| 2019-06-10 12:53:41 | BUILDING REVIEW COMMENTS: |
| | |
| | W.P.B. PERMIT: 19051127 |
| | REVIEWED: JUNE 10, 2019 |
| | |
| | DYLAN BATTLES |
| | BUILDING PLANS EXAMINER PX4191 |
| | [email protected] |
| | 561-805-6718 |
| | |
| | FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017) |
| | FBC[B] = FBC BUILDING |
| | FBC[EXISTING] = FBC EXISTING BUILDING |
| | FBC[A] = FBC ACCESSIBILITY |
| | |
| | 1) 454.1.3.1 FBC[B]DECKS AND WALKWAYS. DOORED ACCESS |
| | POINTS FROM PUBLIC ROOMS SUCH AS LOBBIES OR CLUB HOUSES |
| | NEED NOT BE THROUGH GATES IF THE DOOR(S) MEET THE SAME |
| | SELF-CLOSING, SELF-LATCHING REQUIREMENTS AS A GATE. |
| | GATES SHALL OPEN OUTWARD AWAY FROM THE POOL AREA. A |
| | LATCHED, LOCKABLE GATE SHALL BE PLACED IN THE FENCE |
| | WITHIN 10 FEET (3048 MM) OF THE CLOSEST POINT BETWEEN |
| | THE POOL AND THE EQUIPMENT AREA FOR SERVICE ACCESS. |
| | -PLEASE SHOW HOW THE INTERIOR ACCESS DOORS MEET THE |
| | REQUIRMENTS IN 454.1.3.1.9 |
| | |
| | 2) 1004.1 FBC[B] DESIGN OCCUPANT LOAD. IN DETERMINING |
| | MEANS OF EGRESS REQUIREMENTS, THE NUMBER OF OCCUPANTS |
| | FOR WHOM MEANS OF EGRESS FACILITIES ARE PROVIDED SHALL |
| | BE DETERMINED IN ACCORDANCE WITH THIS SECTION. |
| | -WHAT IS THE OCCUPANT LOAD ON THE POOL DECK AND HOW IS |
| | EGRESS PROVIDED? |
| | |
| | NOTES: |
| | |
| | -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS |
| | OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) |
| | SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT |
| | DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER |
| | SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" |
| | OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS |
| | APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE |
| | NEED "VOID", RENDERING THEM NOT USABLE. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F |
| | 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME |
| | [email protected] |
| | |
| | |
| | |