Plan Review Details - Permit 19051069
Plan Review Stops For Permit 19051069
Review Stop G GAS REVIEW
Rev No 2 Status P Date 2019-06-03 Cont ID  
Sent By tklarge Date 2019-06-03 Time 09:06 Rev Time 0.00
Received By tklarge Date 2019-06-03 Time 08:09 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2019-05-28 Cont ID  
Sent By tklarge Date 2019-05-28 Time 08:08 Rev Time 0.00
Received By tklarge Date 2019-05-28 Time 06:17 Sent To  
Notes
2019-05-28 06:35:581.) SUBMIT TWO COPIES OF THE MANUFACTURER'S
 SPECIFICATION SHEETS / INSTALLATION MANUAL FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54,
 NFPA 58, AND FBC-2017 FUEL GAS CODE SEC. 402.2, AND
 301.3. GAS APPLIANCES SHALL BE LISTED AND LABELED. THE
 INSTALLATION MANUALS FOR ALL GAS APPLIANCES / EQUIPMENT
 SHALL BE ONSITE AT THE TIME OF INSPECTION. FGC
 SEC.305.1, THE SPECS FOR THE RANGE ARE PARTIAL AND DO
 NOT SHOW THE EQUIPMENT IS LISTED AND LABELED.
 2) SUBMIT TWO COPIES OF A FLOOR PLAN SHOWING THE
 LOCATION OF THE TANKLESS WATER HEATER AND THE LOCATION
 AND DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN
 RELATION TO THE WATER HEATER. THE LOCATION OF THE WATER
 HEATER SHALL COMPLY WITH THE MANUFACTURER'S
 INSTALLATION INSTRUCTIONS. THE HOUSE PLAN / FLOOR PLAN
 CAN BE HAND DRAWN. WPB AMEND. TO FBC SEC. 107.2.1.
 3) INDICATE ON THE PLAN IF THE TANKLESS WATER HEATERS
 ARE INSIDE OR OUTSIDE.WPB AMEND. TO FBC SEC. 107.2.1.
 4) SUBMIT COMBUSTION AIR CALCULATIONS FOR THE GAS
 APPLIANCES. 2017 FBC-FUEL GAS SEC. 304.1. WHERE
 COMBUSTION AIR IS PROVIDED BY THE BUILDING?S MECHANICAL
 VENTILATION SYSTEM, THE SYSTEM SHALL PROVIDE THE
 SPECIFIED COMBUSTION AIR RATE IN ADDITION TO THE
 REQUIRED VENTILATION AIR. 2017 FBC-FUEL GAS
 SEC.304.9.3.
 5) EACH OF THE APPLIANCES SERVED SHALL BE INTERLOCKED
 WITH THE MECHANICAL AIR SUPPLY SYSTEM TO PREVENT MAIN
 BURNER OPERATION WHEN THE MECHANICAL AIR SUPPLY SYSTEM
 IS NOT IN OPERATION. 2017 FBC-FUEL GAS SEC.304.9.2.
 6) SUBMIT TWO COPIES OF A DETAIL SHOWING THE TYPE OF
 VENT, LOCATION, SIZE, TERMINATION POINT, HEIGHT ABOVE
 THE ROOF AND ANCHORING DETAILS OF THE GAS VENT(S) PER
 2017 FBC-FUEL GAS SECS. 502 THRU 505 ( IF APPLICABLE).
 7) EMERGENCY HOOD SHUT DOWN SHUT OFF VALVE SHALL BE
 BELOW THE CEILING. THE MANUAL SHUTOFF VALVE SHALL BE
 UPSTREAM. UNION TO BE DOWN STREAM OF MANUAL VALVE.
 SECS. 10.4.1, 10.4.3, 10.4.4, 10.5.1 OF NFPA 96-14.
 8) INDICATE ON THE PLAN IF THE TANKLESS WATER HEATER IS
 REPLACING AN EXISTING TANKLESS WATER HEATER OR IS IT
 REPLACING A STORAGE TANK TYPE WATER HEATER OR IS IT
 BEING ADDED TO THE EXISTING HOT WATER SYSTEM? WPB
 AMEND. TO FBC SEC. 107.2.1.
 9) PUT THE NAME OF THIS BUSINESS ON THE PERMIT
 APPLICATIONS. CITY RECORDS DO NOT CURRENTLY SHOW ANY
 PREVIOUS PERMITS FOR THIS SPACE OR ANY BUSINESS TAX
 RECEIPT FOR ANY PREVIOUS BUSINESS AT THIS UNIT ADDRESS.
 IS THIS A CHANGE OF OCCUPANCY PER THE 2017 FBC-EXISTING
 BUILDING CODE CHAPTER 10? WPB AMEND. TO FBC SEC.
 107.2.1.
 10) LIST THE LAST PREVIOUS BUSINESS AND OCCUPANCY TYPE
 THAT WAS LOCATED IN THIS SPACE. WPB AMEND. TO FBC SEC.
 107.2.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-06-03 Cont ID  
Sent By tklarge Date 2019-06-03 Time 09:06 Rev Time 0.00
Received By tklarge Date 2019-05-30 Time 13:24 Sent To  
Notes
2019-05-31 13:24:28RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-05-28 Cont ID  
Sent By tklarge Date 2019-05-28 Time 08:08 Rev Time 0.00
Received By tklarge Date 2019-05-23 Time 13:27 Sent To  
Notes
2019-05-24 13:27:49PLUMB<5K