Plan Review Details - Permit 19051312
Plan Review Stops For Permit 19051312
Review Stop AD ADDRESSING
Rev No 1 Status N Date 2019-07-11 Cont ID  
Sent By dbattles Date 2019-07-11 Time 08:49 Rev Time 0.00
Received By dbattles Date 2019-07-11 Time 08:49 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2019-10-11 Cont ID  
Sent By dbattles Date 2019-10-11 Time 11:24 Rev Time 0.00
Received By dbattles Date 2019-10-11 Time 11:24 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-07-29 Cont ID  
Sent By dbattles Date 2019-07-29 Time 10:30 Rev Time 0.00
Received By dbattles Date 2019-07-29 Time 10:29 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-07-11 Cont ID  
Sent By shill Date 2019-07-11 Time 08:47 Rev Time 0.00
Received By dbattles Date 2019-07-09 Time 18:05 Sent To  
Notes
2019-07-11 08:47:22BUILDING REVIEW COMMENTS:
  
 W.P.B. PERMIT: 19051312
 REVIEWED: JULY 10, 2019
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER PX4191
 [email protected]
 561-805-6718
  
 FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC[B] = FBC BUILDING
 FBC[EXISTING] = FBC EXISTING BUILDING
 FBC[A] = FBC ACCESSIBILITY
 FBC[E] = FBC ENERGY CONSERVATION
  
 1) 107.5.3 FBC[AMENDED] CODE EDITION.
 - COVER SHEET SAYS ACCESSIBILITY 2014. THIS SHOULD BE
 2017 FLORIDA BUILDING CODE ACCESSIBILITY 6TH EDITION.
  
 2) 501 FBC[EXISTING] STATE THE LEVEL OF ALTERATION FOR
 WORK BEING PERFORMED.
 A) LEVEL 1 ALTERARTION
 B) LEVEL 2 ALTERARTION
 C) LEVEL 3 ALTERARTION
 - LEVEL OF ALTERATION SHOULD BE LEVEL 2 SINCE WALLS ARE
 BEING REMOVED AND REPLACED.
  
 3) 1004.1 FBC[B] DESIGN OCCUPANT LOAD. IN DETERMINING
 MEANS OF EGRESS REQUIREMENTS, THE NUMBER OF OCCUPANTS
 FOR WHOM MEANS OF EGRESS FACILITIES ARE PROVIDED SHALL
 BE DETERMINED IN ACCORDANCE WITH THIS SECTION.
 - OCCUPANT LOAD SHOULD BE 15 PERSONS. SINCE SQ. FOOTAGE
 EXCEEDS 1400 IT ROUNDS UP TO 1500.
  
 4) 404.2.4 FBC[A] MANEUVERING CLEARANCES. MINIMUM
 MANEUVERING CLEARANCES AT DOORS
 - SHOW CLEAR SPACE AT EXAM ROOM 3 FROM ROOM INTERIOR.
  
 NOTES:
  
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
  
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  
 PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F
 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME
 [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2019-10-11 Cont ID  
Sent By ppetty Date 2019-10-11 Time 13:19 Rev Time 0.00
Received By ppetty Date 2019-10-11 Time 13:19 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-08-13 Cont ID  
Sent By ppetty Date 2019-08-13 Time 10:26 Rev Time 0.00
Received By ppetty Date 2019-08-13 Time 10:26 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-06-24 Cont ID  
Sent By jpearson Date 2019-06-24 Time 15:37 Rev Time 0.00
Received By jpearson Date 2019-06-24 Time 15:37 Sent To  
Notes
2019-06-24 15:37:18CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. NEC 210.8, 210.12, 210.19, 210.20, 215.5,
 408.4
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-07-29 Cont ID  
Sent By pleduc Date 2019-07-29 Time   Rev Time 0.00
Received By pleduc Date 2019-07-29 Time 12:21 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2019-05-30 Cont ID  
Sent By sathomas Date 2019-05-30 Time 00:00 Rev Time 0.00
Received By sathomas Date 2019-05-30 Time 00:00 Sent To E
Notes
2019-05-30 14:49:071.PROVIDE DRAWING NOTE INDICATING ALL CONSTRUCTION AND
 DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS OF
 NFPA 241. TRASH AND CONSTRUCTION DEBRIS SHALL BE
 REMOVED FROM THE SITE DAILY. SMOKING SHALL BE
 PROHIBITED EXCEPT IN DESIGNATED EXTERIOR AREAS. ALL
 OTHER DEMOLITION OR CONSTRUCTION AREAS SHALL HAVE "NO
 SMOKING" SIGNS POSTED. WHERE SMOKING IS PERMITTED, SAFE
 RECEPTACLES FOR SMOKING MATERIALS SHALL BE PROVIDED.
  
 2.PROVIDE DRAWING NOTE INDICATING, ?FIRE PROTECTION
 SYSTEMS SHALL REMAIN ACTIVE DURING DEMOLITION AND
 RENOVATION ACTIVITIES. IN THE EVENT A FIRE PROTECTION
 SYSTEM IS OUT OF SERVICE FOR MORE THAN 4-HOURS IN A
 24-HOUR PERIOD, THE BUILDING SHALL BE PLACED UNDER A
 FIRE WATCH. ALL FIRE WATCH REQUESTS MUST BE SUBMITTED
 BY EMAIL ([email protected]) OR IN WRITING (FAX:
 561-804-4774) AND APPROVED BY THE OFFICE OF THE FIRE
 MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY.
  
 3.SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER
 SYSTEM AND/OR FIRE ALARM SYSTEM.
  
 4.OCCUPANY CLASSIFICATION IS LISTED AS STORAGE AND
 BUSINESS PER PLANS, HOWEVER THE FACILITY APPEARS TO BE
 A BUSINESS OCCUPANCY.
  
 S. THOMAS
 561-804-4728

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-10-11 Cont ID  
Sent By ppetty Date 2019-10-11 Time 13:19 Rev Time 0.00
Received By ppetty Date 2019-10-04 Time 14:37 Sent To  
Notes
2019-10-07 14:37:39B11

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-08-16 Cont ID  
Sent By cmontell Date 2019-08-16 Time 13:39 Rev Time 0.00
Received By cmontell Date 2019-07-24 Time 14:09 Sent To  
Notes
2019-07-25 14:10:04B28

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-07-11 Cont ID  
Sent By dbattles Date 2019-07-11 Time 08:49 Rev Time 0.00
Received By dbattles Date 2019-05-24 Time 15:22 Sent To  
Notes
2019-05-28 15:22:29B02

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2019-08-16 Cont ID  
Sent By cmontell Date 2019-08-16 Time 13:38 Rev Time 0.00
Received By cmontell Date 2019-08-16 Time 13:37 Sent To I
Notes
2019-08-16 13:38:18NO MECHANICAL WORK PER SCOPE OF WORK
 SEE PLAN CVR

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-07-08 Cont ID  
Sent By ccole Date 2019-07-08 Time 10:22 Rev Time 0.00
Received By ccole Date 2019-07-08 Time 10:21 Sent To  
Notes
2019-07-08 10:38:221ST REVIEW FBC-2017 MECHANICAL
 PERMIT
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) EXHAUST VENTILATION AT A RATE OF 1.0 CFMS PER SQ.
 FT. IS REQUIRED FOR THE LAB PER TABLE 403.3.1.1 FBC M.
 PLEASE PROVIDE A CALCULATION, SHOW DETAILS AND
 SPECIFICATIONS FOR THE SYSTEM, AND THE SYSTEM'S
 SEQUENCE OF OPERATION.
  
 2) PROVIDE ON THE PLAN A NARRATIVE THAT DESCRIBES THE
 PROCESSES THAT OCCUR IN THE LAB, WHAT EQUIPMENT IS
 USED, AND A LIST MATERIALS TO BE USED AND STORED IN THE
 LAB- SECTION 107.2.1 WPB, AND SECTIONS 414.2.1 &
 414.2.2 FBC B.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 BUILDING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2019-10-10 Cont ID  
Sent By gjohnson Date 2019-10-10 Time 16:40 Rev Time 0.00
Received By gjohnson Date 2019-10-09 Time 15:29 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2019-08-15 Cont ID  
Sent By jesmith Date 2019-08-15 Time 10:27 Rev Time 0.00
Received By jesmith Date 2019-08-15 Time 08:31 Sent To  
Notes
2019-08-15 10:27:53CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 NFPA 54= STANDARD FOR VENTILATION CONTROLAND FIRE
 PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
  
 2ND REVIEW
 PLUMBING COMMEMTS: DENIED
 ORIGINAL COMMENTS
 1) COMPLIED
 2) COMPLIED
 3) COMPLIED
 4) SHT. S1 TOILET DETAIL SHOWS 15? TO TOP OF TOILET.
 THE TOILET SHALL BE BETWEEN 17?-19?-ACC 604.4. COMMENT:
 SEE RED LINED COMMENT ON S1; FIXTURE ELEVATION AND
 COMPLY.
 5) SHT.S1 TOILET DISPENSER SHALL BE SHOWN AS 7?-9? FROM
 THE FRONT LIP OF THE BOWL. FBC-ACC 604.7. COMMENT: SEE
 RED LINED COMMENT ON S1; FIXTURE ELEVATION AND COMPLY.
 6) COMPLIED
 7) SHT. S1 TOILET GRAB BAR DETAIL PROVIDE SHOWS GRAB
 BAR MOUNT TO THE CENTER OF BAR. THE 33"-36" SHALL BE TO
 THE TOP OF THE GRIPPING SURFACE. FBC-ACC 609.4.
 COMMENT: SEE RED LINED COMMENT ON S1; FIXTURE ELEVATION
 AND COMPLY.
 8) WILL THE LAB-SINK ALSO BE USED AS A BREAK ROOM SINK?
 IF SO, PLEASE PROVIDE CABINET TOP AND CLEAR FLOOR SPACE
 DETAIL. FBC 107.2.1. COMMENT: SHOW DIMENSIONED CLEAR
 FLOOR SPACE FOR THE SINK TO COMPLY WITH FBC ACC 305.
  
 NEW COMMENTS
 1) SHT. E1; SANITARY RISER: THE NEW H/C SINK MAY BE
 VENTED WITH AN AIR ADMITTANCE VALVE AS NOTED, HOWEVER
 THE NEW UNDERGROUND PIPING NEEDS TO BE AN EXTENSION OF
 THE EXISTING HORIZONTAL WET VENT SERVICING THE WATER
 CLOSET AND SHALL CONNECT TO IT IN A MANNER THAT THERE
 IS NO HORIZONTAL DRY PORTION OF THE ORIGINAL VENT AT
 THE ORIGINAL BATHROOM SINK. TO BE CLEAR, DO NOT CONNECT
 DOWNSTREAM OF THE ORIGINAL VERTICAL VENT. PER WPB FBC
 107.2.1, SHOW THIS ON THE RISER DIAGRAM.
 2) IS THE RELOCATED BREAKROOM SINK GOING TO CONNECT TO
 THE ORIGINAL VERTICAL WASTE/VENT? IF SO, PER WPB FBC
 107.2.12, PROVIDE A PLUMBING NOTE STATING SUCH AND
 PROVIDE FOR AN AIR ADMITTANCE VALVE AT THE FIXTURE IF
 THE DRAIN LENGTH EXCEEDS THE REQUIREMENTS OF FBC PL
 909.1 AND TABLE 909.1. OTHERWISE PROVIDE A SANITARY
 RISER DIAGRAM SHOWING HOW THE FIXTURE WILL BE DRAINED
 AND VENTED.
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  
 19051312 1920 PALM BEACH LAKES BLVD # 114
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-06-11 Cont ID  
Sent By thunt Date 2019-06-11 Time 12:27 Rev Time 0.00
Received By thunt Date 2019-06-11 Time 09:06 Sent To  
Notes
2019-06-11 12:28:33PLUMBING 1ST REVIEW**DENIED**
  
 1) SHT. CVR: OCCUPANT LOAD SHALL BE ROUNDED UP TO 15.
 PROVIDE OVERALL DIMENSION OF THE COMBINED SPACE.
 OCCUPANCY IS LISTED AS STORAGE AND BUSINESS, BUT I AM
 NOT ABLE TO LOCATE THE STORAGE AREA. PLEASE CLARIFY.
 FBC 107.3.5
  
 2) SHT. CRV UNDER ACCESSIBILITY NOTES LIST TO COMPLY
 WITH THE 2014 FLORIDA ACCESSIBILITY. CURRENT CODE IS
 THE 2017 FLORIDA ACCESSIBILITY CODE. FBC 107.2.1
  
 3) SHT. S1 LIST SIDE GRAB BAR AS 11? FROM BACK WALL.
 YOUR SHOW A 42? BAR WHICH MUST BE MOUNTED @ 12? FROM
 REAR WALL TO GET THE REQUIRED 54? OVERALL. FBC-ACC
 604.5.1
  
 4) SHT. S1 TOILET DETAIL SHOWS 15? TO TOP OF TOILET.
 THE TOILET SHALL BE BETWEEN 17?-19? TO THE SEAT.
 FBC-ACC 604.4
  
 5) SHT.S1 TOILET DISPENSER SHALL BE SHOWN AS 7?-9? FROM
 THE FRONT LIP OF THE BOWL. FBC-ACC 604.7
  
 6) SHT.CVR CALLS OUT NO PLUMBING WORK TO BE DONE.
 PLEASE CLARIFY. FBC 107.2.1
  
 7) SHT. S1 TOILET GRAB BAR DETAIL PROVIDE SHOWS GRAB
 BAR MOUNT TO THE CENTER OF BAR. THE 33?-36? SHALL BE TO
 THE TOP OF THE GRIPPING SURFACE. FBC-ACC 609.4
  
 8) WILL THE LAB-SINK ALSO BE USED AS A BREAK ROOM SINK?
 IF SO PLEASE PROVIDE CABINET TOP AND CLEAR FLOOR SPACE
 DETAIL. FBC 107.2.1
  
  
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR