Plan Review Details - Permit 19051059
Plan Review Stops For Permit 19051059
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-07-25 Cont ID  
Sent By cthroop Date 2019-07-25 Time 15:54 Rev Time 0.00
Received By cthroop Date 2019-07-19 Time 07:02 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-06-18 Cont ID  
Sent By cthroop Date 2019-06-18 Time 10:58 Rev Time 0.00
Received By cthroop Date 2019-06-14 Time 16:18 Sent To  
Notes
2019-06-18 11:03:30BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC M = FLORIDA BUILDING CODE MECHANICAL 2017 6TH
 EDITION
 FBC P = FLORIDA BUILDING CODE PLUMBING 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 1. DESIGNER TO SPECIFY INSULATION TYPE AND R - VALUE
 FOR CEILING INSULATION.
 2. ENERGY SUBMITTAL SHALL INCLUDE THIS VALUE IN IT'S
 CALCULATIONS.
 FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405
 (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE
 SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE
 COMPLIANCE BY SECTION 405.
  
 3. PROVIDE SITE DRAINAGE PLAN.
 FBC R401.3 SITE DRAINAGE
 PROVIDE TWO SETS OF A SITE DRAINAGE PLAN SHOWING
 COMPLIANCE WITH FBC R401.3 DRAINAGE.
 SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER
 CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION THAT
 DOES NOT CREATE A HAZARD.
 LOTS SHALL BE GRADED TO DRAIN SURFACE WATER AWAY FROM
 FOUNDATION WALLS. THE GRADE SHALL FALL A MINIMUM OF 6
 INCHES WITHIN THE FIRST 10 FEET.
 EXCEPTION: WHERE LOT LINES, WALLS, SLOPES OR OTHER
 PHYSICAL BARRIERS PROHIBIT 6 INCHES OF FALL WITHIN 10
 FEET, DRAINS OR SWALES SHALL BE CONSTRUCTED TO ENSURE
 DRAINAGE AWAY FROM THE STRUCTURE.
 IMPERVIOUS SURFACES WITHIN 10 FEET OF THE BUILDING
 FOUNDATION SHALL BE SLOPED A MINIMUM OF
 2 PERCENT AWAY FROM THE BUILDING.
  
 FBC R 401.3 (DRAINAGE)
 FBC 107.2.5 (SITE PLAN)
 FBC 110.9 (IMPACT OF CONSTRUCTION)
  
 4. PROVIDE LANDING AT EXTERIOR GARAGE DOOR.
 R311.3 FLOORS AND LANDINGS AT EXTERIOR DOORS.
  
 THERE SHALL BE A LANDING OR FLOOR ON EACH SIDE OF EACH
 EXTERIOR DOOR. THE WIDTH OF EACH LANDING SHALL NOT BE
 LESS THAN THE DOOR SERVED. EVERY LANDING SHALL HAVE A
 MINIMUM DIMENSION OF 36 INCHES (914 MM) MEASURED IN THE
 DIRECTION OF TRAVEL. EXTERIOR LANDINGS SHALL BE
 PERMITTED TO HAVE A SLOPE NOT TO EXCEED 1/4 UNIT
 VERTICAL IN 12 UNITS HORIZONTAL (2-PERCENT).
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-07-25 Cont ID  
Sent By cthroop Date 2019-07-25 Time 15:54 Rev Time 0.00
Received By cthroop Date 2019-07-19 Time 07:02 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-06-18 Cont ID  
Sent By jpearson Date 2019-06-18 Time 15:07 Rev Time 0.00
Received By jpearson Date 2019-06-18 Time 15:07 Sent To I
Notes
2019-06-18 11:26:09CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. RISER DIAGRAM SHOWS THREE # 6 WIRES FEEDING THE A/C
 COMPRESSORS WITH ONE #10 GROUND. WHY IS THERE THREE
 WIRES FEEDING THIS UNIT WHEN THIS IS SHOWN AS A SINGLE
 PHASE SERVICE? CLARIFY AND/OR CORRECT AS NEEDED. WPB
 FBC 107.2.1
 2. FEEDERS TO PANEL A AND PANEL B MUST INCLUDE AND
 EQUIPMENT GROUNDING CONDUCTOR SIZED PER CODE. PROVIDE
 CORRECTION. NEC 250.122; FBC RE E3704.6, 3607.3.1
 3. RISER DIAGRAM SHOWS THREE 2/0 CONDUCTORS FEEDING
 PANEL A AND PANEL B, FED FROM A 200 AMP BREAKER. WIRE
 SIZES FROM NEC 310.15(B)(7), OR FBC RE E3603.1, CAN
 ONLY BE USED WHEN THE SERVICE CONDUCTOR SUPPLIES 100%
 OF THE LOAD. SINCE THIS IS NOT THE CASE, PROVIDE
 CORRECTED WIRE SIZE FROM MAIN TO PANELS, SIZED FOR 200
 AMPS. NEC 310.15(B)(7) AND (B)(16); FBC RE E3603.1,
 E3705.1
 4. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT
 SERVICE. SHOW ON PLAN. NEC 250.94; FBC RE E3609.3
 5. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR
 SERVICE INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT IS ADEQUATE. PROVIDE AIC RATING OF
 SERVICE PANEL. NEC 110.9, 110.10; FBC RE E3606.3
 6. NOTE 5 STATES THAT ALL WIRING SHALL BE A MINIMUM
 SIZE 12 GAUGE, BUT THE PANEL SCHEDULES CALL FOR SEVERAL
 15 AMP CIRCUITS WITH 14 GAUGE WIRE. CORRECTE
 DISCREPANCY. WPB FBC 107.2.1
 7. PANEL B SHOWS BATHROOM GFCI RECEPTACLE CIRCUITS
 NUMBER 23 AND 25 AS 15 AMP CIRCUITS ON 14 GAUGE WIRE. A
 MINIMUM OF ONE 20 AMPERE BRANCH CIRCUIT SHALL BE
 PROVIDED TO SUPPLY BATHROOM RECEPTACLE OUTLET(S). SUCH
 CIRCUITS SHALL HAVE NO OTHER OUTLETS. PROVIDE
 CORRECTION. NEC 210.11(C)(3) , FBC RE E3703.4
 8. AFCI PROTECTION SHOWN IS NOT CODE COMPLIANT. ALL
 BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15-
 AND 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY
 ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES,
 DENS, BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS,
 HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS
 SHALL BE AFCI PROTECTED. THIS INCLUDES LIGHTING AND
 POWER OUTLETS AND RECEPTACLES. SOME AREAS REQUIRE BOTH
 AFCI AND GFCI PROTECTION. PROVIDE CORRECTION. NEC
 210.8, 210.12; FBC RE E3902
 9. PROVIDE COMPLIANCE: A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS. A NOTE WILL SUFFICE.
 FBC EC C405.1, R404.1
 10. GFCI PROTECTION IS REQUIRED FOR ALL RECEPTACLE
 OUTLETS IN GARAGE, INCLUDING THE GARAGE DOOR OPENER.
 PROVIDE CORRECTION. NEC 210.8; FBC RE E3902.2
 11. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC
 210.8(D); FBC RE E3902.10
 12. PANEL SCHEDULES SHOW 5 SMALL APPLIANCE CIRCUITS,
 BUT ONLY 2 ARE INCLUDED IN THE LOAD CALCULATION.
 PROVIDE ACCURATE LOAD CALCULATION IN COMPLIANCE WITH
 FBC RE E3602.2.
 13. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A
 NOTE WILL SUFFICE. NEC 406.12; FBC RE E4002.14
 14. SEVERAL AREAS DO NOT COMPLY WITH THE WALL SPACING
 REQUIREMENTS FOR OUTLETS. RECEPTACLES SHALL BE
 INSTALLED SO THAT NO POINT MEASURED HORIZONTALLY ALONG
 THE FLOOR LINE OF ANY WALL SPACE IS MORE THAN 6 FEET
 FROM A RECEPTACLE OUTLET. THE WALL SPACING REQUIREMENTS
 FOR KITCHEN COUNTER SPACE STATE THAT RECEPTACLE OUTLETS
 SHALL BE INSTALLED SO THAT NO POINT ALONG THE WALL LINE
 IS MORE THAN 24 INCHES MEASURED HORIZONTALLY FROM A
 RECEPTACLE OUTLET IN THAT SPACE. THE PLAN PROVIDED DOES
 NOT MEET THIS CODE IN SOME AREAS. PROVIDE CORRECTION.
 NEC 210.52(C)(1); FBC RE E3901
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-07-25 Cont ID  
Sent By cthroop Date 2019-07-25 Time 15:54 Rev Time 0.00
Received By cthroop Date 2019-07-02 Time 15:03 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2019-06-18 Time   Rev Time 0.00
Received By lmarchan Date 2019-05-29 Time 15:27 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2019-07-31 Cont ID  
Sent By lmarchan Date 2019-07-31 Time 11:43 Rev Time 0.00
Received By lmarchan Date 2019-07-30 Time 09:04 Sent To  
Notes
2019-07-31 11:43:49RECEIPT - MU-219-023878-000 - $0.00 - NO FEES DUE
2019-07-30 09:05:047/30/19 EMAILED IMPACT FEE OFFICE. LEM

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2019-06-18 Cont ID  
Sent By cthroop Date 2019-06-18 Time 10:57 Rev Time 0.00
Received By cthroop Date 2019-06-14 Time 16:18 Sent To  
Notes
2019-06-18 10:57:53PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected] .

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2019-06-18 Cont ID  
Sent By cthroop Date 2019-06-18 Time 10:49 Rev Time 0.00
Received By cthroop Date 2019-06-14 Time 16:18 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-07-17 Cont ID  
Sent By gjohnson Date 2019-07-17 Time 17:36 Rev Time 0.00
Received By gjohnson Date 2019-07-17 Time 17:19 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2019-06-14 Cont ID  
Sent By gjohnson Date 2019-06-14 Time 13:50 Rev Time 0.00
Received By gjohnson Date 2019-06-14 Time 12:44 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2019-06-18 Cont ID  
Sent By cthroop Date 2019-06-18 Time 10:49 Rev Time 0.00
Received By cthroop Date 2019-06-14 Time 16:18 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2019-07-25 Cont ID  
Sent By cthroop Date 2019-07-25 Time 15:54 Rev Time 0.00
Received By cthroop Date 2019-07-19 Time 07:02 Sent To  
Notes
2019-07-17 17:37:21 
 PLUMBINGL SHEET: PER THE WPB AMENDMENTS TO THE FBC,
 EACH SHEET OF PLAN IS REQUIRED TO BE SIGNED AND SEALED
 BY THE PERSON RESPONSIBLE FOR THE DESIGN. A DIGITAL
 PLAN REQUIRES A DIGITAL SIGNATURE WITH THE PROPER THIRD
 PARTY VERIFICATION. SELF-CERTIFICATION IS NOT
 ACCEPTABLE FOR ENGINEERS. ADDITIONALLY, THE DIGITAL
 SIGNATURE MUST INCLUDE THE STATEMENT "SIGNED AND
 SEALED" AS PER FAC 61G15-23.004. PROVIDE CORRECTION.
 WPB FBC 107.1; FS 471/481
 ELECTRICAL SHEETS: PER THE WPB AMENDMENTS TO THE FBC,
 EACH SHEET OF PLAN IS REQUIRED TO BE SIGNED AND SEALED
 BY THE PERSON RESPONSIBLE FOR THE DESIGN. A DIGITAL
 PLAN REQUIRES A DIGITAL SIGNATURE WITH THE PROPER THIRD
 PARTY VERIFICATION. SELF-CERTIFICATION IS NOT
 ACCEPTABLE FOR ENGINEERS. ADDITIONALLY, THE DIGITAL
 SIGNATURE MUST INCLUDE THE STATEMENT "SIGNED AND
 SEALED" AS PER FAC 61G15-23.004. PROVIDE CORRECTION.
 WPB FBC 107.1; FS 471/481

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2019-06-18 Cont ID  
Sent By cthroop Date 2019-06-18 Time 10:49 Rev Time 0.00
Received By cthroop Date 2019-06-14 Time 16:18 Sent To  
Notes
2019-06-18 10:57:05BUILDING PLAN REVIEW - DIGITAL SIGNATURE AND SEAL
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 THE FOLLOWING PLAN PAGES DO NOT HAVE THE APPROPRIATE
 SIGNATURE AND SEAL FROM THE DESIGN PROFESSIONAL.
 A.04, A.05, E.01, E.02 & P.01
  
 1. DIGITAL SIGNATURES/SEALS ARE NOT IN ACCORDANCE WITH
 FS 471, FS 481 AS NOTED. NEW SHEETS SUBMITTED IN THE
 NEXT REVIEW CYCLE REQUIRE REVIEW.
  
 2. UPLOAD VIA THE PROJECTDOX PORTAL WITH DIGITAL
 SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE
 THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT.
  
  
  
  

Review Stop Z ZONING
Rev No 2 Status P Date 2019-07-03 Cont ID  
Sent By llouie Date 2019-07-03 Time   Rev Time 0.00
Received By llouie Date 2019-07-03 Time   Sent To  
Notes
2019-07-03 15:04:09ZONING PROVISO:
  
 1.) SEPARATE PERMIT REQUIRED FOR DRIVEWAY/HARDSCAPE.

Review Stop Z ZONING
Rev No 1 Status F Date 2019-06-12 Cont ID  
Sent By llouie Date 2019-06-12 Time   Rev Time  
Received By llouie Date 2019-06-12 Time   Sent To  
Notes
2019-06-12 09:57:52** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) SETBACK LINES DEPICTED IN THE SITE PLAN (SHEET
 A.01) ARE INCONSISTENT WITH THE SETBACK REQUIREMENTS OF
 THE ZONING AND LAND DEVELOPMENT REGULATIONS (ZLDRS).
 PLEASE ADDRESS FOR CONSISTENCY.
  
 2.) SHOW THE SETBACK DISTANCE ALL PROPOSED STRUCTURES
 TO THE PROPERTY LINES (I.E. BUILDING, SITE WALL,
 DRIVEWAY, ETC.)
  
 3.) HOW TALL IS THE PROPOSED SITE WALL FROM THE
 EXTERIOR OF THE WALL AT GRADE? PLEASE PROVIDE NOTE THE
 DIMENSION IN THE SITE PLAN. ALSO NOTE THAT A SEPARATE
 PERMIT AND REVIEW WILL BE REQUIRED FOR THE SITE WALL.
 [ZLDR S.94-302
  
 4.) THE SITE WALL SEEMS TO EXTEND BEYOND THE PROPERTY
 LINE AND ENCROACH INTO THE ADJACENT YARD. THIS IS NOT
 PERMITTED. PLEASE ADDRESS.
  
 5.) CLEARLY SHOW THE EXTENT OF THE PROPOSED NEW SITE
 WALL AND THE EXISTING CONCRETE WALL IN THE SITE PLAN.
  
 6.) PROVIDE DIMENSION OF THE WIDTH OF THE DRIVEWAY AT
 THE PROPERTY LINE. THE WIDTH OF THE DRIVEWAY CANNOT
 EXCEED 20 FT. [ZLDR S.94-312]
  
 7.) STRUCTURAL OVERHANGS (I.E. TRELLIS, ETC.) SHALL NOT
 EXTEND MORE THAN 3 FT. INTO ANY SETBACK. PLEASE SHOW
 DIMENSIONS TO DEMONSTRATE CONSISTENCY WITH THE ZLDRS.
 [ZLDRS S.94-305(B)(2)]
  
 8.) IN THE ELEVATION DRAWINGS, SHOW THE HEIGHT OF THE
 STRUCTURE AT THE TALLEST POINT PER THE DEFINITION OF
 HEIGHT IN THE ZLDRS.
  
 9.) BUILDING ELEVATIONS DO NOT SEEM TO MATCH THE FLOOR
 PLANS. PLEASE ADDRESS FOR CONSISTENCY.
  
 10.)THE VALUE OF THE CONSTRUCTION ($400,000.00) EXCEEDS
 50% OF THE STRUCTURE'S VALUE ($246,169.00) ACCORDING TO
 THE P.B.C. PROPERTY APPRAISER'S OFFICE; THEREFORE,
 PURSUANT TO SECTION 94-441(C)(2) OF THE ZONING AND LAND
 DEVELOPMENT REGULATIONS (ZLDR), THE LANDSCAPE ON THE
 SITE SHALL BE IN COMPLIANCE WITH ALL APPLICABLE
 REGULATIONS FOUND IN ARTICLE XIV OF THE ZLDR. IF THE
 SITE CONFORMS TO ARTICLE XIV, THEN TWO (2) COPIES OF A
 LANDSCAPE PLAN DEMONSTRATING COMPLIANCE SHALL BE
 INCLUDED WITH THE PERMIT RE-SUBMITTAL. IF THE SITE DOES
 NOT CONFORM TO ARTICLE XIV, THEN PRIOR TO THE ZONING
 APPROVAL OF THIS PERMIT A SEPARATE LANDSCAPE PERMIT AND
 IRRIGATION PERMIT SHALL BE SUBMITTED SHOWING MATERIAL
 TO BRING THE SITE INTO CONFORMITY.
  
 11.) THERE SEEMS TO BE OVERHEAD LINES AT THE REAR OF
 THE PROPERTY, WHICH INDICATES THAT A UTILITY EASEMENT
 EXISTS. HOWEVER, THIS IS NOT DEPICTED IN THE SURVEY.
 ALL EASEMENTS SHALL BE PROVIDED IN THE SURVEY, AS NO
 STRUCTURES CAN ENCROACH INTO ANY EASEMENTS WITHOUT
 CONSENT FROM THE HOLDER OF THE EASEMENT(S).
  
  
 NOTES:
  
 * REVISIONS TO THE PLANS MAY RESULT IN ADDITIONAL
 COMMENTS.
  
 * SEPARATE PERMITS REQUIRED FOR: DRIVEWAY/HARDSCAPES,
 LANDSCAPING.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  
 * ZONE: SF7