Plan Review Details - Permit 19050931
Plan Review Stops For Permit 19050931
Review Stop AD ADDRESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-08-20 Cont ID  
Sent By jwitmer Date 2019-08-20 Time 10:57 Rev Time 0.00
Received By jwitmer Date 2019-08-20 Time 10:33 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-07-15 Cont ID  
Sent By jwitmer Date 2019-07-15 Time 08:50 Rev Time 0.00
Received By jwitmer Date 2019-07-15 Time 06:46 Sent To  
Notes
2019-07-15 08:49:592017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19050931
 ADD: 2478 METROCENTRE BLVD. E
 CONT: BLUEFIN CONSTRUCTION, INC.
 TEL: 954-428-1011
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. JULY 15/ 2019
 ACTION: DENIED
  
 1) THE COVERSHEET G001:
  
 1A) PLEASE UPDATE CODE REFERENCE MAXIMUM COMMON PATH OF
 TRAVEL THE PLANS REFERENCE TABLE 1014.3. IN THE 2017
 FBC-B COMMON PATH OF TRAVEL IS FOUND IN SECTION 106.2.1
 AND TABLE 1006.2.1.
  
 1B) PLEASE UPDATE THE CODE REFERENCE FOR THE MAXIMUM
 TRAVEL DISTANCE. THE COVERSHEET REFERENCES TABLE
 1016.2. IN THE 2017 FBC-B THE MAXIMUM TRAVEL DISTANCES
 ARE FOUND IN TABLE 1017.2 OF THE 2017 FBC-B. PLEASE
 UPDATE THE CODE REFERENCES.
  
 1C) PLEASE UPDATE THE CODE REFERENCES FOR MINIMUM
 CORRIDOR WIDTH, THE PLANS STATE SECTION 1018.2. IN THE
 2017 FBC-B SECTION 1020.2 & TABLE 1020.2 WOULD BE THE
 SECTIONS TO REFERENCE.
  
 1D) THE COVERSHEET ALSO LIST DEAD ENDS FOUND IN SECTION
 1018.4. IN THE 2017 FBC-B DEAD ENDS ARE FOUND 1020.4.
 PLEASE UPDATE PLANS TO THE 2017 FBC-B.
  
 1E) PLEASE ALSO UPDATE THE CODE REFERENCE FOR THE NO.
 OF EXITS, SECTION 1021. IN THE 2017 FBC-B THE NUMBER OF
 REQUIRED EXITS OR EXIT ACCESS DOORWAYS IS FOUND UNDER
 SECTION & TABLE 1006.2.1.
  
 1F) THE NUMBER OF REQUIRED EXITS OR EXIT ACCESS TO
 EXITS PER STORY IS FOUND IN SECTION & TABLE 1006.3.1.
  
 1G) IT IS ASSUMED THAT THIS IS A NON-SPRINKLERED
 BUILDING WITH THE VARIOUS DISTANCES GIVEN IN THE ABOVE
 TABLES. 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED.
  
 2) SHEET 004-A121 THE FLOOR PLAN INDICATES THE CORRIDOR
 BUT THE LENGTH IS NOT GIVEN. WHEN THE PLANS ARE
 CALIBRATED FOR MEASUREMENTS THE LENGTH OF THE DEAD END
 CORRIDOR IS APPROXIMATELY 28 FEET. IT IS ASSUMED THIS
 IS A NON-SPRINKLERED BUILDING LIMITING THE LENGTH OF A
 DEAD END CORRIDOR TO 20 FEET. THE LIFE SAFETY SHEET
 DOES NOT INDICATE WITH AN EXIT DIRECTIONAL GOING
 THROUGH THE STORAGE ROOM AND THIS IS CORRECT SINCE
 SECTION 1016.2 EGRESS THROUGH INTERVENING SPACES DOES
 NOT ALLOW EGRESS THROUGH STORAGE ROOMS. THE EXIT SIGN
 WITHIN THE STORAGE ROOM IS CORRECT SINCE IT IS ONLY FOR
 THIS ROOM.
  
 3) PLEASE PROVIDE AN EXPLANATION OF WHERE THE INTERIOR
 AND EXTERIOR OF THE BUILDING IS IN RELATION TO THE
 NORTH WALL WITH WINDOWS, DOORS AND OVERHEAD EXTERIOR
 DOOR. BOTH THIS AREA AND THE OPPOSITE SIDE OF THE
 TENANT SEPARATION WALL ARE BOTH SHADED WITH THE SAME
 GRAY. 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED.
  
 4) SHEET A405 ADA STANDARDS NEED TO UPDATE THE HEIGHT
 OF GRAB BARS TO THE 2017 FBC-ACCESSIBILITY CODE SECTION
 609.4 POSITION OF GRAB BARS. GRAB BARS SHALL BE
 INSTALLED IN A HORIZONTAL POSITION, 33 INCHES MINIMUM
 AND 36 INCHES MAXIMUM ABOVE THE FINISH FLOOR MEASURED
 TO THE TOP OF THE GRIPPING SURFACE, NOT CENTERLINE.
  
 5) SHEET A410 DETAILS THE INTERIOR ELEVATIONS & DETAIL
 D CABINET BASE @ MICROWAVE SHELF. IN BOTH DETAILS THEY
 SHOW THE BOTTOM OF THE SHELF THAT HOLDS THE MICROWAVE
 ARE LOCATED 4 FEET 10 INCHES ABOVE THE FINISH FLOOR.
 PLEASE CORRECT THE PLANS TO SHOW COMPLIANCE WITH THE
 2017 FBC-ACCESSIBILITY CODE SECTIONS:
  
 5A) 308 REACH RANGES. 308.2 FORWARD REACH. / 308.2.1
 UNOBSTRUCTED/ 308.2.2 OBSTRUCTED HIGH REACH.
 308.3 SIDE REACH. / 308.3.1 UNOBSTRUCTED/ 308.3.2
 OBSTRUCTED HIGH REACH.
  
 5B) 309 OPERABLE PARTS. 309.3 HEIGHT. OPERABLE PARTS
 SHALL BE PLACED WITHIN ONE OR MORE OF THE REACH RANGES
 SPECIFIED IN 308. 309.4 OPERATION. OPERABLE PARTS SHALL
 BE OPERABLE WITH ONE HAND AND SHALL NOT REQUIRE TIGHT
 GRASPING, PINCHING, OR TWISTING OF THE WRIST. THE FORCE
 REQUIRED TO ACTIVATE OPERABLE PARTS SHALL BE 5 POUNDS
 MAXIMUM.
  
 6) THE MECHANICAL PLANS M-2.1 NOTE 14 INDICATE THE
 INSTALLATION OF A A/C STAND ON THE ROOF. PLEASE PROVIDE
 COMPLIANCE WITH:
 2017 FBC-B 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA
 DEPARTMENT OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE
 61G20-3.005, RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY
 OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE
 PRODUCT APPROVALS:
 (31)(G) PRE-ENGINEERED A/C STANDS
  
 6A) W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
  
 6B) THE ROOF TOP A/C STAND PRODUCT APPROVAL A
 MIAMI-DADE NOA # 17-1218.02 WAS INDICATED ON SHEET
 M2.1. THIS NOA NEEDS TO BE REVIEWED BY THE DESIGNER OF
 RECORD. PLEASE IDENTIFY THE FOLLOWING REQUIREMENTS
 CALCULATING THE AREA (SIDE VIEW) OF THE ROOF TOP
 COMPRESSORS, CONFIGURATION ON STAND, THE MEAN ROOF
 HEIGHT OF THE STAND AND COMPRESSORS, WEIGHT, CIRCLED
 THE DESIGN PARAMETERS IN THE TABLES, ANCHORS AND UPLIFT
 VERSES MOMENT FOR THE UNIT TO THE STAND AND THE STAND
 TO THE ROOF. THE PRODUCT APPROVAL IS TO BE REVIEWED BY
 THE DESIGNER OF RECORD, APPROVED BEFORE SUBMISSION TO
 THE BUILDING DEPARTMENT.
  
 7) 2017 FBC-B 1603.1.4 WIND DESIGN DATA. THE FOLLOWING
 INFORMATION RELATED TO WIND LOADS SHALL BE SHOWN,
 REGARDLESS OF WHETHER WIND LOADS GOVERN THE DESIGN OF
 THE LATERAL FORCE-RESISTING SYSTEM OF THE STRUCTURE:
  
 7.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED,
 VASD, AS DETERMINED IN ACCORDANCE WITH SECTION
 1609.3.1.
  
 7.2. RISK CATEGORY.
  
 7.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2.
 HEIGHT AND EXPOSURE.
  
 7.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
  
 7.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENTS AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF.
 TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING. 1609.3.1 WIND SPEED CONVERSION VULT TO VASD.
  
 8) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-08-11 Cont ID  
Sent By jpearson Date 2019-08-11 Time 11:20 Rev Time 0.00
Received By jpearson Date 2019-08-11 Time 11:20 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-06-17 Cont ID  
Sent By jpearson Date 2019-06-17 Time 15:44 Rev Time 0.00
Received By jpearson Date 2019-06-17 Time 15:44 Sent To  
Notes
2019-06-17 15:44:10CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. RECEPTACLE OUTLETS WITHIN 6 FEET OF A SINK REQUIRE
 GFCI PROTECTION. PROVIDE CORRECTION. NEC 210.8
 2. PROVIDE DEMAND LOAD FOR EACH PHASE OF PANEL C1. THE
 CURRENT LOAD STATED FOR A PHASE SHOWS A LOAD OF 214
 AMPS ON A 200 AMP PANEL. PROVIDE CORRECTION. NEC
 408.30, 408.36, 215.2, 310.15
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E-LOWVOLT ELECTRICAL LOW VOLTAGE
Rev No 1 Status P Date 2019-08-11 Cont ID  
Sent By jpearson Date 2019-08-11 Time 11:17 Rev Time 0.00
Received By jpearson Date 2019-08-11 Time 11:17 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2019-08-07 Cont ID  
Sent By pleduc Date 2019-08-07 Time   Rev Time 0.00
Received By pleduc Date 2019-08-07 Time 11:29 Sent To  
Notes
2019-08-07 11:31:28THE FOLLOWING COMMENTS ARE SUBMITTED AS PROVISO.
  
 FAILURE TO PROPERLY ADDRESS THEM MAY RESULT IN FAILED
 INSPECTIONS.
  
  
  
 1) ANY FIRE ALARM WORK SHALL BE DONE UNDER SEPARATE
 PERMIT AND SHOP DRAWINGS.
  
  
  
 2) ANY FIRE SPRINKLER WORK SHALL BE DONE UNDER SEPARATE
 PERMIT AND SHOP DRAWINGS.
  
  
  
 3) ANY CARD READER AND/OR ACCESS CONTROL WORK SHALL BE
 DONE UNDER SEPARATE PERMIT AND SHOP DRAWINGS.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-06-17 Cont ID  
Sent By pleduc Date 2019-06-17 Time   Rev Time 0.00
Received By pleduc Date 2019-06-17 Time 10:57 Sent To  
Notes
2019-06-17 11:07:45PREVIOUS FIRE COMMENTS DO NOT APPEAR TO BE SPECIFICALY
 ADDRESSED.
  
 THE FOLLOWING COMMENTS ARE SUBMITTED AS PROVISO.
  
 FAILURE TO PROPERLY ADDRESS THEM MAY RESULT IN FAILED
 INSPECTIONS.
  
  
  
 1) SHEET G001 - THERE ARE INCORRECT EDITIONS INDICATION
 UNDER THE FLORIDA FIRE PREVENTION CODE.
  
 PROPOSED PROJECTS SHALL MEET THE REQUIREMENTS OF THE
 6TH EDITION OF FLORIDA FIRE PREVENTION CODE WHICH
 INCLUDES THE 2015 EDITION OF NFPA 1 AND NFPA 101.
  
 PLEASE REVIEW, CORRECT AND ENSURE COMPLIANCE.
  
 NEW COMMENT: UPDATE YOUR RECORDS.
  
  
  
 2) ADDRESSED AND CORRECTED
  
  
  
 3) SHEET G 001 & A 101 - THERE ARE INDICATIONS OF FIRE
 ALARM CONSULTANTS AND FIRE ALARM EQUIPMENT (WITHIN THE
 SYMBOL LEGEND).
  
 PLEASE CLARIFY IF A FIRE ALARM IS EXISTING, PROPOSED OR
 NONAPPLICABLE.
  
 NEW COMMENT: ANY FIRE ALARM WORK SHALL BE DONE UNDER
 SEPARATE PERMIT AND SHOP DRAWINGS.
  
  
  
 4) SHEET G 001 - THERE IS AN INDICATION OF A FIRE
 PROTECTION CONSULTANT, BUT NO INDICATION OF FIRE
 PROTECTION EQUIPMENT.
  
 PLEASE CLARIFY IF A FIRE SPRINKLER PROTECTION IS
 EXISTING, PROPOSED OR NONAPPLICABLE.
  
 NEW COMMENT: ANY FIRE SPRINKLER WORK SHALL BE DONE
 UNDER SEPARATE PERMIT AND SHOP DRAWINGS.
  
  
  
  
 5) SHEET A 101 - THERE ARE INDICATIONS OF CARD READER
 AT SOME LOCATIONS.
  
 CARD READER SHALL BE SUBMITTED UNDER SEPRATE PERMIT AND
 SHOP DRAWINGS.
  
 CARD READER WITHIN A MEANS OF EGRESS SHALL COMPLY WITH
 NFPA 101, CH 7.
  
 7.2.1.5.6 ELECTRICALLY CONTROLLED EGRESS DOOR
 ASSEMBLIES. DOOR ASSEMBLIES IN THE MEANS OF EGRESS
 SHALL BE PERMITTED TO BE ELECTRICALLY LOCKED IF
 EQUIPPED WITH APPROVED, LISTED HARDWARE, PROVIDED THAT
 ALL OF THE FOLLOWING CONDITIONS ARE MET:
 (1) THE HARDWARE FOR OCCUPANT RELEASE OF THE LOCK IS
 AFFIXED TO THE DOOR LEAF.
 (2) THE HARDWARE HAS AN OBVIOUS METHOD OF OPERATION
 THAT IS READILY OPERATED IN THE DIRECTION OF EGRESS.
 (3) THE HARDWARE IS CAPABLE OF BEING OPERATED WITH ONE
 HAND IN THE DIRECTION OF EGRESS.
 (4) OPERATION OF THE HARDWARE INTERRUPTS THE POWER
 SUPPLY DIRECTLY TO THE ELECTRIC LOCK AND UNLOCKS THE
 DOOR ASSEMBLY IN THE DIRECTION OF EGRESS.
 (5)* LOSS OF POWER TO THE LISTED RELEASING HARDWARE
 AUTOMATICALLY UNLOCKS THE DOOR ASSEMBLY IN THE
 DIRECTION OF EGRESS.
 (6) HARDWARE FOR NEW INSTALLATIONS IS LISTED IN
 ACCORDANCE WITH ANSI/UL 294, STANDARD FOR ACCESS
 CONTROL SYSTEM UNITS.
  
 PLEASE REVIEW, ENSURE COMPLIANCE AND PROVIDE AN AN
 APPLICABLE NOTE
  
 NEW COMMENT: ANY CARD READER WORK SHALL BE DONE UNDER
 SEPARATE PERMIT AND SHOP DRAWINGS.
  
  
  
 6) N/A
  
  
 7) N/A
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2019-06-04 Cont ID  
Sent By pleduc Date 2019-06-04 Time   Rev Time 0.00
Received By pleduc Date 2019-06-04 Time 10:31 Sent To  
Notes
2019-06-04 11:19:11THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET G001 - THERE ARE INCORRECT EDITIONS INDICATION
 UNDER THE FLORIDA FIRE PREVENTION CODE.
  
 PROPOSED PROJECTS SHALL MEET THE REQUIREMENTS OF THE
 6TH EDITION OF FLORIDA FIRE PREVENTION CODE WHICH
 INCLUDES THE 2015 EDITION OF NFPA 1 AND NFPA 101.
  
 PLEASE REVIEW, CORRECT AND ENSURE COMPLIANCE.
  
  
  
 2) SHEET G 001 - THE ADDRESS INDICATED ON THE
 APPLICATION IS 2442 METROCENTRE BLVD E; HOWEVER, THE
 TITLE BLOCK INDICATION 2474.
  
 PLEASE REVIEW, CORRECT TO THE PROPER ADDRESS OR JUSTIFY
 WITH DETAILS.
  
  
  
 3) SHEET G 001 & A 101 - THERE ARE INDICATIONS OF FIRE
 ALARM CONSULTANTS AND FIRE ALARM EQUIPMENT (WITHIN THE
 SYMBOL LEGEND).
  
 PLEASE CLARIFY IF A FIRE ALARM IS EXISTING, PROPOSED OR
 NONAPPLICABLE.
  
  
  
 4) SHEET G 001 - THERE IS AN INDICATION OF A FIRE
 PROTECTION CONSULTANT, BUT NO INDICATION OF FIRE
 PROTECTION EQUIPMENT.
  
 PLEASE CLARIFY IF A FIRE SPRINKLER PROTECTION IS
 EXISTING, PROPOSED OR NONAPPLICABLE.
  
  
  
 5) SHEET A 101 - THERE ARE INDICATIONS OF CARD READER
 AT SOME LOCATIONS.
  
 CARD READER SHALL BE SUBMITTED UNDER SEPRATE PERMIT AND
 SHOP DRAWINGS.
  
 CARD READER WITHIN A MEANS OF EGRESS SHALL COMPLY WITH
 NFPA 101, CH 7.
  
 7.2.1.5.6 ELECTRICALLY CONTROLLED EGRESS DOOR
 ASSEMBLIES. DOOR ASSEMBLIES IN THE MEANS OF EGRESS
 SHALL BE PERMITTED TO BE ELECTRICALLY LOCKED IF
 EQUIPPED WITH APPROVED, LISTED HARDWARE, PROVIDED THAT
 ALL OF THE FOLLOWING CONDITIONS ARE MET:
 (1) THE HARDWARE FOR OCCUPANT RELEASE OF THE LOCK IS
 AFFIXED TO THE DOOR LEAF.
 (2) THE HARDWARE HAS AN OBVIOUS METHOD OF OPERATION
 THAT IS READILY OPERATED IN THE DIRECTION OF EGRESS.
 (3) THE HARDWARE IS CAPABLE OF BEING OPERATED WITH ONE
 HAND IN THE DIRECTION OF EGRESS.
 (4) OPERATION OF THE HARDWARE INTERRUPTS THE POWER
 SUPPLY DIRECTLY TO THE ELECTRIC LOCK AND UNLOCKS THE
 DOOR ASSEMBLY IN THE DIRECTION OF EGRESS.
 (5)* LOSS OF POWER TO THE LISTED RELEASING HARDWARE
 AUTOMATICALLY UNLOCKS THE DOOR ASSEMBLY IN THE
 DIRECTION OF EGRESS.
 (6) HARDWARE FOR NEW INSTALLATIONS IS LISTED IN
 ACCORDANCE WITH ANSI/UL 294, STANDARD FOR ACCESS
 CONTROL SYSTEM UNITS.
  
 PLEASE REVIEW, ENSURE COMPLIANCE AND PROVIDE AN AN
 APPLICABLE NOTE
  
  
 6) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 7) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-08-26 Cont ID  
Sent By gjohnson Date 2019-08-26 Time 18:20 Rev Time 0.00
Received By gjohnson Date 2019-08-06 Time 10:25 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-07-15 Cont ID  
Sent By lmarchan Date 2019-07-15 Time 09:43 Rev Time 0.00
Received By lmarchan Date 2019-06-14 Time 10:27 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-06-11 Cont ID  
Sent By lmarchan Date 2019-06-11 Time 14:24 Rev Time 0.00
Received By lmarchan Date 2019-05-30 Time 12:47 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2019-07-15 Cont ID  
Sent By jwitmer Date 2019-07-15 Time 08:50 Rev Time 0.00
Received By jwitmer Date 2019-07-15 Time 06:47 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2019-08-14 Cont ID  
Sent By pvalenti Date 2019-08-14 Time 16:58 Rev Time 0.00
Received By ccole Date 2019-08-14 Time 16:58 Sent To  
Notes
2019-08-14 17:00:182ND MECHANICAL REVIEW
  
 APPROVED PER CHRIS COLE (REMOTELY)

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-07-01 Cont ID  
Sent By ccole Date 2019-07-01 Time 10:05 Rev Time 0.00
Received By ccole Date 2019-07-01 Time 10:05 Sent To  
Notes
2019-07-01 10:32:141ST REVIEW FBC-2017 MECHANICAL
 PERMIT
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M-2.1: PLEASE CLARIFY NOTE #7 AND SHOW THE
 ROOF TOP LOCATIONS OF THE O/A INLETS FOR AHU'S 1, 2, &
 3- SECTION 107.2.1 WPB. PLEASE INLCUDE CLEARANCE
 DISTANCE MEASUREMENTS PER SECTUION 401.4 FBC M.
  
 2) SUBMIT NOA #17-1218.02.
  
 3) ELECTRONIC PLANS: THE DIGITALLY SIGNED PLANS SHALL
 ALSO BEAR THIS STATEMENT IN ACCORDANCE WITH SECTION
 61G15-23.005- "THIS ITEM HAS BEEN ELECTRONICALLY SIGNED
 AND SEALED BY _________ON DATE________USING A SHA-1
 AUTHENTICATION CODE." THE CURRENT MECHANICAL PLANS
 INDICATE THEY ARE SIGNED ONLY. IN ADDITION ENGINEERS
 MAY NOT SELF-CERTIFY ELECTRONIC SIGNATURES AND SEALS.
 CERTIFICATION SHALL BE BY A THIRD-PARTY AGENCY.
  
 4) PROVIDE CONDENSATE DISPOSAL PLANS FOR THE NEW AND
 RELOCATED AIR HANDLERS- SECTION 307.2.1 GFBC M.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 BUILDING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-08-26 Cont ID  
Sent By gjohnson Date 2019-08-26 Time 18:20 Rev Time 0.00
Received By gjohnson Date 2019-08-26 Time 17:33 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-06-21 Cont ID  
Sent By gjohnson Date 2019-06-21 Time 16:52 Rev Time 0.00
Received By gjohnson Date 2019-06-21 Time 15:38 Sent To  
Notes
2019-06-21 17:07:221ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. SHOW COMPLIANCE WITH FBC ACC 604.7 DISPENSERS.TOILET
 PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND SHALL BE 7
 INCHES MINIMUM AND 9 INCHES MAXIMUM IN FRONT OF THE
 WATER CLOSET MEASURED TO THE CENTERLINE OF THE
 DISPENSER. THE OUTLET OF THE DISPENSER SHALL BE 15
 INCHES MINIMUM AND 48 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR.
  
 2. SHOW COMPLIANCE WITH FBC ACC 604.5.2 REAR WALL. THE
 REAR WALL GRAB BAR SHALL BE 36 INCHES LONG MINIMUM AND
 EXTEND FROM THE CENTERLINE OF THE WATER CLOSET 12
 INCHES MINIMUM ON ONE SIDE AND 24 INCHES MINIMUM ON THE
 OTHER SIDE.
  
 3. THE GRAB BARS SHALL BE MEASURED TO THE TOP OF THE
 GRIPPING SURFACE PLACE NOTE ON PLAN. PER FBC ACC 609.4
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2019-08-14 Cont ID  
Sent By shill Date 2019-08-14 Time 17:35 Rev Time 0.00
Received By shill Date 2019-08-14 Time 17:35 Sent To  
Notes
2019-08-11 11:16:39REPEAT COMMENT: PER THE WPB AMENDMENTS TO THE FBC, EACH
 SHEET OF PLAN IS REQUIRED TO BE SIGNED AND SEALED BY
 THE PERSON RESPONSIBLE FOR THE DESIGN. A DIGITAL PLAN
 REQUIRES A DIGITAL SIGNATURE WITH THE PROPER THIRD
 PARTY VERIFICATION. SELF-CERTIFICATION IS NOT
 ACCEPTABLE. ADDITIONALLY, THE DIGITAL SIGNATURE MUST
 INCLUDE THE STATEMENT "SIGNED AND SEALED" AS PER FAC
 61G15-23.004. PROVIDE CORRECTION. WPB FBC 107.1; FS
 471/481

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2019-06-17 Cont ID  
Sent By jpearson Date 2019-06-17 Time 15:05 Rev Time 0.00
Received By jpearson Date 2019-06-17 Time 15:05 Sent To  
Notes
2019-06-17 15:05:46PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN
 IS REQUIRED TO BE SIGNED AND SEALED BY THE PERSON
 RESPONSIBLE FOR THE DESIGN. A DIGITAL PLAN REQUIRES A
 DIGITAL SIGNATURE WITH THE PROPER THIRD PARTY
 VERIFICATION. SELF-CERTIFICATION IS NOT ACCEPTABLE.
 ADDITIONALLY, THE DIGITAL SIGNATURE MUST INCLUDE THE
 STATEMENT "SIGNED AND SEALED" AS PER FAC 61G15-23.004.
 PROVIDE CORRECTION. WPB FBC 107.1; FS 471/481

Review Stop Z ZONING
Rev No 3 Status P Date   Cont ID  
Sent By   Date 2019-08-12 Time   Rev Time 0.00
Received By pgreilic Date 2019-08-12 Time 10:44 Sent To  
Notes
2019-08-12 10:44:58PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]
  
  

Review Stop Z ZONING
Rev No 2 Status P Date   Cont ID  
Sent By   Date 2019-06-21 Time   Rev Time 0.00
Received By pgreilic Date 2019-06-21 Time 11:09 Sent To  
Notes
2019-06-21 11:10:02PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]
  
  

Review Stop Z ZONING
Rev No 1 Status P Date   Cont ID  
Sent By pgrehili Date 2019-06-13 Time   Rev Time 0.00
Received By pgreilic Date 2019-06-13 Time 16:16 Sent To  
Notes
2019-06-13 16:17:08PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]
  