Plan Review Details - Permit 19050941
Plan Review Stops For Permit 19050941
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2019-09-09 Cont ID  
Sent By pvalenti Date 2019-09-09 Time 14:25 Rev Time 0.00
Received By pvalenti Date 2019-09-09 Time 14:25 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-07-16 Cont ID  
Sent By shill Date 2019-07-16 Time 09:50 Rev Time 0.00
Received By shill Date 2019-07-16 Time 09:50 Sent To  
Notes
2019-07-16 09:52:16****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. SEE PAGE 13, A .9 FACTOR IS TO BE APPLIED TO SHUTTER
 SPACING IF THE EDGE DISTANCE IS LESS THAN 3.5"; REVISE
 INSTALLATION SCHEDULE ACCORDINGLY.
  
 2. MOUNTING TYPE WW WAS SPECIFIED; ON THE PRODUCT
 APPROVAL THAT IS FOR WOOD SUBSTRATE. SEE PAGE 12,
 MOUNTING TYPES A AND D WERE CIRCLED. REVISE
 INSTALLATION SCHEDULE.
  
 3. YOU MAY RESUBMIT UP TO TWO PAGES, ALONG WITH A
 COMPLETED RESUBMITTAL FORM, VIA EMAIL TO
 [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT
 NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE
 RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-05-21 Cont ID  
Sent By shill Date 2019-05-21 Time 09:54 Rev Time 0.00
Received By shill Date 2019-05-21 Time 09:54 Sent To  
Notes
2019-05-21 09:54:47****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 THE INSTALLATION SCHEDULE SUBMITTED HAS THE FOLLOWING
 ISSUES, FBC R 301:
  
 1. SEE SHEET 13 OF THE PRODUCT APPROVAL; AN EDGE
 DISTANCE OF 3" REQUIRES A .78 FACTOR APPLIED TO THE
 ANCHOR SPACING SPECIFIED IN THE CHARTS.
  
 2. THE SHUTTER SPAN FOR ACCORDIONS SHOULD BE THE BLADE
 LENGTH. SEE OPENING 1, 108 X 64; 115" IS SPECIFIED AS
 SHUTTER SPAN. OPENING 3, 27X64 SPECIFIES 34". PLEASE
 REVISE.
  
 3. CONNECTION TYPE SPECIFIED IS W, BUT THAT IS FOR WOOD
 SUBSTRATE AND MOUNTING TYPES A, D, AND I ARE CIRCLED ON
 SHEETS 12, 14.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-09-09 Cont ID  
Sent By pvalenti Date 2019-09-09 Time 14:31 Rev Time 0.00
Received By pvalenti Date 2019-09-05 Time 11:32 Sent To  
Notes
2019-09-06 11:32:46RESUB ROUTED TO PVALENTI

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-07-16 Cont ID  
Sent By shill Date 2019-07-16 Time 09:52 Rev Time 0.00
Received By shill Date 2019-07-09 Time 09:50 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-05-21 Cont ID  
Sent By shill Date 2019-05-21 Time 09:54 Rev Time 0.00
Received By shill Date 2019-05-20 Time 11:33 Sent To  
Notes
***NONE***