Plan Review Details - Permit 19051456
Plan Review Stops For Permit 19051456
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2019-12-04 Cont ID  
Sent By dbattles Date 2019-12-04 Time 13:35 Rev Time 0.00
Received By dbattles Date 2019-12-04 Time 13:35 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-10-29 Cont ID  
Sent By jwitmer Date 2019-10-29 Time 10:24 Rev Time 0.00
Received By jwitmer Date 2019-10-28 Time 16:22 Sent To  
Notes
2019-10-29 10:13:162017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19051456
 ADD: 2711 EXCHANGE COURT
 CONT: TBD/ TO BE DETERMINED
 TEL: 786-488-4714
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: TUES. OCT. 29/2019
 ACTION: DENIED
  
 NOTE: NEW DESIGNER OF RECORD.
 1) IN THE ARCHITECTS TITLEBLOCK WITHIN THE SEAL IT
 APPEARS THE ARCHITECT HAS USED A RUBBER STAMP
 SIGNATURE, NOT AN ORIGINAL SINCE THEY ARE EXACTLY THE
 SAME ON EACH SHEET. DEFINITION OF SIGNATURE: A
 SIGNATURE IS A HANDWRITTEN (AND OFTEN STYLIZED)
 DEPICTION OF SOMEONE'S NAME OR EVEN A SIMPLE "X" OR
 OTHER MARK THAT A PERSON WRITES ON DOCUMENTS AS A PROOF
 OF IDENTITY AND INTENT. FLORIDA STATUTE 481 REQUIRES A
 SIGNATURE (HANDWRITTEN).
 F. S. 481.221(4) NO REGISTERED ARCHITECT SHALL AFFIX,
 OR PERMIT TO BE AFFIXED, HER OR HIS SEAL OR SIGNATURE
 TO ANY FINAL CONSTRUCTION DOCUMENT OR INSTRUMENT OF
 SERVICE WHICH INCLUDES ANY PLAN, SPECIFICATION,
 DRAWING, OR OTHER DOCUMENT WHICH DEPICTS WORK WHICH SHE
 OR HE IS NOT COMPETENT TO PERFORM.
  
 2) THE COVERSHEET LIST FOR SUITE: A AN EDUCATIONAL
 OCCUPANCY. INDICATE THE USAGE?
  
 2A)(1) THE MAJOR PORTION OF THE SQUARE FOOTAGE OF THIS
 TENANT SPACE 2584 SQ. FT. AS OPEN GYM. PLEASE PROVIDE
 WHAT AGE GROUP ARE USING THIS FACILITY. IS THIS GYM
 ASSOCIATED WITH A SCHOOL?
 2017 FBC-B SECTION 305.1 EDUCATIONAL GROUP E.
 EDUCATIONAL GROUP E OCCUPANCY INCLUDES, AMONG OTHERS,
 THE USE OF A BUILDING OR STRUCTURE, OR A PORTION
 THEREOF, BY SIX OR MORE PERSONS AT ANY ONE TIME FOR
 EDUCATIONAL PURPOSES THROUGH THE 12TH GRADE.
  
 2A)(2) THE OPEN GYM WITH A SQUARE FOOTAGE OF 2584 SQ.
 FEET AS INDICATED ON THE COVERSHEET ALSO STATES AN
 OCCUPANT LOAD FACTOR OF 20 NET. THIS OCCUPANT LOAD
 FACTOR IS TAKEN FOR A CLASSROOM SETTING WITH DESK AND
 CHAIRS. PLEASE REVIEW IN THE 2017 FBC-B TABLE 1004.1.2
 FOR EXERCISE ROOMS AN OCCUPANT LOAD FACTOR OF 50 GROSS
 SHOULD BE TAKEN.
  
 2A)(3) TO TAKE THE OCCUPANT LOAD FACTOR FOR A GYM YOU
 WILL NEED TO PROVIDE AN EQUIPMENT LAYOUT OF THE
 EQUIPMENT. TABLE 1004.1.2.
  
 2A)(4) PLEASE ALSO REVIEW THE REQUIREMENTS UNDER THE
 2017 FBC-ACCESSIBILITY CODE FOR EXERCISE MACHINES AND
 EQUIPMENT SECTION 1004.1 CLEAR FLOOR SPACE. EXERCISE
 MACHINES AND EQUIPMENT SHALL HAVE A CLEAR FLOOR SPACE
 COMPLYING WITH 305 POSITIONED FOR TRANSFER OR FOR USE
 BY AN INDIVIDUAL SEATED IN A WHEELCHAIR. CLEAR FLOOR OR
 GROUND SPACES REQUIRED AT EXERCISE MACHINES AND
 EQUIPMENT SHALL BE PERMITTED TO OVERLAP.
  
 2B) IS THIS TENANT SPACE GOING TO BE USED AS A DAYCARE?
 2017 FBC-B SECTION 305.2 GROUP E, DAY CARE FACILITIES.
 THIS GROUP INCLUDES BUILDINGS AND STRUCTURES OR
 PORTIONS THEREOF OCCUPIED BY MORE THAN FIVE CHILDREN
 OLDER THAN 21/2 YEARS OF AGE WHO RECEIVE EDUCATIONAL,
 SUPERVISION OR PERSONAL CARE SERVICES FOR FEWER THAN 24
 HOURS PER DAY.
  
 2C) THE COVERSHEET ALSO LIST OFFICE/ VOCATIONAL
 TRAINING WITH1623 SQUARE FEET, AN AND OCCUPANT LOAD
 FACTOR OF 50 NET. PLEASE PROVIDE ADDITIONAL INFORMATION
 AS TO WHAT AGE GROUP WILL BE ATTENDING AND RECEIVING
 VOCATIONAL TRAINING? SEE THE 2017 FBC-B SECTION:
 304.1 BUSINESS GROUP B OCCUPANCIES INCLUDE : TRAINING
 AND SKILL DEVELOPMENT NOT IN A SCHOOL OR ACADEMIC
 PROGRAM (THIS SHALL INCLUDE, BUT NOT BE LIMITED TO,
 TUTORING CENTERS, MARTIAL ARTS STUDIOS, GYMNASTICS AND
 SIMILAR USES REGARDLESS OF THE AGES SERVED, AND WHERE
 NOT CLASSIFIED AS A GROUP A OCCUPANCY.
  
 3) SHEET A-2 THE FLOOR PLAN FOR SUITES A & B AND A4
 RESTROOM ELEVATIONS ARE ALL WRONG FOR ACCESSIBILITY TO
 THE WATERCLOSET FOR AN ACCESSIBLE RESTROOM. PLEASE
 REVIEW THE 2017 ACCESSIBILITY CODE SECTIONS:
  
 3A) WATER CLOSET. 604.3.1 SIZE. CLEARANCE AROUND A
 WATER CLOSET SHALL BE 60 INCHES (1525 MM) MINIMUM
 MEASURED PERPENDICULAR FROM THE SIDE WALL AND 56 INCHES
 (1420 MM) MINIMUM MEASURED PERPENDICULAR FROM THE REAR
 WALL.
  
 3B) 604.3.2 OVERLAP. THE REQUIRED CLEARANCE AROUND THE
 WATER CLOSET SHALL BE PERMITTED TO OVERLAP THE WATER
 CLOSET, ASSOCIATED GRAB BARS, DISPENSERS, SANITARY
 NAPKIN DISPOSAL UNITS, COAT HOOKS, SHELVES, ACCESSIBLE
 ROUTES, CLEAR FLOOR SPACE AND CLEARANCES REQUIRED AT
 OTHER FIXTURES, AND THE TURNING SPACE. NO OTHER
 FIXTURES OR OBSTRUCTIONS SHALL BE LOCATED WITHIN THE
 REQUIRED WATER CLOSET CLEARANCE.
  
 3C) THE REAR WALL OF THE RESTROOM SHOWS THE REAR GRAB
 BAR BUT THERE ARE NO HORIZONTAL DIMENSIONS SHOWING
 COMPLIANCE WITH:
 2017 ACCESSIBILITY CODE 604.5.2 REAR WALL. THE REAR
 WALL GRAB BAR SHALL BE 36 INCHES (915 MM) LONG MINIMUM
 AND EXTEND FROM THE CENTERLINE OF THE WATER CLOSET 12
 INCHES (305 MM) MINIMUM ON ONE SIDE AND 24 INCHES (610
 MM) MINIMUM ON THE OTHER SIDE.
  
 3D) THE SINKS WILL ALSO NEED TO SHOW COMPLIANCE WITH:
 2017 ACCESSIBILITY CODE 606.5 EXPOSED PIPES AND
 SURFACES. WATER SUPPLY AND DRAIN PIPES UNDER LAVATORIES
 AND SINKS SHALL BE INSULATED OR OTHERWISE CONFIGURED TO
 PROTECT AGAINST CONTACT. THERE SHALL BE NO SHARP OR
 ABRASIVE SURFACES UNDER LAVATORIES AND SINKS.
  
 4) SHEET A2 NEW OFFICE # 6 SHOW A NEW GLAZED WINDOW
 WITHIN 2 FEET OF THE DOOR. PLEASE SHOW COMPLIANCE WITH
 2406.4.2 GLAZING ADJACENT TO DOORS. GLAZING IN AN
 INDIVIDUAL FIXED OR OPERABLE PANEL ADJACENT TO A DOOR
 WHERE THE NEAREST VERTICAL EDGE OF THE GLAZING IS
 WITHIN A 24-INCH (610 MM) ARC OF EITHER VERTICAL EDGE
 OF THE DOOR IN A CLOSED POSITION AND WHERE THE BOTTOM
 EXPOSED EDGE OF THE GLAZING IS LESS THAN 60 INCHES
 (1524 MM) ABOVE THE WALKING SURFACE SHALL BE CONSIDERED
 A HAZARDOUS LOCATION.
  
 5A) SHEET A2 SHOWS A LUNCHROOM / CAFETERIA. THERE ARE
 NO ELEVATIONS FOR THIS ROOM COMPLIANCE CAN NOT BE
 REVIEWED FOR: 2017 ACCESSIBILITY CODE SECTION 2017
 FBC-ACCESSIBILITY CODE SECTION 606.3 HEIGHT. LAVATORIES
 AND SINKS SHALL BE INSTALLED WITH THE FRONT OF THE
 HIGHER OF THE RIM OR COUNTER SURFACE 34 INCHES MAXIMUM
 ABOVE THE FINISH FLOOR OR GROUND.
  
 5B) 2017 FBC-ACCESSIBILITY CODE 606.2 CLEAR FLOOR
 SPACE. A CLEAR FLOOR SPACE COMPLYING WITH 305,
 POSITIONED FOR A FORWARD APPROACH, AND KNEE AND TOE
 CLEARANCE COMPLYING WITH 306 SHALL BE PROVIDED.
  
 EXCEPTIONS: 1.A PARALLEL APPROACH COMPLYING WITH 305
 SHALL BE PERMITTED TO A KITCHEN SINK, IN A SPACE WHERE
 A COOK TOP OR CONVENTIONAL RANGE IS NOT PROVIDED, AND
 TO WET BARS.
  
 6) SHEET A2 SHOWS A LUNCHROOM / CAFETERIA. THERE IS NO
 FURNITURE PLAN FOR THIS ROOM COMPLIANCE CANNOT BE
 REVIEWED FOR: 2017 ACCESSIBILITY CODE SECTIONS:
  
 6A ) 902.1 .DINING SURFACES AND WORK SURFACES SHALL
 COMPLY WITH 902.2 AND 902.3. ADVISORY 902.1 GENERAL.
 DINING SURFACES INCLUDE, BUT ARE NOT LIMITED TO, BARS,
 TABLES, LUNCH COUNTERS, AND BOOTHS. EXAMPLES OF WORK
 SURFACES INCLUDE WRITING SURFACES, STUDY CARRELS,
 STUDENT LABORATORY STATIONS, BABY CHANGING AND OTHER
 TABLES OR FIXTURES FOR PERSONAL GROOMING, COUPON
 COUNTERS, AND WHERE COVERED BY THE ADA SCOPING
 PROVISIONS, EMPLOYEE WORK STATIONS.
  
 6A)(1) 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR
 SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD
 APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED.
  
 6A)(2) 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND
 WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 7) ARE ALL OF THE EXITS LEVEL WITH THE EXTERIOR GRADE,
 NOT SHOWN ON THE PLANS? 2017 ACCESS. CODE 206.4.1
 PUBLIC ENTRANCES. IN ADDITION TO ENTRANCES REQUIRED BY
 206.4.2 THROUGH 206.4.9, AT LEAST 60 PERCENT OF ALL
 PUBLIC ENTRANCES SHALL COMPLY WITH 404.
 2017 FBC-ACCESSIBILITY CODE SECTION 207.1 MEANS OF
 EGRESS SHALL COMPLY WITH SECTION 1003.2.13 OF THE
 INTERNATIONAL BUILDING CODE (2000 EDITION AND 2001
 SUPPLEMENT) OR SECTION 1007 OF THE INTERNATIONAL
 BUILDING CODE (2003 EDITION).
 2003 IBC-B 1007.1 WHERE MORE THAN ONE MEANS OF EGRESS
 IS REQUIRED BY SECTIONS 1014.1 OR 1018.1 FROM ANY
 ACCESSIBLE SPACE, EACH ACCESSIBLE PORTION OF THE SPACE
 SHALL BE SERVED BY NOT LESS THAN TWO MEANS OF EGRESS.
  
 8) AT THIS TIME A OCCUPANCY CANNOT BE DETERMINED, FOR
 DAYCARE AND EDUCATIONAL OCCUPANCIES CHAPTER 4 OF THE
 FBC-B 2017 HAS SEPARATE REQUIREMENTS FOR THESE
 OCCUPANCIES:
 DAYCARE OCCUPANCIES SECTION 466
 SCHOOLS: KINDERGARTEN THROUGH THE 12 GRADE SECTION 468.
  
 9) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-07-08 Cont ID  
Sent By jwitmer Date 2019-07-08 Time 08:08 Rev Time 0.00
Received By jwitmer Date 2019-07-08 Time 06:19 Sent To  
Notes
2019-07-08 08:08:142017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19051456
 ADD: 2711 EXCHANGE COURT
 CONT: TBD/ TO BE DETERMINED
 TEL: 786-488-4714
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. JULY 09/2019
 ACTION: DENIED
  
 1) FIRE SAFETY FLOOR PLAN MISSING INFORMATION:
 1A) THE COVERSHEET & LIFE SAFETY/ FIRE SAFETY FLOOR
 PLAN INDICATE THE PLANS WERE DESIGNED TO THE 2017
 EXISTING BUILDING CODE & BUILDING CODE. WHAT THE PLANS
 ARE MISSING AS UNDER THE 2017 EXISTING BUILDING CODE
 WHAT METHOD LISTED IN SECTIONS 301.1.1 THROUGH 301.1.3
 DID THE DESIGNER OF RECORD USE?
  
 1B) ON THE COVERSHEET UNDER THE HEADING CODE
 INFORMATION THE PLANS STATE THE PLANS WERE ALSO
 DESIGNED TO PALM BEACH COUNTY LOCAL AMENDMENTS. PLEASE
 BE AWARE THIS PROJECT IS LOCATED IN THE CITY LIMITS OF
 WEST PALM BEACH, FLORIDA AND SUBJECT TO THE 2017 WEST
 PALM BEACH AMENDMENTS (CHAPTER 1 ADMINISTRATION) TO THE
 FLORIDA BUILDING CODE, NOT THE COUNTY AMENDMENTS.
 PLEASE UPDATE PLANS.
  
 1C) THE 2017 WEST PALM BEACH AMENDMENTS (CHAPTER 1
 ADMINISTRATION)TO THE FLORIDA BUILDING CODE
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1. BUILDING.
 OCCUPANCY TYPE
 MINIMUM TYPE OF CONSTRUCTION
 OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE:
 OCCUPANCY LOAD
 GROSS
 NET
 FIRE SPRINKLERED OR NOT / REQUIRED?
  
 1D) NEITHER THE COVERSHEET NOR THE LIFE SAFETY/ FIRE
 SAFETY FLOOR PLAN INDICATE TO WHAT SCALE THE PLANS WERE
 DRAWN TOO? 107.2.1.3 QUALITY OF BUILDING PLANS.
 BUILDING PLANS SHALL BE DRAWN TO A MINIMUM 1/8
 INCH SCALE.
  
 1E) THE DESIGNER OF RECORD LIST ON THE LIFE SAFETY/
 FIRE SAFETY FLOOR PLAN INDICATES THE DEMISING WALL IS
 TO BE A 2 HOUR FIRE RATED WALL A DESCRIPTION OF THE
 COMPONENTS IS GIVEN BUT NOT THE LISTING OF THE ASSEMBLY
 NOR THE SIZE AND SPACING FOR THE FASTENERS.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. CONSTRUCTION DOCUMENTS SHALL BE
 OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT
 IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
 2017 FBC-B SECTION 708.3 & 708.4. FIRE PARTITIONS AND
 CONTINUITY.
  
 1F) THERE ARE 2 NOTES DEALING WITH JOINTS AND OR
 OPENINGS WITHIN THE 2 HOUR FIRE RATED WALL. 1ST)
 PROVIDE FIRER RETARDANT FOAM CAULKING FOR AREAS, THE
 2ND) USE FIRE RETARDANT COMPOUND TO SEAL ANY OPENINGS
 IN THE FIRE RATED WALL.
 2017 FBC-B 715.1. JOINTS INSTALLED IN OR BETWEEN
 FIRE-RESISTANCE-RATED WALLS, SHALL BE PROTECTED BY AN
 APPROVED FIRE-RESISTANT JOINT SYSTEM DESIGNED TO RESIST
 THE PASSAGE OF FIRE FOR A TIME PERIOD NOT LESS THAN THE
 REQUIRED FIRE-RESISTANCE RATING OF THE WALL BETWEEN
 WHICH THE SYSTEM IS INSTALLED. FIRE-RESISTANT JOINT
 SYSTEMS SHALL BE TESTED IN ACCORDANCE WITH SECTION
 715.3. PLEASE PROVIDE DOCUMENTATION OF APPROVAL. IF
 THIS IS TO LEFT TO THE CONTRACTOR THEN THE SYSTEM WILL
 NEED TO HAVE THE DESIGNER OF RECORD APPROVAL (SHOP
 DRAWING STAMP OF APPROVAL) BEFORE BEING SUBMITTED TO
 THE BUILDING DEPARTMENT BEFORE THE INSTALLATION OF THE
 PRODUCT. THE FIRE-RESISTANT JOINT SYSTEMS SHALL BE
 TESTED IN ACCORDANCE WITH SECTION 715.3.
  
 1G) THE PLANS INDICATE A 2 HOUR TENANT SEPARATION WALL
 IS TO BE INSTALLED BUT THE WALL DOES NOT INDICATE A 2
 HOUR RATING FROM EXTERIOR WALL TO THE OPPOSITE EXTERIOR
 WALL. THE FOYER IS IN QUESTION IT COULD BE A COMMON
 ELEMENT TO BOTH TENANTS? THE OTHER ISSUE IS WHEN YOU
 GET INTO THE RESTROOMS THERE ARE NO NEW WALLS SHOWN OR
 FIRE RATING. THE SAME SYMBOL IS USED FOR NEW WALLS AND
 THE 2 HOUR FIRE RATED WALLS.
 107.2.1.2. ADDITIONAL INFORMATION IS REQUIRED.
  
 1H) WITHIN THIS SET OF PLANS THERE IS NO DOOR
 IDENTIFICATION TAGS OR DOOR SCHEDULE TO SHOW COMPLIANCE
 WITH SECTION 1010.1.1. SIZE OF DOORS OF THE 2017 FBC-B.
  
 1I) IN THE 2 HOUR FIRE RATED WALL THERE IS AT LEAST ONE
 DOOR OPENING THAT WOULD NEED TO HAVE A FIRE RATING
 COMPLYING WITH 2017 FBC-B TABLE 716.5.
  
 THE FLOOR PLAN DOES NOT INDICATE THE OCCUPANT LOAD FOR
 OFFICE A. BUT THE OFFICE A IS OVER 5,000 SQ. FT.
 REQUIRING 2 EXITS. PLEASE SHOW THE ACCESSIBLE 2
 REQUIRED EXITS.
  
 2017 FBC-ACCESSIBILITY CODE SECTION 207.1 MEANS OF
 EGRESS SHALL COMPLY WITH SECTION 1003.2.13 OF THE
 INTERNATIONAL BUILDING CODE (2000 EDITION AND 2001
 SUPPLEMENT) OR SECTION 1007 OF THE INTERNATIONAL
 BUILDING CODE (2003 EDITION).
  
 2003 IBC-B 1007.1 WHERE MORE THAN ONE MEANS OF EGRESS
 IS REQUIRED BY SECTIONS 1014.1 OR 1018.1 FROM ANY
 ACCESSIBLE SPACE, EACH ACCESSIBLE PORTION OF THE SPACE
 SHALL BE SERVED BY NOT LESS THAN TWO MEANS OF EGRESS.
  
 THE GOOGLE MAPS SHOWS THE FRONT ENTRY WITH A RAMP BUT
 NO TOP LANDING, PLEASE PROVIDE THE RISE AND RUN OF THE
 EXISTING RAMP TO SEE IF THIS IS A CODE COMPLIANT RAMP.
 THERE ARE 2 OTHER EXITS SHOWN ON THE PLANS BUT NEITHER
 OF THESE EXITS HAVE A RAMP EGRESS COMPONENT.
  
 1J) THE VALUE OF THIS PROJECT IS INDICATED AS
 $80,000.00 DOLLARS IN VALUE. PLEASE SHOW WHERE UP TO
 20% ($16,000.00) OF THIS VALUE WILL BE USED IN
 ACCESSIBLE UPGRADES TO THE PROJECT AND AS IN ORDER AS
 LISTED
 BELOW. EITHER THE DESIGNER OF RECORD OR THE CONTRACTOR
 WILL NEED TO SUBMIT ON THEIR LETTERHEAD WHERE THE FUNDS
 WILL BE SPENT.
 2017 FBC-ACCESSIBILITY CODE. 202.4.2 ACCESSIBLE
 FEATURES IN THE EVENT OF DISPROPORTIONALITY.
  
 WHEN THE COST OF ALTERATIONS NECESSARY TO MAKE THE PATH
 OF TRAVEL TO THE ALTERED AREA FULLY ACCESSIBLE IS
 DISPROPORTIONATE TO THE COST OF THE OVERALL ALTERATION,
 THE PATH OF TRAVEL SHALL BE MADE ACCESSIBLE TO THE
 EXTENT THAT IT CAN BE MADE ACCESSIBLE WITHOUT INCURRING
 DISPROPORTIONATE COSTS. IN CHOOSING WHICH ACCESSIBLE
 ELEMENTS TO PROVIDE, PRIORITY SHOULD BE GIVEN TO THOSE
 ELEMENTS THAT WILL PROVIDE THE GREATEST ACCESS, IN THE
 FOLLOWING ORDER: (I) AN ACCESSIBLE ENTRANCE; (II) AN
 ACCESSIBLE ROUTE TO THE ALTERED AREA; (III) AT LEAST
 ONE ACCESSIBLE RESTROOM FOR EACH SEX OR A SINGLE UNISEX
 RESTROOM; (IV) ACCESSIBLE TELEPHONES; (V) ACCESSIBLE
 DRINKING FOUNTAINS; AND (VI) WHEN POSSIBLE, ADDITIONAL
 ACCESSIBLE ELEMENTS SUCH AS PARKING, STORAGE, AND
 ALARMS.
  
 1K) THE FLOOR PLAN INDICATES THE OFFICE CAFETERIA IS
 EXISTING COMPLIANCE WITH AN ACCESSIBLE SINK CANNOT BE
 DETERMINED NOR IF THERE IS A MICROWAVE BUILT INTO THE
 UPPER CABINETS?
 SINKS. 2017 FBC-ACCESSIBILITY CODE SECTION 606.3
 HEIGHT. SINKS SHALL BE INSTALLED WITH THE FRONT OF THE
 HIGHER OF THE RIM OR COUNTER SURFACE 34 INCHES MAXIMUM
 ABOVE THE FINISH FLOOR OR GROUND.
  
 308 REACH RANGES. 308.2 FORWARD REACH. / 308.2.1
 UNOBSTRUCTED/ 308.2.2 OBSTRUCTED HIGH REACH.
 308.3 SIDE REACH. / 308.3.1 UNOBSTRUCTED/ 308.3.2
 OBSTRUCTED HIGH REACH.
  
 309 OPERABLE PARTS. 309.3 HEIGHT. OPERABLE PARTS SHALL
 BE PLACED WITHIN ONE OR MORE OF THE REACH RANGES
 SPECIFIED IN 308. 309.4 OPERATION. OPERABLE PARTS SHALL
 BE OPERABLE WITH ONE HAND AND SHALL NOT REQUIRE TIGHT
 GRASPING, PINCHING, OR TWISTING OF THE WRIST. THE FORCE
 REQUIRED TO ACTIVATE OPERABLE PARTS SHALL BE 5 POUNDS
 MAXIMUM.
  
 2) THE ACCESSIBLE RESTROOMS ARE NOT SHOWN ON THE LIFE
 SAFETY/ FIRE FLOOR PLAN BUT IN THE PLUMBING SHEET P1.
 2A) PLEASE NOTE THE GRAB BARS FOR THE WATER CLOSET ARE
 SHOWN TO BE MEASURED FROM THE FINISH FLOOR TO THE
 CENTER OF THE GRAB BAR. PLEASE NOTE UNDER THE 2010
 ACCESSIBILITY CODE THE GRAB BARS ARE TO BE MEASURED TO
 THE TOP OF THE GRASPABLE SURFACE NOT CENTER LINED. 2017
 FBC-ACCESSIBILITY CODE SECTION 609.4 POSITION OF GRAB
 BARS. GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL
 POSITION, 33 INCHES MINIMUM AND 36 INCHES MAXIMUM ABOVE
 THE FINISH FLOOR MEASURED TO THE TOP OF THE GRIPPING
 SURFACE, NOT CENTERLINE.
  
 2B) MIRRORS. 2017 FBC-ACCESSIBILITY CODE 603.3 MIRRORS.
 MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL
 BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING
 SURFACE 40 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR
 GROUND. MIRRORS NOT LOCATED ABOVE LAVATORIES OR
 COUNTERTOPS SHALL BE INSTALLED WITH THE BOTTOM EDGE OF
 THE REFLECTING SURFACE 35 INCHES MAXIMUM ABOVE THE
 FINISH FLOOR OR GROUND.
  
 2C) PLEASE PROVIDE THE DIMENSIONS FOR THE BACKWALL OF
 THE ACCESSIBLE RESTROOMS ON THE FLOOR PLAN. IT APPEARS
 THAT THE DETAIL # 2 IS CORRECT AS FAR AS A CLEAR
 OVERLAP FOR THE WATER CLOSET BUT THE FLOOR PLAN DOES
 NOT SHOW COMPLIANCE WITH THE 2017 ACCESS. CODE SECTION
 604.3.1 SIZE. CLEARANCE AROUND A WATER CLOSET SHALL BE
 60 INCHES MINIMUM MEASURED PERPENDICULAR FROM THE SIDE
 WALL AND 56 INCHES MINIMUM MEASURED PERPENDICULAR FROM
 THE REAR WALL.
  
 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2020-01-23 Cont ID  
Sent By gjohnson Date 2020-01-24 Time 12:03 Rev Time 0.00
Received By jpearson Date 2020-01-23 Time 14:34 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2019-12-04 Cont ID  
Sent By jpearson Date 2019-12-04 Time 09:22 Rev Time 0.00
Received By jpearson Date 2019-12-04 Time 09:22 Sent To  
Notes
2019-12-04 09:22:18CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. CORRECTED.
 2. CORRECTED.
 3. PROVIDE THE ADDITIONAL AUTOMATIC LIGHTING CONTROLS
 STIPULATED IN THE FBC ENERGY CODE. FBC EC C405.2 (NOT
 CORRECTED, NO RESPONSE PROVIDED.)
  
 NEW COMMENTS:
  
 4. PROVIDE CLARIFICATION FOR RISER DIAGRAM. RISER SHOWS
 AN EXISTING PANEL B WITH A J-BOX UNDERNEATH THAT WILL
 FEED NEW PANEL A, BUT THE RISER ALSO SHOWS AN EXISTING
 PANEL A. WILL PANEL B REMAIN, OR WILL IT BE
 REPLACED/RELOCATED? WILL THERE BE TWO PANEL A'S? THE
 RISER IS CONFUSING. PROVIDE CORRECTIONS. NEC 215.5; WPB
 FBC 107.2.1
 5. AN EQUIPMENT GROUNDING CONDUCTOR IS REQUIRED TO BE
 INSTALLED AFTER THE FIRST MEANS OF DISCONNECT. PROVIDE
 CORRECTION. NEC 250.24, 250.110, 250.118, 250.122
 6. FOR RE-WORK OF ELECTRICAL SERVICE, PROVIDE AVAILABLE
 SHORT CIRCUIT CALCULATION FOR SERVICE INCLUDING
 INFORMATION FROM THE POWER COMPANY STATING WHAT THE
 AVAILABLE SHORT CIRCUIT CURRENT IS FOR THE SERVICE TO
 CONFIRM THE STATED AIC RATING OF THE SERVICE EQUIPMENT
 IS ADEQUATE. NEC 110.9, 110.10
 7. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF
 SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND
 AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24
 8. LOAD CALCULATION AND PANEL SCHEDULES SHOW THE SYSTEM
 AS 120/240 VOLT 3 PHASE. THIS SYSTEM WOULD HAVE A HIGH
 LEG ON B PHASE AND 120 VOLT LOAD COULD NOT BE CONNECTED
 TO THIS. THIS WOULD ALSO REQUIRE MARKING OF B PHASE PER
 NEC 110.15. IS THIS IN FACT A HIGH LEG SYSTEM? OR IS
 THIS A 120/208 VOLT 3 PHASE SYSTEM? PROVIDE
 CLARIFICATION AND CORRECTIONS AS NEEDED. NEC 110.3,
 110.15, 215.5, 408.30; WPB FBC 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2019-10-28 Cont ID  
Sent By jpearson Date 2019-10-28 Time 08:51 Rev Time 0.00
Received By jpearson Date 2019-10-28 Time 08:51 Sent To  
Notes
2019-10-28 08:51:46CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. PROVIDE PANEL SCHEDULES INDICATING ANY NEW OR
 ALTERED CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE
 CIRCUITS, AND AFCI OR GFCI PROTECTION WHERE APPLICABLE
 TO COMPLY WITH CODE. NEC 210.8, 210.12, 210.19, 210.20,
 215.5, 408.4; WPB FBC 107.2.1 (RISER SHOWS 3 PANLELS,
 ONLY 2 PANEL SCHEDULES PROVIDED. WHAT IS ON PANEL A-1?)
 2. IS THERE ANY NEW LOADS BEING ADDED? IF SO, PROVIDE
 ACCURATE LOAD CALCULATION FOR SERVICE, INCLUDE EXISTING
 AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE IS
 ADEQUATE. NEC 215.2, 220, 408.30 (PANEL A-1 DOES NOT
 APPEAR TO BE ADDED TO THE LOAD CALCULATIONS PROVIDED.
 PROVIDE CORRECTION.)
 3. PROVIDE THE ADDITIONAL AUTOMATIC LIGHTING CONTROLS
 STIPULATED IN THE FBC ENERGY CODE. FBC EC C405.2 (NOT
 CORRECTED, NO RESPONSE PROVIDED.)
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-07-12 Cont ID  
Sent By jpearson Date 2019-07-12 Time 13:16 Rev Time 0.00
Received By jpearson Date 2019-07-12 Time 10:51 Sent To  
Notes
2019-07-12 13:16:34CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE PANEL SCHEDULES INDICATING ANY NEW OR
 ALTERED CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE
 CIRCUITS, AND AFCI OR GFCI PROTECTION WHERE APPLICABLE
 TO COMPLY WITH CODE. NEC 210.8, 210.12, 210.19, 210.20,
 215.5, 408.4; WPB FBC 107.2.1
 2. IS THERE ANY NEW LOADS BEING ADDED? IF SO, PROVIDE
 ACCURATE LOAD CALCULATION FOR SERVICE, INCLUDE EXISTING
 AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE IS
 ADEQUATE. NEC 215.2, 220, 408.30
 3. PROVIDE THE ADDITIONAL AUTOMATIC LIGHTING CONTROLS
 STIPULATED IN THE FBC ENERGY CODE. FBC EC C405.2
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2019-12-13 Cont ID  
Sent By pleduc Date 2019-12-13 Time   Rev Time 0.00
Received By pleduc Date 2019-12-13 Time 15:31 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-10-22 Cont ID  
Sent By pleduc Date 2019-10-22 Time   Rev Time 0.00
Received By pleduc Date 2019-10-22 Time 14:42 Sent To  
Notes
2019-10-22 14:48:47THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
  
 1) SHEET A 2 - DOOR 21 IS A REQUIRED RATED DOOR;
 HOWEVER, THE DOOR SCHEDULE DOES NOT HAVE A YES WITHIN
 THE FIRE RATING LABEL BOX.
  
 PLEASE ENSURE THE DOOR HAS THE REQUIRED LABEL.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2019-06-03 Cont ID  
Sent By pleduc Date 2019-06-03 Time   Rev Time 0.00
Received By pleduc Date 2019-06-03 Time 14:07 Sent To  
Notes
2019-06-03 14:34:186/3/19
  
 THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET FLOOR PLAN - THERE IS AN INDICATION OF A NEW 2
 HR FIRE RATED DEMISING WALL; HOWEVER, THERE IS NO
 LISTED DESIGN CALL OUT.
  
 PLEASE PROVIDE A LISTED 2 HR FIRE RATING WALL DESIGN.
  
  
  
 1A) SHEET FLOOR PLAN - THERE IS AN INDICATION OF A NEW
 1 HR FIRE RATED DEMISING WALL; HOWEVER, THERE IS NO
 LISTED DESIGN CALL OUT.
  
 PLEASE PROVIDE A LISTED 1 HR FIRE RATING WALL DESIGN.
  
  
  
 2) SHEET FLOOR PLAN - THERE ARE NO INDICATIONS OF THE
 WALLS SEPARATING THE BATHROOMS ARE 2 HR FIRE RATED.
  
 PLEASE PROVIDE DETAILS OF CONTINUES FIRE SEPARATED WALL
 RATINGS.
  
  
  
  
 2A) SHEET FLOOR PLAN - THERE ARE NO INDICATIONS OF THE
 WALL SEPARATING THE OFFICE CAFETERIA AND BATHROOM IS 1
 HR FIRE RATED.
  
 PLEASE PROVIDE DETAILS OF CONTINUES FIRE SEPARATED WALL
 RATINGS.
  
  
  
  
 3) NO SHEET - THERE ARE DOORS INDICATED WITHIN THE 2 HR
 FIRE RATED WALLS; HOWEVER, THERE IS NO DOOR SCHEDULE
 SHOWING APPLICABLE RATING.
  
 PLEASE PROVIDE RATED DOORS AND A DOOR SCHEDULE,
 INCLUDING HARDWARE.
  
  
  
 4) NO SHEET - THERE ARE NUMEROUS DOORS LOCATED
 THROUGHOUT THE PROJECT; HOEVER THERE IS NO DOOR
 SCHEDULE .
  
 PLEASE PROVIDE A DOOR SCHEDULE FOR EACH DOOR AND
 INCLUDE HARDWARE.
  
  
  
 5) SHEET FLOOR PLAN - THERE IS ONLY ONE EXIT FROM LEFT
 HAND SUITE AND THE OTHER SUITE THERE ARE NO INDICATION
 OF TRAVEL DISTANCE NOR COMMON PATH OF TRAVEL TO THE
 EXIT.
  
 PER NFPA 101, CH
  
 38.2.4 NUMBER OF MEANS OF EGRESS.
 38.2.4.1 MEANS OF EGRESS SHALL COMPLY WITH ALL OF THE
 FOLLOWING, EXCEPT
 AS OTHERWISE PERMITTED BY 38.2.4.2 THROUGH 38.2.4.6:
 (1) THE NUMBER OF MEANS OF EGRESS SHALL BE IN
 ACCORDANCE WITH
 SECTION 7.4.
 (2) NOT LESS THAN TWO SEPARATE EXITS SHALL BE PROVIDED
 ON EVERY STORY.
 (3) NOT LESS THAN TWO SEPARATE EXITS SHALL BE
 ACCESSIBLE FROM EVERY
 PART OF EVERY STORY.
 38.2.4.2 EXIT ACCESS, AS REQUIRED BY 38.2.4.1(3), SHALL
 BE PERMITTED TO
 INCLUDE A SINGLE EXIT ACCESS PATH FOR THE DISTANCES
 PERMITTED AS COMMON
 PATHS OF TRAVEL BY 38.2.5.3.
 38.2.4.3 A SINGLE EXIT SHALL BE PERMITTED FOR A ROOM OR
 AREA WITH A TOTAL
 OCCUPANT LOAD OF LESS THAN 100 PERSONS, PROVIDED THAT
 ALL OF THE
 FOLLOWING CRITERIA ARE MET:
 (1) THE EXIT SHALL DISCHARGE DIRECTLY TO THE OUTSIDE AT
 THE LEVEL OF EXIT
 DISCHARGE FOR THE BUILDING.
 (2) THE TOTAL DISTANCE OF TRAVEL FROM ANY POINT,
 INCLUDING TRAVEL WITHIN
 THE EXIT, SHALL NOT EXCEED 100 FT (30 M).
 (3) THE TOTAL DISTANCE OF TRAVEL SPECIFIED IN
 38.2.4.3(2) SHALL BE ON THE
 SAME STORY, OR, IF TRAVERSING OF STAIRS IS NECESSARY,
 SUCH STAIRS SHALL
 NOT EXCEED 15 FT (4570 MM) IN HEIGHT, AND BOTH OF THE
 FOLLOWING
 ALSO SHALL APPLY:
 (A) INTERIOR STAIRS SHALL BE PROVIDED WITH COMPLETE
 ENCLOSURES TO
 SEPARATE THEM FROM ANY OTHER PART OF THE BUILDING, WITH
 NO
 DOOR OPENINGS THEREIN.
 (B) A SINGLE OUTSIDE STAIR IN ACCORDANCE WITH 7.2.2
 SHALL BE
 PERMITTED TO SERVE ALL STORIES PERMITTED WITHIN THE 15
 FT (4570
 MM) VERTICAL TRAVEL LIMITATION.
  
 PLEASE PROVIDE A LIFE SAFETY SHEET WITH DIMENSIONS
 SHOWING COMPLIANCE WITH THE ABOVE.
  
  
 6) SHEET FLOOR PLAN - AN EXIT SIGN IS INDICATED WITHIN
 THE NEW LOBBY AREA AT THE DOOR LEADING TO THE ADJACENT
 SUITE.
  
 AN EXIT CAN NOT PASS THRU AND ADJACENT OCCUPANCY.
  
 PER NFPA 101, CH 7
  
 7.5.1.6 EXIT ACCESS FROM ROOMS OR SPACES SHALL BE
 PERMITTED TO BE
 THROUGH ADJOINING OR INTERVENING ROOMS OR AREAS,
 PROVIDED THAT SUCH
 ROOMS OR AREAS ARE ACCESSORY TO THE AREA SERVED.
 FOYERS, LOBBIES, AND
 RECEPTION ROOMS CONSTRUCTED AS REQUIRED FOR CORRIDORS
 SHALL NOT BE
 CONSTRUED AS INTERVENING ROOMS. EXIT ACCESS SHALL BE
 ARRANGED SO
 THAT IT IS NOT NECESSARY TO PASS THROUGH ANY AREA
 IDENTIFIED UNDER
 PROTECTION FROM HAZARDS IN CHAPTERS 11 THROUGH 43.
 7.5.2 IMPEDIMENTS TO EGRESS. SEE ALSO 7.1.9 AND
 7.2.1.5.
 7.5.2.1* ACCESS TO AN EXIT SHALL NOT BE THROUGH
 KITCHENS,
 STOREROOMS OTHER THAN AS PROVIDED IN CHAPTERS 36 AND
 37,
 RESTROOMS, CLOSETS, BEDROOMS OR SIMILAR SPACES, OR
 OTHER ROOMS OR
 SPACES SUBJECT TO LOCKING, UNLESS PASSAGE THROUGH SUCH
 ROOMS OR
 SPACES IS PERMITTED FOR THE OCCUPANCY BY CHAPTER 18,
 19, 22, OR 23.
  
 THERE WOULD BE NO WAY OF KNOWING THAT THE ADJACENT
 OCCUPANCY IS OPEN NOR IF THE SOLE EXIT DOOR IS
 UNLOCKED.
  
 THIS DOOR CAN NOT BE AN EXIT.
  
 PLEASE CORRECT.
  
  
 7) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2020-01-24 Cont ID  
Sent By gjohnson Date 2020-01-24 Time 12:02 Rev Time 0.00
Received By gjohnson Date 2020-01-17 Time 14:05 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-12-17 Cont ID  
Sent By gjohnson Date 2019-12-17 Time 16:26 Rev Time 0.00
Received By gjohnson Date 2019-11-27 Time 14:58 Sent To  
Notes
2019-12-02 14:58:55C10

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2019-10-29 Time   Rev Time 0.00
Received By lmarchan Date 2019-10-18 Time 13:51 Sent To  
Notes
2019-10-21 13:51:58C09

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2019-07-12 Time   Rev Time 0.00
Received By lmarchan Date 2019-05-29 Time 15:39 Sent To  
Notes
2019-05-30 15:40:03C09

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2019-12-12 Cont ID  
Sent By ccole Date 2019-12-12 Time 11:02 Rev Time 0.00
Received By ccole Date 2019-12-12 Time 10:48 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2019-10-25 Cont ID  
Sent By ccole Date 2019-10-25 Time 09:03 Rev Time 0.00
Received By ccole Date 2019-10-25 Time 07:51 Sent To  
Notes
2019-10-25 09:04:33MECH PASSED WITH PROVISO NOTES ON SHEET M1.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-07-02 Cont ID  
Sent By ccole Date 2019-07-02 Time 13:41 Rev Time 0.00
Received By ccole Date 2019-07-02 Time 12:18 Sent To  
Notes
2019-07-02 14:12:041ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19051456
 7/2/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET AC-1: REFER TO SECTION 809.2 FBC-17 EXISTING
 BUILDING CODE AND PROVIDE MINIMUM VENTILATION
 CALCULATIONS FOR ALL ROOMS AND SPACES PER TABLE
 403.3.1.1 FBC-17 MECHANICAL. PROVIDE A SCHEDULE THAT
 INDICATES THE REQUIRED AND PROVIDED CFMS OF OUTDOOR
 AIR.
  
 2) AC-1: PLEASE IDENTIFY THE LARGE OPEN ROOM IN THE
 MIDDLE OF THE TENANT SPACE- SECTION 107.2.1 WPB.
  
 3) AC-1: SHOW THE SUPPLY CFMS AT EACH NEW DIFFUSER, AND
 THE DIMENSIONS OF THE NEW DIFFUSERS AND RETURN GRILLES-
 SECTION 603.1& 603.2 FBC M.
  
 4) AC-1: SHOW WHERE THE NEW FLEX DUCTS ARE CONNECTING
 TO THE MAIN DUCT TRUNK(S), AND PROVIDE DUCT SUPPORT,
 HANGING, AND CONNECTION DETAILS- 603.1 & 603.2 FBC M.
  
 5) AC-1: IT APPEARS THAT THERE IS AN EXISTING RETURN
 AIR PLENUM. PLEASE PLACE A NOTE TO CLARIFY AND SHOW HOW
 THE AIR FROM THE NEW OFFICES IS BEING RETURNED TO THE
 AIR HANDLER- SECTION 601.6 & 602.1 FBC M.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 BUILDING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2020-01-24 Cont ID  
Sent By gjohnson Date 2020-01-24 Time 12:02 Rev Time 0.00
Received By gjohnson Date 2020-01-24 Time 12:02 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2019-12-17 Cont ID  
Sent By gjohnson Date 2019-12-17 Time 15:36 Rev Time 0.00
Received By gjohnson Date 2019-12-17 Time 14:25 Sent To  
Notes
2019-12-17 16:25:472ND REVIEW: 19051456
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS: PREVIOUS COMMENTS NOT COMPLIED WITH.
  
 10. THE SANITARY RISER HAS MULTIPLE CODE VIOLATIONS.
 LABEL EXISTING PIPING AND NEW PIPING PER WPB AMEND TO
 FBC 107.2.1
  
 B) THE TOILETS SHALL BE VENTED BEFORE CONNECTING TO THE
 BUILDING DRAIN. PER FBC PL 901.2.1, 912.1
  
 11. SEPARATE WATER RISER BETWEEN THE TWO SUITES, EACH
 SUITE SHALL HAVE A SEPARATE SHUT OFF VALVE ON THE MAIN
 WATER SUPPLY. PER FBC PL 606.1(2)
  
 12. SHUT OFF VALVES ARE REQUIRED AT EACH HOT AND COLD
 WATER DROP. PER FBC PL 606.1(5)
  
 14. SHOW TEMPERED WATER IS BRING SUPPLIED TO ALL TOILET
 ROOM SINK BY A ASSE 1070 APPROVED DEVICE. FBC-P 416.5,
 607.1.2
  
 15. PROVIDE MIN FIXTURE SUPPLY SCHEDULED SHOWING MIN
 REQUIRED UNDER FBC-P 403.1 AND FIXTURES BEING SUPPLIED.
  
 NEW COMMENTS:
  
 1. THE NEW MOP SINK SHALL BE VENTED SEPARATELY AND
 CONNECT TO DOWN STREAM OF THE BATHROOM GROUP. PER FBC
 PL 901.2.1, 912.1
  
 2. EXPAND WATER ISOMETRIC IT APPEARS THAT THE THE WATER
 PIPING FROM THE TWO UNITS ARE CONNECTTING EACH UNIT
 SHALL HAVE SEPARATE HOT AND COLD PIPING. PER WPB AMEND
 TO FBC 107.2.1 SEE PREVIOUS COMMENT 11.
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2019-10-25 Cont ID  
Sent By gjohnson Date 2019-10-25 Time 15:43 Rev Time 0.00
Received By gjohnson Date 2019-10-25 Time 09:53 Sent To  
Notes
2019-10-25 15:43:482ND REVIEW: 19051456
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. CITY RECORDS SHOW THE LAST LEGAL OCCUPANCY FOR THIS
 BUILDING WAS A BUSINESS THAT MAKES THIS PROJECT A
 CHANGE OF OCCUPANCY SHALL COMPLY WITH FBC EXISTING
 1006.1 GENERAL. ACCESSIBILITY IN PORTIONS OF BUILDINGS
 UNDERGOING A CHANGE OF OCCUPANCY CLASSIFICATION SHALL
 COMPLY WITH THE PROVISIONS OF THE FLORIDA BUILDING
 CODE, ACCESSIBILITY.
  
 2. SHT. A-4 BATHROOMS 1-2-3 ARE NOT COMPLIANT WITH
 CURRENT FBC ACC IN THE GANG BATHROOMS THE ACCESSIBLE
 STALL IS NOT WIDE ENOUGH THE CLEAR FLOOR SPACE FOR THE
 TOILET SHALL NOT HAVE ANY OTHER FIXTURES ENCROACHING
 INTO IT. IT SHALL COMPLY WITH FBC ACC 604.3.2 604.3.1
 SIZE. CLEARANCE AROUND A WATER CLOSET SHALL BE 60
 INCHES (1525 MM) MINIMUM MEASURED PERPENDICULAR FROM
 THE SIDE WALL AND 56 INCHES (1420 MM) MINIMUM MEASURED
 PERPENDICULAR FROM THE REAR WALL.
  
 3. PER FBC PL TABLE 403.1 2 TOILETS AND 2 LAVATORY'S
 ARE REQUIRED FOR EACH SEX IN SUITE A. SEPARATE
 FACILITIES REQUIRED PER FBC PL 403.2 EACH BATHROOM
 SHALL HAVE A COMPLIANT ACCESSIBLE TOILET STALL PER FBC
 ACC 213.3.1
  
 4. SEPARATE FACILITIES REQUIRED IN SUITE B PER PER FBC
 PL 403.2
  
 5. MOP SINK IS REQUIRED IN SUITE A PER FBC PL TABLE
 403.1
  
 6. SHOW COMPLIANCE WITH FBC ACC 604.5.2 REAR WALL. THE
 REAR WALL GRAB BAR SHALL BE 36 INCHES (915 MM) LONG
 MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER
 CLOSET 12 INCHES (305 MM) MINIMUM ON ONE SIDE AND 24
 INCHES (610 MM) MINIMUM ON THE OTHER SIDE.
  
 7. SHOW COMPLIANCE WITH FBC ACC 604.6 FLUSH CONTROLS.
 FLUSH CONTROLS SHALL BE HAND OPERATED OR AUTOMATIC.
 HAND OPERATED FLUSH CONTROLS SHALL COMPLY WITH 309.
 FLUSH CONTROLS SHALL BE LOCATED ON THE OPEN SIDE OF THE
 WATER CLOSET EXCEPT IN AMBULATORY ACCESSIBLE
 COMPARTMENTS COMPLYING WITH 604.8.2.
  
 8. SHOW TANKLESS WATER HEATER ON THE FLOOR PLAN. PER
 WPB AMEND TO FBC 107.2.1
  
 9. PROVIDE MANUFACTURE SPECIFICATION AND INSTILLATION
 GUIDE FOR TANKLESS WATER HEATER. PER WPB AMEND TO FBC
 107.2.1
  
 10. THE SANITARY RISER HAS MULTIPLE CODE VIOLATIONS.
 LABEL EXISTING PIPING AND NEW PIPING PER WPB AMEND TO
 FBC 107.2.1
 A)THE NEW WATER FOUNTAIN BRANCH DRAIN SHALL CONNECT TO
 THE BUILDING DRAIN DOWN STREAM OF THE BATHROOM GROUP.
 PER FBC PL 912.1
 B) THE TOILETS SHALL BE VENTED BEFORE CONNECTING TO THE
 BUILDING DRAIN. PER FBC PL 901.2.1, 912.1
  
 11. SEPARATE WATER RISER BETWEEN THE TWO SUITES, EACH
 SUITE SHALL HAVE A SEPARATE SHUT OFF VALVE ON THE MAIN
 WATER SUPPLY. PER FBC PL 606.1(2)
  
 12. SHUT OFF VALVW ARE REQUIRED AT EACH HOT AND COLD
 WATER DROP. PER FBC PL 606.1(5)
  
  
 13.TOILET ROOM NEAR BREAKROOM EXISTING AND NEW PLAN IS
 NOT PER CITY RECORDS (#03070117) AND FBC-ACC 604.8.1.7
 REQUIRES THE TOILET TO BE DIAGONAL TO THE DOOR.
  
  
 14. SHOW TEMPERED WATER IS BRING SUPPLIED TO ALL TOILET
 ROOM SINK BY A ASSE 1070 APPROVED DEVICE. FBC-P 416.5,
 607.1.2
  
  
  
 15. PROVIDE MIN FIXTURE SUPPLY SCHEDULED SHOWING MIN
 REQUIRED UNDER FBC-P 403.1 AND FIXTURES BEING SUPPLIED.
  
  
  
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-07-02 Cont ID  
Sent By thunt Date 2019-07-02 Time 11:11 Rev Time 0.00
Received By thunt Date 2019-07-01 Time 16:20 Sent To  
Notes
2019-07-02 11:09:39PLUMBING 1ST REVIEW**DENIED**
  
 1) PROVIDE OCCUPANCY AND OCCUPANT LOAD FOR EACH SPACE.
 FBC 107.3.5
  
 2) BEING THAT THIS WILL BE 2 SEPARATE SPACES THE
 PLUMBING CODE 403.1, 410.3 REQUIRE BOTH A MOP SINK AND
 HI-LOW DRINKING FOUNTAIN FOR EACH SPACE.
  
 3) PROVIDE CLEAR FLOOR AND TURNING SPACE FOR ALL TOILET
 ROOMS. FBC-ACC 603.2.1, 304
  
 4) PROVIDE CLEAR FLOOR AND TURNING SPACE WITH DETAIL OF
 CABINET HEIGHT SHOWING MAX 34" FOR THE BREAK ROOM SINK
 IS TO REMAIN COMPLIANT AS DESIGNED AND INSTALLED UNDER
 PERMIT # 03070117. FBC 107.2.1
  
 5) TOILET ROOM NEAR BREAKROOM EXISTING AND NEW PLAN IS
 NOT PER CITY RECORDS (#03070117) AND FBC-ACC 604.8.1.7
 REQUIRES THE TOILET TO BE DIAGONAL TO THE DOOR.
  
 6) LABEL EACH TOILET ROOM AS MEN'S AND WOMEN'S SHOWING
 YOU ARE PROVIDING SEPARATE FACILITIES FOR EACH. FBC-P
 403.2
  
 7) PROVIDE ROOM MEASUREMENTS ON PLANS. FBC 107.3.5
  
 8) PROVIDE LOCATION AND INSTALLATION MANUAL OF WATER
 HEATER. SHOW TOTAL DEVELOP LENGTH OF HOT WATER LINE
 FROM THE WATER HEATER TO THE MOST REMOTE OUTLET. PLEASE
 NOTE MUST BE WITH IN 50' OR HAVE A HOT WATER RETURN
 SYSTEM AND ALL HOT WATER PIPING SHALL BE INSULATED.
 FBC-P 607.2, 607.5
  
 9) SHOW TEMPERED WATER IS BRING SUPPLIED TO ALL TOILET
 ROOM SINK BY A ASSE 1070 APPROVED DEVICE. FBC-P 416.5,
 607.1.2
  
 10) PROVIDE A COMPLETED RISER ISOMETRIC FOR BOTH THE
 SANITARY AND WATER SUPPLY SYSTEM. FBC 107.3.5
  
 11) SHT. P1 DETAIL #2 SHOW GRAB BAR BEING MOUNTED 12"
 FROM CENTERLINE OF TOILET. FBCC-ACC 604.5.2
  
 12) PROVIDE MIN FIXTURE SUPPLY SCHEDULED SHOWING MIN
 REQUIRED UNDER FBC-P 403.1 AND FIXTURES BEING SUPPLIED.
  
 13) SHT. P1 SHOW MIRROR AS MAX 40" TO THE REFLECTING
 SURFACE AND NOT TO THE BOTTOM FRAME. FBC-ACC 603.3
  
 14) SHT. P1 CALLS FOR FIXTURES TO BE REPLACED IN SAME
 LOCATION. BEING THIS IS A CHANGE OF USE AND RELOCATION
 OF THE FIXTURE'S THE TOILET ROOMS WILL BE REQUIRED TO
 COMPLY WITH 2017 6TH ED OF THE FLORIDA ACCESSIBILITY
 CODE. PLEASE REMOVE NOTE ON PLAN AS IT MAY MIS-LEAD
 FIELD INSPECTOR. FBC 107.2.1
  
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR
 BUILDING DIVISION
 CITY OF WEST PALM BEACH
 401 CLEMATIS STREET, 1ST FLOOR
 PALM BEACH, FL 33401
 561-248-2703
 [email protected]
  