| 2019-06-07 10:49:16 | BUILDING REVIEW COMMENTS: |
| | |
| | W.P.B. PERMIT: 19051313 |
| | REVIEWED: JUNE 7, 2019 |
| | |
| | DYLAN BATTLES |
| | BUILDING PLANS EXAMINER PX4191 |
| | [email protected] |
| | 561-805-6718 |
| | |
| | FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017) |
| | FBC[B] = FBC BUILDING |
| | FBC[EXISTING] = FBC EXISTING BUILDING |
| | |
| | 1) 105.2 FBC[B] WORK EXEMPT FROM PERMIT. EXEMPTIONS |
| | FROM PERMIT REQUIREMENTS OF THIS CODE SHALL NOT BE |
| | DEEMED TO GRANT AUTHORIZATION FOR ANY WORK TO BE DONE |
| | IN ANY MANNER IN VIOLATION OF THE PROVISIONS OF THIS |
| | CODE OR ANY OTHER LAWS OR ORDINANCES OF THIS |
| | JURISDICTION. PERMITS SHALL NOT BE REQUIRED FOR THE |
| | FOLLOWING: |
| | |
| | REPLACEMENT OF CABINETS AND COUNTERTOPS WITHOUT |
| | RECONFIGURATION, PAINTING, PAPERING, TILING, CARPETING, |
| | AND SIMILAR FINISH WORK, WITH NO ELECTRICAL OR PLUMBING |
| | WORK. THIS EXCEPTION DOES NOT INCLUDE HARD FLOORING |
| | IMMEDIATELY ABOVE ADJACENT DWELLING UNITS, OR OTHER |
| | WORK FOR WHICH THERE ARE SPECIFIC REQUIREMENTS IN |
| | FLORIDA BUILDING CODE THAT AFFECT THE PROPOSED WORK. |
| | - IF NO RECONFIGURATION THEN NO PERMIT NEEDED FOR |
| | COUNTERTOPS AND CABINETS. HOWEVER, THE FLOORING DOES |
| | NEED PERMIT FOR SOUND TRANSMISSION SUBMITTAL. |
| | |
| | 2) 1207.2 FBC[B] FLOORING SUBMITTAL. |
| | - FLOOR PLAN LAYOUT TO SHOW DIMENSIONS, AREA AND TYPE |
| | OF FLOORING FOR EACH AREA. |
| | |
| | 3) 1207.2 FBC[B] FLOORING SUBMITTAL. |
| | - TYPE OF CEILING ASSEMBLE INCLUDING THICKNESS OF |
| | CONCRETE AND IF THERE IS A SOUND RATED ASSEMBLY IN UNIT |
| | BELOW. |
| | |
| | 4) 1207.2 FBC[B] PLEASE ADVISE ,VIA EMAIL, WHAT |
| | FLOORING AND UNDERLAYMENT ARE PROPOSED? IF THE |
| | UNDERLAYMENT PRODUCT PROPOSED IS NOT ONE FOR WHICH WE |
| | HAVE TEST REPORTS ON FILE, THE FOLLOWING REPORTS WILL |
| | BE REQUIRED: |
| | 4A) 1207.2 FBC[B] AIR-BORNE SOUND. WALLS, PARTITIONS |
| | AND FLOOR/CEILING ASSEMBLIES SEPARATING DWELLING UNITS |
| | AND SLEEPING UNITS FROM EACH OTHER OR FROM PUBLIC OR |
| | SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS OF |
| | NOT LESS THAN 50, OR NOT LESS THAN 45 IF FIELD TESTED, |
| | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| | E90. |
| | 4B) 1207.3 FBC[B] STRUCTURE-BORNE SOUND. FLOOR/CEILING |
| | ASSEMBLIES BETWEEN DWELLING UNITS AND SLEEPING UNITS OR |
| | BETWEEN A DWELLING UNIT OR SLEEPING UNIT AND A PUBLIC |
| | OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN |
| | IMPACT INSULATION CLASS RATING OF NOT LESS THAN 50, OR |
| | NOT LESS THAN 45 IF FIELD TESTED, WHEN TESTED IN |
| | ACCORDANCE WITH ASTM E492. |
| | 4C) 603.1 FBC[B] ALLOWABLE MATERIALS IN NON COMBUSTIBLE |
| | BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL |
| | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE |
| | 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84 |
| | OR UL 723. |
| | - THE PERMIT SAYS LAY TILE OVER. IS THE INTENET TO |
| | LEAVE TO EXISTING FLOO?. PROVIDE DATA FOR WHAT WAS |
| | PREVIOUSLY INSTALLED TO SHOW HOW IT WILL MEET CURRENT |
| | SOUND TRANSMISSION REQUIREMENTS. |
| | |
| | NOTES: |
| | |
| | -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW |
| | OF MATERIALS REQUESTED. |
| | |
| | -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS |
| | OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) |
| | SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT |
| | DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER |
| | SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" |
| | OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS |
| | APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE |
| | NEED "VOID", RENDERING THEM NOT USABLE. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F |
| | 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME |
| | [email protected] |
| | |
| | |
| | |
| | |
| | |