Plan Review Details - Permit 19051156
Plan Review Stops For Permit 19051156
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-07-10 Cont ID  
Sent By jleahy Date 2019-07-10 Time 07:25 Rev Time 0.00
Received By jleahy Date 2019-07-10 Time 07:25 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-06-11 Cont ID  
Sent By jpearson Date 2019-06-11 Time 08:22 Rev Time 0.00
Received By jpearson Date 2019-06-11 Time 08:22 Sent To I
Notes
2019-06-11 08:22:48CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. WIND LOAD DESIGN CRITERIA DETAILED IN NOTE 10 AND 11
 ON SHEET E3.01 DOES NOT MATCH THE WIND LOAD DESIGN
 REQUIRED FOR THIS AREA. ADDITIONALLY, THE EXCEPTION
 NUMBER 7 MENTIONED FOR 1609.1.1 IN NOTE 10 IS FOR
 SCREEN ENCLOSURES. PROVIDE CORRECTION. FBC 1609.3,
 1609.1.1
 2. SHEET E3.00 HAS A BLOCK NOTE, AND NOTE 5, THAT
 STATES A WIND LOADING CALCULATION, WHICH IS
 SIGNED/SEALED BY A STRUCTURAL ENGINEER, SHALL BE
 PROVIDED TO CONFIRM THE PROPOSED INSTALLATION SHALL
 MEET THE FBC WIND LOAD REQUIREMENTS. THIS HAS NOT BEEN
 PROVIDED. PROVIDE CORRECTION. WPB FBC 107.2.1; FBC
 1609.1
 3. PROVIDE VOLTAGE DROP CALCULATIONS TO COMPLY WITH FBC
 ENERGY CONSERVATION. FBC EC C405.6.3
 4. SHEET E2.01 SHOWS DETAILS FOR A RECEPTACLE POLE.
 WHERE WILL THESE BE INSTALLED? ARE THEY IN ADDITION TO
 THE GFCI RECEPTACLES THAT WILL BE INSTALLED ON LIGHT
 POLES? FOR GFCI RECEPTACLES, WHETHER ON LIGHT POLES OR
 A SEPARATE POLE, WILL THESE BE CONTROLLED THROUGH THE
 LIGHTING CONTACTOR CONTROLLED BY PHOTOCELL, OR POWERED
 CONTINUALLY?THE PLAN DOES NOT SPECIFY CONTROL FOR
 RECEPTACLES. PROVIDE CLARIFICATION. WPB FBC 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-07-10 Cont ID  
Sent By jleahy Date 2019-07-10 Time 07:24 Rev Time 0.00
Received By jleahy Date 2019-06-20 Time 15:00 Sent To  
Notes
2019-06-20 15:00:27RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2019-06-11 Time   Rev Time 0.00
Received By lmarchan Date 2019-05-22 Time 16:21 Sent To  
Notes
2019-06-10 08:45:18TOLMARCHAN
2019-05-23 16:21:29ROUTED TO ZONING INBOX

Review Stop Z ZONING
Rev No 2 Status P Date 2019-06-28 Cont ID  
Sent By aaponte Date 2019-06-28 Time 17:57 Rev Time 0.00
Received By aaponte Date 2019-06-28 Time 17:57 Sent To E
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2019-06-10 Cont ID  
Sent By aaponte Date 2019-06-10 Time 08:45 Rev Time 0.00
Received By aaponte Date 2019-06-10 Time 08:45 Sent To E
Notes
***NONE***