Plan Review Details - Permit 19051097
Plan Review Stops For Permit 19051097
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2019-08-30 Cont ID  
Sent By dbattles Date 2019-08-30 Time 13:43 Rev Time 0.00
Received By dbattles Date 2019-08-30 Time 13:43 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-08-06 Cont ID  
Sent By jbrooks Date 2019-08-06 Time 14:30 Rev Time 0.00
Received By jbrooks Date 2019-08-06 Time 14:30 Sent To  
Notes
2019-08-06 14:31:21JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS TUESDAY & THURSDAY 7:00 AM TO 3:00 PM
 (561) 805-6716 ALTERNATE: CONTACT SAMANTHA HILL (561)
 805-6724
 [email protected]
  
 1ST REVIEW: FBC 2017 6TH EDITION
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. AN ENGINEERING EVALUATION AND ANALYSIS THAT
 ESTABLISHES THE STRUCTURAL ADEQUACY OF THE ALTERED
 STRUCTURE SHALL BE PREPARED BY A REGISTERED DESIGN
 PROFESSIONAL AND SUBMITTED TO THE CODE OFFICIAL. AS PER
 907.4.1 AND 907.4.2 FBC-EB. PROVIDE TWO SETS.
 2. FBC B 107.2.1. PLEASE CLARIFY; CONNECTION DETAIL
 PAGE S-1 SHOWS 2?X 6? WOOD BEAMS, DECK FRAMING PLAN
 PAGE S-2 SHOWS 2?X 10? WOOD BEAMS AT PERIMETER. VERIFY
 JOIST HANGERS TO BE USED.
 3. FBC B 107.2.1. PLEASE CLARIFY; ELEVATION DETAILS
 PAGE S-1. WEST ELEVATION DETAIL SHOULD BE NORTH
 ELEVATION AND EAST ELEVATION DETAIL SHOULD BE WEST
 ELEVATION.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-06-13 Cont ID  
Sent By jbrooks Date 2019-06-13 Time 09:41 Rev Time 0.00
Received By jbrooks Date 2019-06-13 Time 09:40 Sent To  
Notes
2019-06-13 09:42:49JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS TUESDAY & THURSDAY 7:00 AM TO 3:00 PM
 (561) 805-6716 ALTERNATE: CONTACT SAMANTHA HILL (561)
 805-6724
 [email protected]
  
 1ST REVIEW: FBC 2017 6TH EDITION
 1ST REVIEW FBC 2017 EXISTING BUILDING
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. CHANGE OCCUPANCY; MIXED USE GROUP B & R2 AS PER
 508.1 FBC
 2. CHANGE ALTERATION LEVEL TO LEVEL 3 ALTERATION AS PER
 505.1 FBC-EB
 3. AN ENGINEERING EVALUATION AND ANALYSIS THAT
 ESTABLISHES THE STRUCTURAL ADEQUACY OF THE ALTERED
 STRUCTURE SHALL BE PREPARED BY A REGISTERED DESIGN
 PROFESSIONAL AND SUBMITTED TO THE CODE OFFICIAL. AS PER
 907.4.1 AND 907.4.2 FBC-EB.
 4. THE STRUCTURAL FRAME AND ROOF CONSTRUCTION
 SUPPORTING IMPOSED LOADS UPON THE ROOF BY ANY ROOFTOP
 STRUCTURE SHALL COMPLY WITH THE REQUIREMENTS OF TABLE
 601. THE FIRE-RESISTANCE REDUCTION PERMITTED BY TABLE
 601, NOTE A, SHALL NOT APPLY TO ROOFS CONTAINING
 ROOFTOP STRUCTURES. AS PER 1510.9 FBC.
 5. ROOFTOP STRUCTURES NOT REGULATED BY SECTIONS 1510.2
 THROUGH 1510.7 SHALL COMPLY WITH SECTIONS 1510.8.1
 THROUGH 1510.8.5, AS APPLICABLE.
 6. HANDRAILS AND GUARDS SHALL BE DESIGNED TO RESIST A
 LINEAR LOAD OF 50 POUNDS PER LINEAR FOOT (PLF) (0.73
 KN/M) IN ACCORDANCE WITH SECTION 4.5.1 OF ASCE 7. GLASS
 HANDRAIL ASSEMBLIES AND GUARDS SHALL ALSO COMPLY WITH
 SECTION 2407.
 7. PLEASE INCREASE THE VALUATION OF THE PROPOSED
 PROJECT TO REFLECT THE ADDITIONAL REQUIREMENTS.
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2019-08-22 Cont ID  
Sent By pleduc Date 2019-08-22 Time   Rev Time 0.00
Received By pleduc Date 2019-08-22 Time 12:42 Sent To B
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-07-22 Cont ID  
Sent By pleduc Date 2019-07-22 Time   Rev Time 0.00
Received By pleduc Date 2019-07-22 Time 10:36 Sent To B
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2019-06-10 Cont ID  
Sent By pleduc Date 2019-06-10 Time   Rev Time 0.00
Received By pleduc Date 2019-06-10 Time 15:02 Sent To B
Notes
2019-06-10 15:35:40THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) SHEET S 1 - THE PROPOSED PROJECT INDICATED A DOOR;
 HOWEVER, THE SIZE OF THE DOOR IS NOT PROVIDED.
  
 THIS DOOR SHALL BE WIDE ENOUGH TO MEET THE MINIMUM
 WIDTH FOR AN EXIT.
  
 PER NFPA 101, CH 7
  
 7.3.4.1.2 IN EXISTING BUILDINGS, THE WIDTH OF EXIT
 ACCESS SHALL BE
 PERMITTED TO BE NOT LESS THAN 28 IN.
  
 PLEASE PROVIDE THE DOOR WIDTH.
  
  
  
 2) SHEET S 1 - THERE IS NO DOOR HARDWARE INDICATED FOR
 THE DOOR.
  
 7.2.1.5 LOCKS, LATCHES, AND ALARM DEVICES.
 7.2.1.5.1 DOOR LEAVES SHALL BE ARRANGED TO BE OPENED
 READILY FROM
 THE EGRESS SIDE WHENEVER THE BUILDING IS OCCUPIED.
  
 7.2.1.5.3 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE
 OF A KEY, A
 TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR OPERATION FROM
 THE EGRESS
 SIDE.
  
 PLEASE PROVIDE DOOR HARDWARE DETAILS.
  
  
 3) SHEET S 1 - THERE ARE NO ROOF DECKING MANUFACTORES
 SPECIFICATION SHEETS.
  
 PLEASE PROVIDE.
  
  
 4) SHEET S 1 - IT APPEARS ON THE EAST ELEVATION THERE
 IS A STEP DOWN IN THE MIDDLE OF THE DECKING.
  
 THE DECK FLOOR PLAN DOES NOT SHOW IT.
  
 PLEASE CLARIFY AND PROVIDE THE STEP DIMENSION COMPLIANT
 WITH THE CODE.
  
  
 5) SHEET S 1 - THERE IS NO INDICATION OF THE TRAVEL
 DISTANCE TO THE EXIT DISCHARGE GOING THROUGH THE DOOR
 TO THE INTERIOR OF THE BUILDING.
  
 PLEASE PROVIDE THE EXISTING EXIT PATH AND TRAVEL
 DISTANCE THROUGH THE INTERIOR OF THE BUILDING TO THE
 EXIT DISCHARGE.
  
 PER NFPA 101, CH 12
  
 12.2.6 TRAVEL DISTANCE TO EXITS.
 12.2.6.1 TRAVEL DISTANCE SHALL BE MEASURED IN
 ACCORDANCE WITH
 SECTION 7.6.
  
 PLEASE SHOW FLOOR PLAN AND PROVIDE DETAILS
  
  
  
 6) THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 7) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-08-30 Cont ID  
Sent By dbattles Date 2019-08-30 Time 13:46 Rev Time 0.00
Received By dbattles Date 2019-08-20 Time 15:40 Sent To  
Notes
2019-08-21 16:08:36ROUTED FROM ZONING TO PERMIT LIBRARIAN 8/21/19 EL
2019-08-20 15:40:32RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-08-06 Cont ID  
Sent By jbrooks Date 2019-08-06 Time 14:32 Rev Time 0.00
Received By jbrooks Date 2019-07-11 Time 14:49 Sent To  
Notes
2019-07-18 16:14:56ROUTED FROM ZONING TO PERMIT LIBRARIAN 7/18/19 EL
2019-07-12 14:49:25RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-06-13 Cont ID  
Sent By jbrooks Date 2019-06-13 Time 09:43 Rev Time 0.00
Received By jbrooks Date 2019-05-22 Time 14:19 Sent To  
Notes
2019-06-06 15:37:01TO LMARCHAN
2019-06-05 14:19:45ROUTED TO ZONING INBOX

Review Stop Z ZONING
Rev No 3 Status P Date 2019-08-21 Cont ID  
Sent By elevesqu Date 2019-08-21 Time 16:08 Rev Time 0.00
Received By elevesqu Date 2019-08-21 Time 16:08 Sent To FIRE
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2019-07-18 Cont ID  
Sent By elevesqu Date 2019-07-18 Time 16:14 Rev Time 0.00
Received By elevesqu Date 2019-07-18 Time 16:14 Sent To FIRE
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2019-06-06 Cont ID  
Sent By aaponte Date 2019-06-06 Time 15:33 Rev Time 0.00
Received By aaponte Date 2019-06-06 Time 15:33 Sent To FIRE
Notes
***NONE***