Plan Review Details - Permit 19051134
Plan Review Stops For Permit 19051134
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-09-16 Cont ID  
Sent By jleahy Date 2019-09-16 Time 07:55 Rev Time 0.00
Received By jleahy Date 2019-09-16 Time 07:55 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-07-08 Cont ID  
Sent By jleahy Date 2019-07-08 Time 14:34 Rev Time 0.00
Received By jleahy Date 2019-07-08 Time 14:34 Sent To  
Notes
2019-07-08 15:56:15FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 GROUNDING ELECTRODES TO BE COMMON RUN A JUMPER FROM
 GENERATOR GE TO SERVICE GE. 250.58
  
 YOU HAVE THREE (3) #1S FROM TRANFERSWITCH TO TAP BOX
 AND THEN FOUR (4) #4S TO 150A DISCONNECTS, MISSING AND
 EQUIPMENT GROUND FROM TRANSFERSWITCH.
  
 NOTE AT TOP OF DRAWING ABOUT NEUTRAL ????

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-09-16 Cont ID  
Sent By jleahy Date 2019-09-16 Time 07:55 Rev Time 0.00
Received By jleahy Date 2019-09-11 Time 11:25 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-07-08 Cont ID  
Sent By jleahy Date 2019-07-08 Time 14:35 Rev Time 0.00
Received By jleahy Date 2019-06-24 Time 10:29 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2019-09-16 Cont ID  
Sent By jleahy Date 2019-09-16 Time 07:56 Rev Time 0.00
Received By jleahy Date 2019-09-16 Time 07:56 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2019-07-08 Cont ID  
Sent By jleahy Date 2019-07-08 Time 14:35 Rev Time 0.00
Received By jleahy Date 2019-07-08 Time 14:35 Sent To  
Notes
***NONE***