Plan Review Details - Permit 19051024
Plan Review Stops For Permit 19051024
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-06-17 Cont ID  
Sent By jleahy Date 2019-06-17 Time 11:56 Rev Time 0.00
Received By jleahy Date 2019-06-17 Time 11:56 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-06-13 Cont ID  
Sent By cthroop Date 2019-06-13 Time 08:37 Rev Time 0.00
Received By cthroop Date 2019-06-13 Time 08:37 Sent To HIST
Notes
2019-06-13 09:24:35ADDRESS: 444 29TH ST PERMIT # 19051024
 TYPE: GEN-RES
  
 BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC M = FLORIDA BUILDING CODE MECHANICAL 2017 6TH
 EDITION
 FBC P = FLORIDA BUILDING CODE PLUMBING 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 1. PROVIDE A FOUNDATION.
 1A. SITE BUILT - PROVIDE DESIGN OF FOUNDATION WITH
 MEANS OF ATTACHMENT AND FASTENERS.
 1B. SELECT CONCRETE MOUNTING PAD FROM MANUFACTURERS
 INSTALLATION INSTRUCTIONS. PRE-FAB. PAD SHALL BE
 GENERATOR SPECIFIC.
  
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-06-17 Cont ID  
Sent By jleahy Date 2019-06-17 Time 11:56 Rev Time 0.00
Received By jleahy Date 2019-06-17 Time 11:56 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-06-13 Cont ID  
Sent By cthroop Date 2019-06-13 Time 11:18 Rev Time 0.00
Received By cthroop Date 2019-06-13 Time 11:18 Sent To  
Notes
2019-06-13 12:43:37ADDRESS: 444 29TH ST PERMIT # 19051024
 TYPE: GEN-RES
  
 ELECTRICAL PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC M = FLORIDA BUILDING CODE MECHANICAL 2017 6TH
 EDITION
 FBC P = FLORIDA BUILDING CODE PLUMBING 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 1. SEE LEGEND NOTE # 5 - LOCATION OF 1ST MEANS OF
 DISCONNECT TO BE DETERMINED.
 E3607.2 LOCATION OF GROUNDING ELECTRODE CONDUCTOR
 CONNECTION.
  
 2. SEE LEGEND NOTE # 6 - CONDUCTORS OTHER THAN SEVICE
 CONDUCTORS SHALL NOT BE INSTALLED IN THE SAME RACEWAY.
 E3601.4 OTHER CONDUCTORS IN RACEWAY OR CABLE. NEC 230.7
 & EXHIBIT 230.16.
  
 3. SPECIFY WHICH PRE-FABRICATED CONCRETE PAD WILL BE
 USED.
 SEE MANUFACTURERS INSTALLATION INSTRUCTIONS.
  
  
 4. PROVIDE COPY OF CONTRACT SIGNED BY OWNER TO VERIFY
 VALUE.
 CITY OF WPB CHPT. 1 ? VALUE
 109.3 BUILDING PERMIT VALUATIONS.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2019-06-04 Cont ID  
Sent By thunt Date 2019-06-04 Time 07:32 Rev Time 0.00
Received By thunt Date 2019-06-04 Time 07:32 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status N Date 2019-06-14 Cont ID  
Sent By fmittner Date 2019-06-14 Time 12:38 Rev Time 0.00
Received By fmittner Date 2019-06-14 Time 12:38 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-06-14 Cont ID  
Sent By lmarchan Date 2019-06-14 Time 13:56 Rev Time 0.00
Received By lmarchan Date 2019-05-21 Time 13:07 Sent To  
Notes
2019-05-22 13:07:42ROUTED TO ZONING INBOX

Review Stop Z ZONING
Rev No 1 Status P Date 2019-05-28 Cont ID  
Sent By mcruz Date 2019-05-28 Time 14:06 Rev Time 0.00
Received By mcruz Date 2019-05-28 Time 14:04 Sent To  
Notes
***NONE***