Plan Review Details - Permit 19051293
Plan Review Stops For Permit 19051293
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2019-06-07 Cont ID  
Sent By jgomez Date 2019-06-07 Time 14:35 Rev Time 0.00
Received By jgomez Date 2019-06-07 Time 13:34 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2019-05-30 Cont ID  
Sent By pleduc Date 2019-05-30 Time   Rev Time 0.00
Received By pleduc Date 2019-05-30 Time 10:44 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2019-06-18 Time   Rev Time 0.00
Received By lmarchan Date 2019-06-13 Time 15:48 Sent To  
Notes
2019-06-14 15:48:45RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-06-07 Cont ID  
Sent By jgomez Date 2019-06-07 Time 14:35 Rev Time 0.00
Received By jgomez Date 2019-05-24 Time 14:54 Sent To I
Notes
2019-05-28 14:54:24C12

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2019-06-18 Cont ID  
Sent By ccole Date 2019-06-18 Time 07:59 Rev Time 0.00
Received By ccole Date 2019-06-18 Time 07:59 Sent To I
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-06-06 Cont ID  
Sent By ccole Date 2019-06-06 Time 08:21 Rev Time 0.00
Received By ccole Date 2019-06-05 Time 17:47 Sent To  
Notes
2019-06-06 08:38:551ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19051293
 6/6/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M-1: SHOW HOW OUTSIDE AIR IS BEING PROVIDED TO
 AHU-1. AND HOW IT IS AUTOMATICALLY CONTROLLED- TABLE
 403.1.1 FBC M, AND SECTION C403.2.4.2 FBC EC.
  
 2) M-1: PROVIDE A DUCTED RETURN FROM THE OFFICE 118 TO
 THE AIR HANDLER. THE JUMPER INTO THE CORRIDOR IS NOT
 ALLOWED PER SECTION 601.2 FBC M.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 BUILDING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2019-06-06 Cont ID  
Sent By gjohnson Date 2019-06-06 Time 11:30 Rev Time 0.00
Received By jesmith Date 2019-06-06 Time 11:29 Sent To  
Notes
2019-06-06 11:30:48PLUMBING COMMEMTS: APPROVED
 MASTER PERMIT #18111103
  