time 0.00
Received By pleduc Date 2019-10-31 Time 13:06 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2019-06-25 Cont ID  
Sent By pleduc Date 2019-06-25 Time   Rev Time 0.00
Received By pleduc Date 2019-06-10 Time 00:00 Sent To  
Notes
2019-06-25 10:02:08THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET A 1.0 - RM 110 A STO IS INDICATED WITH A
 ENTRANCE WALLL OF W1 AND REAR WALL OF W3. THE W2A WALL
 ENDS AT THE STO CORNER AND EXTENDS ALONG THE STO SIDE
 ENDING AT THE W3 WALL LEAVING THE W2A WALL PROTECTION
 BROKEN INSIDE THE STO ROOM. EITHER THE FRONT STO ROOM
 WALL AND DOOR NEED TO MEET THE W2A PROTECTION OF THE
 BACK W3 WALL NEEDS TO BE W2A.
  
 PLEASE REVIEW AND CORRECT OR JUSTIFY WITH SPECIFIC CODE
 REFERENCES.
  
  
  
 1A) THERE APPEARS TO BE CONFUSION WITH OCCUPANCY LOAD
 CALCULATIONS ARE NOTED IN BUILDING PLAN REVIEW
 COMMENTS.
  
 TO REDUCE DUPILCATE COMMENTS PLEASE ADDRESS THOSE
 COMMENTS.
  
  
  
  
 2) SHEET LS 1.0 - BUSINESS IS INDICATED AS THE MAIN
 OCCUPANCY; HOWEVER, IT IS CLEAR THAT EDUCATION IS THE
 MAIN OCCUPANCY AND OTHER ACCESSORY.
  
 PER NFPA 101
  
 6.1.3.1* DEFINITION ? EDUCATIONAL OCCUPANCY. AN
 OCCUPANCY USED
 FOR EDUCATIONAL PURPOSES THROUGH THE TWELFTH GRADE BY
 SIX OR MORE
 PERSONS FOR 4 OR MORE HOURS PER DAY OR MORE THAN 12
 HOURS PER WEEK.
  
 PLEASE REVIEW AND CORRECT OR JUSTIFY WITH SPECIFIC CODE
 REFERENCES.
  
  
  
 3) SHEET MK 7.1 - THERE IS AN INDICATION OF A HOOD
 SYSTEM. THE HOOD SYSTEM SHALL BE INSTALLED UNDER
 SEPARATE PERMIT AND SHOP DRAWINGS.
  
 PLEASE PROVIDE AN APPLICABLE NOTE OD SEPARATE PERMIT AS
 YOU DID FOR THE FIRE SUPPRESSION SYSTEM.
  
  
  
 4) E 3.1 - THERE IS NO INDICATION OF A PULL STATION ON
 THE WEST DOOR LEADING TOWARD THE AUDITORIUM. THOUGH THE
 FIRE ALARM IS UNDER SEPARATE PERMIT, PLEASE PROVIDE AND
 PULL STATION INDICATION HERE FOR REFERENCE PURPOSES.
  
 PER NFPA 101, CH 14 NEW EDUCATIONAL OCCUPANCIES AND CH
 9 BUILDING SERVICE AND FIRE PROTECTION EQUIPMENT
  
 14.3.4 DETECTION, ALARM, AND COMMUNICATIONS SYSTEMS.
 14.3.4.1 GENERAL.
 14.3.4.1.1 EDUCATIONAL OCCUPANCIES SHALL BE PROVIDED
 WITH A FIRE
 ALARM SYSTEM IN ACCORDANCE WITH SECTION 9.6.
  
 9.6.2.3 A MANUAL FIRE ALARM BOX SHALL BE PROVIDED AS
 FOLLOWS,
 UNLESS MODIFIED BY ANOTHER SECTION OF THIS CODE:
 (1) FOR NEW ALARM SYSTEM INSTALLATIONS, THE MANUAL FIRE
 ALARM
 BOX SHALL BE LOCATED WITHIN 60 IN. (1525 MM) OF EXIT
 DOORWAYS.
  
  
  
 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2020-01-26 Cont ID  
Sent By cpuell Date 2020-01-26 Time 09:26 Rev Time 0.00
Received By cpuell Date 2020-01-13 Time 12:49 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-12-20 Cont ID  
Sent By lmarchan Date 2019-12-20 Time 13:03 Rev Time 0.00
Received By lmarchan Date 2019-12-04 Time 14:28 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2019-11-14 Time   Rev Time 0.00
Received By lmarchan Date 2019-10-29 Time 13:12 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-07-03 Cont ID  
Sent By lmarchan Date 2019-07-03 Time 16:18 Rev Time 0.00
Received By lmarchan Date 2019-06-07 Time 16:40 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2019-06-19 Cont ID  
Sent By jwitmer Date 2019-06-19 Time 09:18 Rev Time  
Received By jwitmer Date 2019-06-19 Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2019-11-12 Cont ID  
Sent By ccole Date 2019-11-12 Time 15:35 Rev Time 0.00
Received By ccole Date 2019-11-12 Time 15:34 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-06-28 Cont ID  
Sent By ccole Date 2019-06-28 Time 10:52 Rev Time 0.00
Received By ccole Date 2019-06-27 Time 16:55 Sent To  
Notes
2019-06-28 11:26:431ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19051482
 6/28/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M2.1: SHOW THE DS DETECTOR IN THE SUPPLY
 SYSTEM OF RTU-1-4- SECTION 606.2.1 FBC M.
  
 2) M2.1, LS-1: NOTE #2 EXCEPTION TO SECTION 607.5.4
 CORRIDOR/SMOKE BARRIERS IS NOT RELEVANT TO SMOKE
 PARTITIONS. PLEASE REFER TO SECTION 607.5.7 AND CORRECT
 THE NOTE.
  
 3) M2.2: PROVIDE A MINIMUM 5' CLEARANCE FROM THE KEF-1
 DISCHARGE TO RTU-1-1 CURB- SECTION 506.3.13.3 EXCEPTION
 FBC M.
  
 4) M2.2: CORRECT NOTE #1- MINIMUM 4' SUPPORT SPACING
 FOR THE PVC CONDENSATE PIPING REQUIRED PER TABLE 305.4
 FBC M.
  
 5) M5.3 & S1.1: SUBMIT THE NOA FOR THE THYBAR CURB WITH
 SHOP DRAWING APPROVAL BY THE ENGINEER OF RECORD-
 SECTION 107.2.1 WPB.
  
 6) M5.3: SUBMIT NOA #16-0209.03 FOR THE FAN CURB ITH
 SHPOP DRAWING APPROVAL BY THE EOR- SECTION 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 BUILDING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2020-01-24 Cont ID  
Sent By gjohnson Date 2020-01-24 Time 18:35 Rev Time 0.00
Received By gjohnson Date 2020-01-24 Time 18:35 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2019-12-20 Cont ID  
Sent By tklarge Date 2019-12-20 Time 12:25 Rev Time 0.00
Received By tklarge Date 2019-12-16 Time 04:50 Sent To  
Notes
2019-12-20 12:00:441) SHT. 8 OF THE ENERGY CALCS NOTE THAT THE MINIMUM EF
 RATING IS .92. THE MINIMUM REQUIRED RATING IS .95 AS OF
 APRIL 16, 2015 PER THE DEPT. OF ENERGY CHANGE TO 10 CFR
 PART 430.32. PLEASE CHANGE THE MINIMUM EFFICIENCY TO
 READ THE MINIMUM OF .95. I AM AWARE THE THE UNIT BEING
 SUPPLIED GAS A DESIGN EF OF .98.
 2) SHT.LS 1.0 - TEACHING KITCHEN - THE PLAN SHOWS AN
 OCCUPANT LOAD AS 12 BUT THE OCCUPANT LOAD CALCULATION
 TABLE NOTES 19 UNDER THE 2017 FBC HEADING. CLARIFY.
 3) SHT. P1.1 - KEYNOTE #1 STATES THE SANITARY DRAIN TO
 CONNECT TO THE GREASE WASTE SYSTEM. THE SANITARY CANNOT
 CONNECT TO THE GREASE WASTE SYSTEM PER 2017
 FBC-PLUMBING SEC.1003.2. THIS IS OBVIOUSLY A
 TYPOGRAPHICAL ERROR AS THE PLAN SHOWS THE CORRECT
 ARRANGEMENT. REVISE THE NOTE.
 4) SHT. P1.1 - REFERS TO CIVIL PLANS FOR THE BUILDING
 SEWER. CIVIL PLANS HAVE NOT BEEN INCLUDED IN THIS
 SUBMITTAL. CLARIFY.
 5) SIZE THE VENT STACK BY THE ICE MACHINE.
 6) SHT. P-2.1 - REFERS TO A ONE INCH DOMESTIC WATER
 SUPPLY LINE BUT THE PLAN SHOWS AN ONE AND ONE-QUARTER
 INCH LINE. CLARIFY.
 7) SHT. P-3.1 - DETAIL #1 - EACH WELL OF A MULTIPLE
 COMPARTMENT SINK SHALL DISCHARGE INDEPENDENTLT TO A
 WASTE RECEPTOR. 2017 FBC-PLUMBING SEC.802.1.1.
 8) THE HOT WATER RETURN LINE SHALL BE INSTALLED IN
 ACCORDANCE WITH THE 2017 FBC-PLUMBING SEC.607.2.2.
 9) THE PREVIOUS REVIEW REFERS TO THE GREASE WASTE
 SYSTEM AS DESIGNED AS A COMBINATION WATSE AND VENT
 SYSTEM WHICH PROHIBITS THE DISCHARGE FROM A FOOD WASTE
 DISPOSER PER 2017 FBC-PLUMBING SEC.915.1.. THERE IS NOT
 EXCEPTION FOR THE USE OF A SOLIDS INTERCEPTOR AS AN
 EXCEPTION OR ALTERNATIVE METHOD. THE
 MAINTENANCE/CLEANING OF SUCH SOLIDS INTERCEPTOR CANNOT
 BE MONITORED FOR COMPLIANCE THEREFORE THE FOOD DISPOSER
 INSTALLATION IS PROHIBITED.
  
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2019-11-14 Cont ID  
Sent By gjohnson Date 2019-11-14 Time 16:56 Rev Time 0.00
Received By gjohnson Date 2019-11-08 Time 14:23 Sent To  
Notes
2019-11-14 16:57:582ND REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. THIS APPEARS TO BE A COMBINATION WASTE VENT SYSTEM A
 COMBINATION WASTE AND VENT SYSTEMS SHALL NOT RECEIVE
 THE DISCHARGE FROM A FOOD WASTE DISPOSER. IN ORDER FOR
 THIS SYSTEM TO BE CODE COMPLIANT A VENT IS REQUIRED
 BETWEEN THE TWO MOST UPSTREAM FIXTURES UPSTREAM OF THE
 FLOOR SINK RECEIVING THE DISCHARGE FROM THE DISPOSER
 CREATING A CIRCUIT VENT. PER FBC PL 915.1 AND 914.2
  
 2. WHAT IS THE WCB-1 WATER COOLER BEING USED FOR IT IS
 NOT SHOWN WITH A DRAIN PROVIDE MANUFACTURE
 SPECIFICATION TO CLARIFY.PER WPB AMEND TO FBC 107.2.1
  
 3. A BACKFLOW DEVISE IS REQUIRED ON THE ICE MACHINE
 WATER FILTER SUPPLY LINE. PER FBC PL 608.3
  
 4. PREVIOUS COMMENT A TRAP PRIMER IS REQUIRED ON THE
 FLOOR DRAIN IN THE PANTRY. PER FBC PL 1002.4.1
  
 PLAN MAY BE APPROVED BY PROVISO IF COMMENTS ARE
 ADDRESSED IN WRITING BY DESIGN PROFESSIONAL OF RECORD
 AND PROVISO IS REQUESTED PLEASE CONTACT ME WITH ANY
 QUESTIONS.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-06-21 Cont ID  
Sent By gjohnson Date 2019-06-21 Time 08:11 Rev Time 0.00
Received By gjohnson Date 2019-06-20 Time 13:30 Sent To  
Notes
2019-06-21 08:11:421ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. THE TRAINING KITCHEN SHALL COMPLY WITH FBC ACC 804
 PER FBC ACC 212.2 PLEASE SHOW COMPLIANCE WITH ALL
 SECTIONS OF 804
  
 2. THE THREE COMP SINK SHALL COMPLY WITH FBC ACC 606.2
  
 3. SHT. P1.2, P2.1, P2.2 THE SHEETS DID NOT LOAD
 PROPERLY THE LABELS ON SOME OF THE FIXTURES ON THE
 ISOMETRIC DRAWING ARE MISSING AND THE FIXTURES IN THE
 CLASS ROOMS ARE MISSING LABELS PLEASE CLARIFY. PER WPB
 AMEND TO FBC 107.2.1
  
 4. A LINT INTERCEPTOR IS REQUIRED ON THE WASHING
 MACHINE PER FBC PL 1003.6
  
 5. PLEASE SHOW TRAP PRIMERS ON THE SANITARY ISOMETRIC .
 PER FBC PL 1002.4.1
  
 6. SHT P2.2 SHUT OFF VALVES ARE REQUIRED ON ALL HOT AND
 COLD DROPS PLEASE SHOW ON THE ISOMETRIC DRAWINGS PER
 FBC PL 606.1(5)
  
 7. WHAT IS THE M1 SHOWN IN THE CLASSROOMS THEY ARE ONLY
 SHOWN ON THE WATER RISER AND FLOOR PLAN NOT ON THE
 SANITARY PLEASE CLARIFY PER WPB AMEND TO FBC 107.2.1
  
 8. SHT. P3.1 DETAIL SHOWS A MIXING VALVE WITH A 110
 DEG. LINE THAT IS NOT SHOWN ON THE WATER PLAN OR
 ISOMETRIC PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 9. SHT. P0.0 THE PLUMBING FIXTURE SCHEDULE IS CALLING
 OUT A WATER COOLER FOR IM-1 THE REST OF THE PLAN SHOWS
 AN ICE MACHINE PLEASE CLARIFY. PER WPB AMEND TO FBC
 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2020-01-22 Cont ID  
Sent By pvalenti Date 2020-01-22 Time 14:38 Rev Time 0.00
Received By pvalenti Date 2020-01-22 Time 14:38 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2019-12-13 Cont ID  
Sent By shill Date 2019-12-13 Time 09:37 Rev Time 0.00
Received By shill Date 2019-12-13 Time 09:37 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2019-11-14 Cont ID  
Sent By jwitmer Date 2019-11-14 Time 17:20 Rev Time 0.00
Received By jwitmer Date 2019-11-14 Time 17:20 Sent To  
Notes
2019-11-12 15:37:06NEW MECH PLANS OK.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2019-07-03 Cont ID  
Sent By shill Date 2019-07-03 Time 15:13 Rev Time 0.00
Received By shill Date 2019-07-03 Time 15:13 Sent To  
Notes
2019-12-20 12:29:12DIGITAL SIGNATURE ON PLUMBING SHEETS OK. T.LARGE
2019-07-03 15:13:42DIGITAL SIGNATURES OK, NEW PAGES SUBMITTED NEXT REVIEW
 CYCLE NEED VERIFICATION
  
2019-06-28 11:34:04MECH PLANS OK

Review Stop Z ZONING
Rev No 1 Status P Date 2019-07-03 Cont ID  
Sent By jroach Date 2019-07-03 Time 16:10 Rev Time 0.00
Received By jroach Date 2019-07-03 Time 15:42 Sent To  
Notes
***NONE***