2019-07-30 13:02:09BUILDING REVIEW COMMENTS:
  
 W.P.B. PERMIT: 19051257
 REVIEWED: JULY 30, 2019
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER PX4191
 [email protected]
 561-805-6718
  
 FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC[B] = FBC BUILDING
 FBC[EXISTING] = FBC EXISTING BUILDING
 FBC[A] = FBC ACCESSIBILITY
 FBC[E] = FBC ENERGY CONSERVATION
  
 1) C402.3 FBC[E]THE ENERGY SHEET C402-2017 SHOWS ONLY
 U-FACTOR FOR FIXED FENESTRATION. PLEASE ADD U FACTOR
 FOR ENTRY DOORS(WITH >50% GLAZING)
 SHGC SHOWS .25 AND THAT IS FINE FOR ALL FENESTRATION,
 BUT THE CODE DOES ALLOW FOR HIGHER SHGC FOR ORIENTATION
 AND PROJECTION FACTOR. PLEASE ADD TO ENERGY SHEET IF
 YOU WANT TO USE INCREASES.
  
 2) SHEET A7.1 SHOWS DOORS, BUT I DON?T SEE THE
 AUTOMATIC DOOR OR ANY PRESSURES THAT THESE DOORS ARE
 RESISTING.
 ALSO, PLEASE STATE THE FIRE RATINGS FOR DOORS.
  
 3) PLEASE PROVIDE WINDOW SCHEDULE AND CURTAIN WALL
 DATA. WHAT ARE THE CONTRIBUTING SIZES OF EACH AREA AND
 THE PRESSURES THEY RESIST.
 ALSO, IT LOOKS LIKE GLAZING SYSTEMS ABOVE 30 FEET ARE
 GOING TO UTILIZE SMALL IMPACT ONLY. PLEASE ADD NOTE OR
 PROVIDE THIS INFORMATION IN GLAZING SCHEDULE.
  
 4) C402.4 MAXIMUM AREA. PLEASE PROVIDE THE PERCENTAGE
 OF FENESTRATION NOT INCLUDING OPAQUE DOORS OR OPAQUE
 SPANDRELS. IF GREATER THAN 30% PROVIDE METHOD FOR
 INCREASING FENESTRATION.
  
 5) ART IN PUBLIC PLACES. THE CITY OF WEST PALM BEACH
 ART IN PUBLIC PLACES ORDINANCE REQUIREMENT THAT APPLIES
 TO ANY REMODEL OR NEW CONSTRUCTION PROJECT FOR WHICH
 THE PERMIT APPLICATION WAS SUBMITTED AFTER 6/29/14, AND
 THE TOTAL PROJECT CONSTRUCTION COSTS ARE EQUAL TO OR
 GREATER THAN $750,000 WILL NEED TO COMPLY WITH THIS
 ORDINANCE. PER CITY OF WEST PALM BEACH ORDINANCE NO.
 4504-14, AND CITY OF WEST PALM BEACH CODE OF
 ORDINANCES, ARTICLE V, ART IN PUBLIC PLACES, SECTION
 78-123(A) AND SECTION 78-126(A), THE ART ASSESSMENT IS
 1% OF THE TOTAL PROJECT CONSTRUCTION COST. PER CITY OF
 WEST PALM BEACH CODE OF ORDINANCES, ARTICLE V, ART IN
 PUBLIC PLACES, SECTION 78-122, RENOVATION AND NEW
 CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO THE
 ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE
 PROJECTS. SEC. 78-129. - PUBLIC ART ASSESSMENT FOR
 PRIVATE DEVELOPMENT. (A) APPLICABILITY. THE PROVISIONS
 OF THIS ARTICLE AND THE PUBLIC ART ASSESSMENT SECTION
 SHALL APPLY TO ALL PRIVATE DEVELOPMENT PROJECTS,
 INCLUDING NEW CONSTRUCTION, OR THE RENOVATION OR
 IMPROVEMENT OF AN EXISTING BUILDING, WHERE TOTAL
 CONSTRUCTION COSTS ARE EQUAL TO OR GREATER THAN
 $750,000.00. ALL BUILDINGS WITHIN NEW PLANNED
 DEVELOPMENTS SHALL BE ASSESSED CUMULATIVELY TOWARDS
 THIS ART IN PUBLIC PLACES REQUIREMENT, EVEN IF THE
 BUILDINGS ARE PERMITTED SEPARATELY OR DEVELOPED IN
 PHASES. THE PROVISIONS OF THIS SECTION APPLY TO NEW
 DEVELOPMENT OR NEW CONSTRUCTION WITHIN EXISTING PLANNED
 DEVELOPMENTS.
 - THIS PROJECT MEETS THE CRITERIA TO PROVIDE AIPP.
 PLEASE CONTACT: MS. SYBILLE WELTER ART IN PUBLIC PLACES
 COORDINATOR 822-1515 E-MAIL: [email protected]
  
 NOTES:
 PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
  
 PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F
 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2019-07-26 Cont ID  
Sent By jleahy Date 2019-07-26 Time 09:50 Rev Time 0.00
Received By jleahy Date 2019-07-26 Time 09:50 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2019-06-21 Cont ID  
Sent By pleduc Date 2019-06-21 Time   Rev Time 0.00
Received By pleduc Date 2019-06-20 Time 16:24 Sent To  
Notes
2019-06-21 16:11:17THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THE PROPOSED PROJECT HAS AREAS THAT APPEAR TO AFFECT
 REQUIRED EGRESS DOORS, STAIRS AND CORRIDORS. THE LIFE
 SAFETY PLANS DO NOT ADDRESS ALTERNATE ROUTES FOR THESE
 AFFECTED AND/OR PHASING TO ENSURE THERE IS SUFFICIENT
 EXIT ACCESS AND EXITING TO A PUBLIC WAY.
  
 PLEASE PROVIDE DETAILS OF ALTERNATE ROUTING OR A
 NARRATIVE EXPLAINING AND DEFINING, WITH DETAILS, THAT
 THESE EXIT AREAS WILL NOT BE AFFECTED BY THE
 CONSRTUCTION.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-07-30 Cont ID  
Sent By cmontell Date 2019-07-30 Time 14:41 Rev Time 0.00
Received By cmontell Date 2019-07-30 Time 14:41 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2019-07-30 Cont ID  
Sent By cmontell Date 2019-07-30 Time 14:40 Rev Time 0.00
Received By cmontell Date 2019-07-30 Time 14:40 Sent To I
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2019-07-30 Cont ID  
Sent By dbattles Date 2019-07-30 Time 13:21 Rev Time 0.00
Received By dbattles Date 2019-07-30 Time 13:21 Sent To  
Notes
2019-07-30 13:21:44A-SHEETS OK
 ANY NEW SHEETS WILL NEED TO BE DIGITALLY SIGNED.

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 1 Status F Date 2019-07-30 Cont ID  
Sent By dbattles Date 2019-07-30 Time 13:07 Rev Time 0.00
Received By dbattles Date 2019-07-30 Time 13:07 Sent To  
Notes
2019-07-30 13:15:58BUILDING REVIEW COMMENTS:
  
 W.P.B. PERMIT: 19051257
 REVIEWED: JULY 30, 2019
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER PX4191
 [email protected]
 561-805-6718
  
 F.S. 553.79(5) THRESHOLD BUILDING.
 THIS PROJECT MEETS THE DEFINITION OF A THRESHOLD
 BUILDING. THE FOLLOWING IS REQUIRED PRIOR TO
 COMMENCEMENT.
 A) ALL PLANS ARE TO INCLUDE THE THRESHOLD STATEMENT
 REQUIRED BY FS553.79(7)(D). ALL PLANS FOR THE BUILDING
 WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY THE
 ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT
 THAT, TO THE BEST OF THE ARCHITECT?S OR ENGINEER?S
 KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE
 APPLICABLE MINIMUM BUILDING CODES AND THE APPLICABLE
 FIRE SAFETY STANDARDS AS DETERMINED BY THE LOCAL
 AUTHORITY IN ACCORDANCE WITH THIS CHAPTER 553 AND
 CHAPTER 633.
 -PLEASE INCLUDE THIS STATEMENT ON ANY NEW SHEETS
 SUBMITTED BY STRUCTURAL ENGINEER AND AT LEAST MAKE SURE
 IT GETS PUT ON SHEET S1.2 STRUCTURAL INSPECTIO PLAN.
 B) OK - THRESHOLD INSPECTION PLAN FOUN D ON SHEET S1.2,
 FS553.79(5)A). - OK
 C) COMPLETE THE THRESHOLD / SPECIAL INSPECTOR AGREEMENT
 OF UNDERSTANDING. IF PDF OF AGREEMENT IS NEEDED PLEASE
 CONTACT THE BUILDING PLAN REVIEWER AND THEY WILL
 PROVIDE VIA E-MAIL ([email protected])
 D) PROVIDE RESUMES AND COPIES OF LICENSES FOR ALL
 PROPOSED INSPECTORS. PLEASE INCLUDE AS MANY ADDITIONAL
 INSPECTORS AS POSSIBLE BECAUSE THESE ARE THE ONLY
 PEOPLE THAT THE CHIEF BUILDING INSPECTOR WILL ALLOW TO
 BE ON-SITE.
  
  

Review Stop Z ZONING
Rev No 1 Status P Date 2019-06-20 Cont ID  
Sent By ajones Date 2019-06-20 Time 15:02 Rev Time 0.00
Received By ajones Date 2019-06-20 Time 15:02 Sent To Z
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved