| 2019-06-17 05:56:17 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. PROVIDE LOAD CALCULATION FOR NEW "CRITICAL LOAD" |
| | SUB-PANEL. NEC 220 FBC 107.2.1 |
| | |
| | 2. PROVIDE CUT SHEETS FOR PRODUCT APPROVAL OF ALL |
| | MATERIALS AND EQUIPMENT. INVERTER, LG BATTERY, |
| | INTERLOCK KITS FOR BREAKER LOCK-OUTS, AND |
| | AUTOTRANSFORMER. MUST BE LISTED BY UL OR ANOTHER NRTL |
| | (NATIONALLY RECOGNIZED TESTING LABORATORY). FBC 107.2.1 |
| | NEC 90.7, 110.2, 110.3B |
| | |
| | 3. PROVIDE LOCATION OF INVERTER AND BATTERY. FBC |
| | 107.2.1 |
| | |
| | 4. FEEDER CONDUCTORS FOR NEW "CRITICAL LOAD" SUB-PANEL |
| | ARE SHOWN AS #10AWG WITH 40AMP OCP. MAX OCP FOR #10AWG |
| | IS 30AMPS. PLEASE SEE NEC 240.D #7 |
| | |
| | 5. NO EQUIPMENT GROUNDING CONDUCTOR SHOWN FOR "CRITICAL |
| | LOAD" PANEL. PROVIDE CORRECTION. NEC 250.110, 250.134B, |
| | 300.3B, |
| | |
| | 6. PROVIDE EXPLANATION AND DOCUMENTATION FOR FPL |
| | PRODUCTION METER. FBC 107.2.1 |
| | |
| | 7. INVERTER HAS BUILT IN ATS? FBC 107.2.1 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | CODES IN EFFECT: |
| | |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2017 6TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | V/R, |
| | |
| | FRANK GIAQUINTO III |
| | ELECTRICAL INSPECTOR |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | [email protected] |
| | CELL: 561-657-1653 |
| | |
| | |