Plan Review Details - Permit 19051030
Plan Review Stops For Permit 19051030
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-09-27 Cont ID  
Sent By jgomez Date 2019-09-27 Time 18:37 Rev Time 0.00
Received By jgomez Date 2019-09-27 Time 17:26 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-06-25 Cont ID  
Sent By jgomez Date 2019-06-25 Time 13:44 Rev Time 0.00
Received By jgomez Date 2019-06-25 Time 11:20 Sent To  
Notes
2019-06-25 13:45:5708/01/19 TALKED TO VICTOR VAZQUEZ. NO PERMITS FOR
 SHUTTERS IN THIS HOUSE.
  
  
 RESIDENTIAL (R3) ADDITION/ALTERATION BUILDING REVIEW
 COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 NOTE:
 SEC. 702.6 FBC-EXISTING BUILDING MATERIALS AND METHODS.
 ALL NEW WORK SHALL COMPLY WITH THE MATERIALS AND
 METHODS REQUIREMENTS IN THE FLORIDA BUILDING CODE,
 BUILDING; FLORIDA BUILDING CODE, ENERGY CONSERVATION;
 FLORIDA BUILDING CODE, MECHANICAL; AND FLORIDA BUILDING
 CODE, PLUMBING, AS APPLICABLE, THAT SPECIFY MATERIAL
 STANDARDS, DETAIL OF INSTALLATION AND CONNECTION,
 JOINTS, PENETRATIONS, AND CONTINUITY OF ANY ELEMENT,
 COMPONENT, OR SYSTEM IN THE BUILDING.
  
  
 1- ENGINEER OF RECORD TO SPECIFY THE WINDOWS AND DOORS
 DESIGN PRESSURES. SEC. R301.2.1 FBC-RESIDENTIAL.
  
 2-PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 A) EXTERIOR DOOR. PROVIDE FLORIDA PRODUCT APPROVAL
 COVER PAGE THAT CORRESPONDS TO DRAWINGS SUBMITTED. DOOR
 PRODUCT APPROVAL SUBMITTED IS INCOMPLETE. NEED TO
 PROVIDE COMPLETE FLORIDA PRODUCT APPROVAL, INCLUDING
 THE FLORIDA PRODUCT APPROVAL COVER PAGE THAT
 CORRESPONDS TO THE DRAWINGS SUBMITTED. THE FLORIDA
 PRODUCT APPROVAL IS REQUIRED BECAUSE IT SHOWS IF
 PRODUCT IS APPROVED AND CURRENT CODE IN EFFECT.
  
 B)SINGLE HUNG WINDOWS. PROVIDE FLORIDA PRODUCT APPROVAL
 COVER PAGE THAT CORRESPONDS TO DRAWINGS SUBMITTED.
 WINDOW PRODUCT APPROVAL SUBMITTED IS INCOMPLETE. NEED
 TO PROVIDE COMPLETE FLORIDA PRODUCT APPROVAL, INCLUDING
 THE FLORIDA PRODUCT APPROVAL COVER PAGE THAT
 CORRESPONDS TO THE DRAWINGS SUBMITTED. THE FLORIDA
 PRODUCT APPROVAL IS REQUIRED BECAUSE IT SHOWS IF
 PRODUCT IS APPROVED AND CURRENT CODE IN EFFECT.
 NOTE: CLEARLY MARK WINDOW GLASS TYPE ON PAGE 1 OF 5 OF
 DRAWINGS SUBMITTED TO VERIFY COMPLIANCE WITH THE
 ENGINEER'S CALCULATED DESIGN PRESSURES.
  
 3-ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 4- SHUTTERS INSTALLATION SCHEDULE SUBMITTED:
 A) DESIGN PRESSURES SHOWN ON COLUMN 3 ARE TOO LOW.
 COORDINATE WITH DESIGN PRESSURES CALCULATED BY THE
 ENGINEER OF RECORD AND REVISE AS REQUIRED. SEC.
 R301.2.1 FBC-RESIDENTIAL.
  
 B) SHUTTER MOUNTING CONDITION TYPE SHOWN ON COLUMN 4 IS
 INCORRECT. THE CONNECTION TYPE IS FOR EXAMPLE WALL
 MOUNTED, BUILD-OUT MOUNTED, ETC. SEE SHEET 2 OF 4 OF
 SHUTTERS PRODUCT APPROVAL DRAWING SUBMITTED AND REVISE
 AS REQUIRED. SEC. 107.2.1 CITY AMENDMENTS.
  
 C)MINIMUM EDGE DISTANCE SHOWN ON COLUMN 8 IS INCORRECT.
 SEE ANCHOR SCHEDULE AND ANCHOR NOTE #6 ON SHEET 3 OF 4
 OF SHUTTERS PRODUCT APPROVAL DRAWING SUBMITTED AND
 REVISE AS REQUIRED. SEC. 107.2.1 CITY AMENDMENTS.
  
 5- PLANS DON'T PROVIDE A NAME FOR THE PROPOSED ROOM.
 ENGINEER OF RECORD TO SPECIFY ON PLANS WHAT'S IS THE
 PROPOSED USE OF THE ROOM. PLEASE NAME THE ROOM. SEC.
 107.2.1 CITY AMENDMENTS.
  
 6- THE LANDING AT THE EXTERIOR DOOR NEED TO BE 36" MIN.
 AS REQUIRED BY SEC. R311.3 FBC-RESIDENTIAL. NOTE:
 TYPICAL WALL SECTION ON SHEET 3/5 SHOWS NEW LANDING TO
 BE 31". REVISE TYPICAL WALL SECTION AND FLOOR PLAN AS
 REQUIRED.
  
 7-WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE, INSERT CORRECTED PAGES INTO THE SUBMITTAL AND
 REMOVE/VOID THE PREVIOUSLY REVIEWED SHEETS.
  
 PLEASE DON'T STAPLE OLD DRAWINGS/DOCUMENTS . SUBMIT OLD
 DRAWINGS/DOCUMENTS FOR REFERENCE.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-09-18 Cont ID  
Sent By ppetty Date 2019-09-18 Time 10:41 Rev Time 0.00
Received By ppetty Date 2019-09-18 Time 10:32 Sent To  
Notes
2019-09-18 10:41:48PROVISO 210.52-A-1 WALL SPACING

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-06-19 Cont ID  
Sent By jpearson Date 2019-06-19 Time 14:18 Rev Time 0.00
Received By jpearson Date 2019-06-19 Time 09:54 Sent To  
Notes
2019-06-19 13:59:06CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. RISER DIAGRAM PROVIDED STATES THAT THERE IS A 150
 AMP SERVICE EXISTING. LOAD CALCULATION STATES THE LOAD
 WILL BE 152 AMPS, WHICH EXCEED THE CAPACITY OF THE
 SERVICE. PROVIDE CORRECTION. NEC 215.2, 310.15, 408.30,
 408.36; FBC RE 3602.2, E3603.1
 2. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL
 LOADS SPECIFIED IN FBC RESIDENTIAL 3602.2. NEC 220; FBC
 RE E3602.2
 3. ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT,
 SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS INSTALLED IN
 KITCHENS, FAMILY ROOMS, DINING ROOMS, LIVING ROOMS,
 PARLORS, LIBRARIES, DENS, BEDROOMS, SUN-ROOMS,
 RECREATIONS ROOMS, CLOSETS, HALLWAYS, LAUNDRY AREAS AND
 SIMILAR ROOMS OR AREAS SHALL BE AFCI PROTECTED. PROVIDE
 CORRECTION. NEC 210.12; FBC RE E3902.16
 4. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A
 NOTE WILL SUFFICE. NEC 406.12; FBC RE E4002.14
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-09-26 Cont ID  
Sent By hmoser Date 2019-09-26 Time 14:57 Rev Time 0.00
Received By hmoser Date 2019-09-06 Time 11:51 Sent To  
Notes
2019-09-06 11:51:48R07

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-06-25 Cont ID  
Sent By jgomez Date 2019-06-25 Time 13:46 Rev Time 0.00
Received By jgomez Date 2019-05-21 Time 14:52 Sent To I
Notes
2019-05-22 14:52:33R08

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2019-09-27 Cont ID  
Sent By jgomez Date 2019-06-24 Time 08:15 Rev Time 0.00
Received By jgomez Date 2019-06-24 Time 08:15 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2019-09-26 Cont ID  
Sent By hmoser Date 2019-09-26 Time 14:57 Rev Time 0.00
Received By hmoser Date 2019-09-26 Time 14:57 Sent To I
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2019-06-11 Cont ID  
Sent By cmontell Date 2019-06-11 Time 09:22 Rev Time 0.00
Received By cmontell Date 2019-06-11 Time 09:22 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2019-09-25 Cont ID  
Sent By pgreilic Date 2019-09-25 Time 09:17 Rev Time 0.00
Received By pgreilic Date 2019-09-25 Time 08:41 Sent To  
Notes
2019-09-25 09:18:09PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date   Cont ID  
Sent By pgrehili Date 2019-06-04 Time   Rev Time 0.00
Received By pgreilic Date 2019-06-04 Time 14:51 Sent To  
Notes
2019-06-04 14:52:13PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]