| 2019-05-27 13:33:43 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. PLAN SHOWS A NEW 400 AMP TRANSFER SWITCH CONNECTING |
| | TO AN EXISTING GENERATOR. AS THE GENERATOR IS NOT |
| | CAPABLE OF SUPPLYING 400 AMPS, A LOAD CALCULATION WILL |
| | BE REQUIRED TO DETERMINE THE GENERATOR HAS THE CAPACITY |
| | REQUIRED, OR PROVIDE DETAILS OF LOAD MANAGEMENT. PLAN |
| | ALSO SHOWS A NEW AC UNIT. IS THIS A REPLACEMENT, OR A |
| | NEW SYSTEM? PROVIDE ACCURATE LOAD CALCULATION INCLUDING |
| | ALL LOADS AND EXPLANATIONS AS REQUIRED. NEC 220, 702.4; |
| | FBC RE E3602.2 |
| | 2. THE NEC AND FBC SPECIFIED FOR DESIGN IS NOT THE |
| | CURRENT CODE. PROVIDE CORRECTION. FBC PREFACE (ALSO SEE |
| | CURRENT CODES ABOVE) |
| | 3. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR |
| | SERVICE INCLUDING INFORMATION FROM THE POWER COMPANY |
| | STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR |
| | THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE |
| | SERVICE EQUIPMENT IS ADEQUATE. NEC 110.9, 110.10; FBC |
| | RE E3606.3 |
| | 4. PROVIDE AIC RATING OF SERVICE RATED TRANSFER SWITCH |
| | AND PANELS. NEC 110.3, 110.9; FBC RE E3606.3 |
| | 5. RISER DIAGRAM STATES THE WIRE SIZE AS (3) SOD. WHAT |
| | DOES THIS MEAN? THIS ABBREVIATION NOT SHOWN IN LEGEND. |
| | PROVIDE WIRE SIZES. WPB FBC 107.2.1 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD |
| | SHEETS. |
| | |