Plan Review Details - Permit 19051383
Plan Review Stops For Permit 19051383
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-06-20 Cont ID  
Sent By J.Walker Date 2019-06-20 Time   Rev Time 0.00
Received By   Date 2019-06-19 Time   Sent To MEDGAS
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2019-05-31 Cont ID  
Sent By J.Walker Date 2019-05-31 Time   Rev Time  
Received By   Date 2019-05-30 Time   Sent To M
Notes
2019-05-31 08:33:31PROVIDE THE FOLLOWING.
 1. CUT SHEETS & MANUFACTURERS SPECIFICATIONS
 2. FUEL CAPACITY OF EXISTING AND NEW FUEL TANKS
 3. LENGTH OF NEW PIPE RUNS.
 NFPA 110 - 7.9
 NFPA 30A - 5.3
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-06-24 Cont ID  
Sent By cmontell Date 2019-06-24 Time 11:25 Rev Time 0.00
Received By cmontell Date 2019-06-17 Time 14:33 Sent To  
Notes
2019-06-18 14:33:31RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-06-14 Cont ID  
Sent By hmoser Date 2019-06-14 Time 07:50 Rev Time 0.00
Received By hmoser Date 2019-05-28 Time 09:53 Sent To  
Notes
2019-05-30 09:53:20ROUTED TO FIRE INBOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2019-06-24 Cont ID  
Sent By cmontell Date 2019-06-24 Time 11:24 Rev Time 0.00
Received By cmontell Date 2019-06-24 Time 11:24 Sent To I
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2019-06-14 Cont ID  
Sent By hmoser Date 2019-06-14 Time 07:49 Rev Time 0.00
Received By hmoser Date 2019-06-14 Time 07:49 Sent To I
Notes
***NONE***