Plan Review Details - Permit 19051127
Plan Review Stops For Permit 19051127
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-06-21 Cont ID  
Sent By dbattles Date 2019-06-21 Time 07:50 Rev Time 0.00
Received By dbattles Date 2019-06-21 Time 07:50 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-06-10 Cont ID  
Sent By dbattles Date 2019-06-10 Time 12:53 Rev Time 0.00
Received By dbattles Date 2019-06-10 Time 12:53 Sent To  
Notes
2019-06-10 12:53:41BUILDING REVIEW COMMENTS:
  
 W.P.B. PERMIT: 19051127
 REVIEWED: JUNE 10, 2019
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER PX4191
 [email protected]
 561-805-6718
  
 FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC[B] = FBC BUILDING
 FBC[EXISTING] = FBC EXISTING BUILDING
 FBC[A] = FBC ACCESSIBILITY
  
 1) 454.1.3.1 FBC[B]DECKS AND WALKWAYS. DOORED ACCESS
 POINTS FROM PUBLIC ROOMS SUCH AS LOBBIES OR CLUB HOUSES
 NEED NOT BE THROUGH GATES IF THE DOOR(S) MEET THE SAME
 SELF-CLOSING, SELF-LATCHING REQUIREMENTS AS A GATE.
 GATES SHALL OPEN OUTWARD AWAY FROM THE POOL AREA. A
 LATCHED, LOCKABLE GATE SHALL BE PLACED IN THE FENCE
 WITHIN 10 FEET (3048 MM) OF THE CLOSEST POINT BETWEEN
 THE POOL AND THE EQUIPMENT AREA FOR SERVICE ACCESS.
 -PLEASE SHOW HOW THE INTERIOR ACCESS DOORS MEET THE
 REQUIRMENTS IN 454.1.3.1.9
  
 2) 1004.1 FBC[B] DESIGN OCCUPANT LOAD. IN DETERMINING
 MEANS OF EGRESS REQUIREMENTS, THE NUMBER OF OCCUPANTS
 FOR WHOM MEANS OF EGRESS FACILITIES ARE PROVIDED SHALL
 BE DETERMINED IN ACCORDANCE WITH THIS SECTION.
 -WHAT IS THE OCCUPANT LOAD ON THE POOL DECK AND HOW IS
 EGRESS PROVIDED?
  
 NOTES:
  
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  
 PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F
 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME
 [email protected]
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-06-21 Cont ID  
Sent By dbattles Date 2019-06-21 Time 07:50 Rev Time 0.00
Received By dbattles Date 2019-06-18 Time 10:11 Sent To  
Notes
2019-06-20 10:12:00RESUB ROUTED TO DBATTLES

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-06-10 Cont ID  
Sent By dbattles Date 2019-06-10 Time 12:53 Rev Time 0.00
Received By dbattles Date 2019-05-23 Time 13:16 Sent To  
Notes
2019-05-24 13:16:27ROUTED TO ZONING INBOX

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 1 Status P Date 2021-02-13 Cont ID  
Sent By shill Date 2021-02-13 Time 10:31 Rev Time 0.00
Received By shill Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By pgreilic Date 2019-07-12 Time 11:26 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date   Cont ID  
Sent By   Date 2019-05-29 Time   Rev Time 0.00
Received By pgreilic Date 2019-05-29 Time 13:59 Sent To B
Notes
2019-05-29 14:01:00PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]