| Plan Review Stops For Permit 19050952 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2019-08-16 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2019-08-16 |
Time |
08:49 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2019-08-16 |
Time |
08:49 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2019-05-31 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2019-05-31 |
Time |
16:04 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2019-05-31 |
Time |
16:04 |
Sent To |
|
|
| Notes |
| 2019-05-31 16:04:32 | ****CORRECTIONS**** | | | W.P.B. PERMIT: 19050952 | | | REVIEWED: MAY 31, 2019 | | | | | | DYLAN BATTLES | | | BUILDING PLANS EXAMINER PX4191 | | | [email protected] | | | 561-805-6718 | | | | | | FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017) | | | FBC[EXISTING] = FBC EXISTING BUILDING | | | FBC[E] = FBC ENERGY CONSERVATION | | | FBC[R] = FBC RESIDENTIAL | | | | | | 107.5.3 FBC[AMENDED] PLEASE PROVIDE PRODUCT APPROVAL | | | FOR EURO WALL SHOWN ON PLAN WITH DESIGNATION T. ALSO, | | | UPDATE DESIGNATION U THAT STATES BI-FOLD IMPACT. | | | | | | -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW | | | OF MATERIALS REQUESTED. | | | | | | -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS | | | OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) | | | SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT | | | DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER | | | SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" | | | OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS | | | APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE | | | NEED "VOID", RENDERING THEM NOT USABLE. | | | | | | PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F | | | 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2019-06-17 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2019-06-17 |
Time |
07:46 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2019-06-17 |
Time |
07:37 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2019-10-11 |
|
|
Cont ID |
|
| Sent By |
cmontell |
Date |
2019-10-11 |
Time |
15:28 |
Rev Time |
0.00 |
| Received By |
cmontell |
Date |
2019-10-11 |
Time |
15:28 |
Sent To |
|
|
| Notes |
| 2019-10-08 13:57:06 | ROUTED TO HMOSER'S DESK |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2019-08-22 |
|
|
Cont ID |
|
| Sent By |
cmontell |
Date |
2019-08-22 |
Time |
14:24 |
Rev Time |
0.00 |
| Received By |
cmontell |
Date |
2019-08-22 |
Time |
14:24 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2019-06-24 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2019-06-24 |
Time |
15:21 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2019-05-20 |
Time |
13:44 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2019-10-11 |
|
|
Cont ID |
|
| Sent By |
cmontell |
Date |
2019-10-11 |
Time |
15:27 |
Rev Time |
0.00 |
| Received By |
cmontell |
Date |
2019-10-11 |
Time |
15:27 |
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2019-08-22 |
|
|
Cont ID |
|
| Sent By |
cmontell |
Date |
2019-08-22 |
Time |
14:23 |
Rev Time |
0.00 |
| Received By |
cmontell |
Date |
2019-08-22 |
Time |
14:23 |
Sent To |
I |
|
| Notes |
| 2019-08-22 14:23:42 | PLAN DENIED | | | | | | 1) PROVIDE MANUFACTURES SPECS. FOR RANGE HOOD | | | PER SECTION M1503.4 MAKE UP AIR REQUIRED 2017 | | | RESIDENTIAL CODE. | | | | | | 2) PROVIDE ENERGY CALCULATIONS FOR ADDITION. PER | | | SECTION M1401.3 SIZING | | | | | | 3) NEED MECHANICAL PLAN PER 2017 - FLORIDA BUILDING | | | CODE - BUILDING SEC. [A] 107.2 CONSTRUCTION DOCUMENTS. | | | | | | CHRIS MONTELLO | | | 805-6733 | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2019-05-25 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2019-05-25 |
Time |
05:14 |
Rev Time |
0.00 |
| Received By |
cmontell |
Date |
2019-05-25 |
Time |
05:09 |
Sent To |
|
|
| Notes |
| 2019-05-25 05:14:01 | PLAN DENIED | | | | | | 1) PROVIDE MANUFACTURES SPECS. FOR RANGE HOOD | | | PER SECTION M1503.4 MAKE UP AIR REQUIRED 2017 | | | RESIDENTIAL CODE. | | | | | | 2) PROVIDE ENERGY CALCULATIONS FOR ADDITION. PER | | | SECTION M1401.3 SIZING | | | | | | 3) NEED MECHANICAL PLAN PER 2017 - FLORIDA BUILDING | | | CODE - BUILDING SEC. [A] 107.2 CONSTRUCTION DOCUMENTS. | | | | | | CHRIS MONTELLO | | | 805-6733 | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2019-08-22 |
|
|
Cont ID |
|
| Sent By |
jesmith |
Date |
2019-08-22 |
Time |
12:51 |
Rev Time |
0.00 |
| Received By |
jesmith |
Date |
2019-08-22 |
Time |
11:43 |
Sent To |
|
|
| Notes |
| 2019-08-22 12:51:35 | PLUMBING COMMEMTS: APPROVED W/PROVISO | | | 1. MASTER BATH AND POWDER ROOM SANITARY PIPING TO | | | COMFORM TO THE REQIREMENTS OF FBC RES P3108.1. SEE | | | REDLINED COMMENT AND CORRECTION ON PLAN SHEET E1 | | | SANITARY RISER DIAGRAM. | | | 2. ADDED LAUNDRY AT THE BRANCH TO EXISTING BATH. SEE | | | REDLINED COMMENT ON PLAN SHEET E1 SANITARY RISER | | | DIAGRAM. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2019-06-04 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2019-06-04 |
Time |
11:24 |
Rev Time |
0.00 |
| Received By |
jesmith |
Date |
2019-06-04 |
Time |
11:24 |
Sent To |
|
|
| Notes |
| 2019-06-04 11:24:35 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL | | | MANUAL REVISED 2017 | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION | | | FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH | | | EDITION | | | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION | | | FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION | | | NFPA 30A | | | FAC= FLORIDA ADMINISTRATIVE CODE | | | FS = FLORIDA STATUTES | | | | | | | | | 1ST REVIEW | | | PLUMBING COMMENTS: DENIED | | | 1. RE: PLAN SHEET E-1; SANITARY RISER DIAGRAM | | | A. PER FBC RES P3108.1, EACH WET VENTED FIXTURE DRAIN | | | SHALL CONNECT INDEPENDENTLY TO THE HORIZONTAL WET VENT. | | | THIS IS APPLICABLE TO THE MASTER BATH WATER CLOSET, | | | BIDET AND SHOWER. BY CONNECTING A VERTICAL DRY VENT TO | | | THE WATER CLOSET HORIZONTAL FIXTURE DRAIN AHEAD OF THE | | | BIDET CONNECTION, THIS SITUATION CAN BE CORRECTED. | | | B. PER WPB FBC 107.2.1, SIZE ALL BRANCHES INCLUDING | | | THOSE CONNECTED TO EXISTING BATHROOM AND LAUNDRY. | | | C. PER WPB FBC 107.2.1, SHOW BRANCH CONNECTION TO | | | EXISTING LAUNDRY. | | | | | | | | | END OF COMMENTS. | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED | | | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. | | | | | | | | | | | | JERALD SMITH | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | EMAIL [email protected] | | | PHONE 561-805-6715 | | | | | | 19050952 224 POTTER RD | | | | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2019-06-24 |
|
|
Cont ID |
|
| Sent By |
awooten |
Date |
2019-06-24 |
Time |
|
Rev Time |
|
| Received By |
awooten |
Date |
2019-06-24 |
Time |
|
Sent To |
|
|
| Notes |
|
|