Plan Review Details - Permit 19051206
| Plan Review Stops For Permit 19051206 |
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
P |
Date |
2019-06-05 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2019-06-05 |
Time |
08:26 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2019-06-05 |
Time |
05:53 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2019-05-30 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2019-05-30 |
Time |
14:33 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2019-05-28 |
Time |
12:59 |
Sent To |
|
|
| Notes |
| 2019-05-28 13:43:55 | 1) THE RECORD GAS DRAWINGS ON FILE IN THE CITY SHOW THE | | | FOLLOWING BTU VALUES FOR THE LISTED APPLIANCES: | | | POOL HEATER - 400,000 BTU'S | | | DRYER - 40,000 BTU'S | | | FIRELOGS - 44,000 | | | GENERATOR - 560,000 BTU'S | | | RANGE - 300,000 BTU'S | | | WATER HEATER - 75,000 | | | TOTAL BTU LOAD - 1,419,000 BTU'S | | | | | | THE GAS DRAWING SUBMITTED FOR THIS PERMIT SHOWS THE | | | FOLLOWING BTU VALUES: | | | POOL HEATER - 125,000 BTU'S | | | DRYER - 22,000 BTU'S | | | FIRELOGS - 32,000 BTU'S | | | GENERATOR - 387,000 BTU'S | | | NEW STOVE - 145,000 | | | WATER HEATER??? WHERE IS THE BTU LOAD? | | | TOTAL BTU LOAD - 711,000 ?? | | | | | | SUBMIT INFORMATION AS TO WHERE YOU OBTAINED THE BTU | | | LOADS OF THE GAS APPLIANCES SHOWN ON YOUR DRAWINGS. | | | THERE IS QUITE A DISCREPANCY IN THE LOADS OF APPLIANCES | | | ON YOUR DRAWING. WPB AMEND. TO FBC SEC. 107.2.1, | | | 107.3.5.3. | | | 2) THE 3/4 INCH LINE TO THE NEW STOVE IS UNDERSIZED PER | | | TABLE 402.4(2). THE MAXIMUM BTU LOAD ON A 3/4 INCH LINE | | | AT 60 FEET IS 137,000 BTU'S. | | | 3) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE RANGE | | | THAT SHOWS THE CORRECT BTU LOAD. THE BURNERS ADD UP TO | | | 62,200 BTU'S. WHAT IS THE BTU LOAD OF THE OVEN? THE GAS | | | PLAN THAT HAS BEEN SUBMITTED SHOWS THE STOVE AT 145,000 | | | BTU'S. CLARIFY. | | | 4) THE STOVE SHALL BE LISTED AND LABELED PER 2017 FBC- | | | FUEL GAS SEC.301.3. THE SUBMITTED SPECIFICATIONS DO NOT | | | SHOW THIS. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2019-06-05 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2019-06-05 |
Time |
08:26 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2019-05-31 |
Time |
14:25 |
Sent To |
I |
|
| Notes |
| 2019-06-03 14:25:49 | RESUB ROUTED TO TKLARGE |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2019-05-30 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2019-05-30 |
Time |
14:33 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2019-05-23 |
Time |
13:17 |
Sent To |
|
|
| Notes |
| 2019-05-24 13:18:02 | PLUMB <5K |
|
|
|