| 2019-06-14 19:04:26 | RESIDENTIAL (R3) BUILDING REVIEW COMMENTS |
| | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| | |
| | NOTE: SEC. 801.3 FBC-EXISTING BUILDING. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | |
| | 1-PLANS SUBMITTED HAVE A COPY OF A DIGITAL SIGNATURE. |
| | THIS IS NOT A DIGITAL SUBMITTAL. ALL PLANS NEED TO HAVE |
| | THE ORIGINAL SEAL AND SIGNATURE OF THE ENGINEER OF |
| | RECORD AS REQUIRED BY SEC. 61G15-23.003 FAC AND CHAPTER |
| | 471 F.S. WHEN SUBMITTING PLANS/DOCUMENTS FOR PUBLIC |
| | RECORDS |
| | |
| | 2- REVISE INFORMATION ON SHEET A-1: |
| | A)ACCORDING TO CITY RECORDS AND PALM BEACH COUNTY |
| | PROPERTY APPRAISER THESE BUILDINGS WERE BUILT IN 1925 |
| | AND THEIR CONSTRUCTION WAS WOOD FRAME. DESIGN CRITERIA |
| | STATES CONSTRUCTION TYPE IIIB. THIS IS INCORRECT. |
| | REVISE AS REQUIRED. SEC. 602.1 FBC-BUILDING. |
| | |
| | B) THIS IS NOT AN ALTERATION LEVEL 2. THE CONVERSION OF |
| | THE EXISTING GARAGE TO LIVABLE SPACE IS A CHANGE OF USE |
| | AND ALTERATION LEVEL 3. REVISE AS REQUIRED. SEC. 505 |
| | AND SEC. 506 FBC-EXISTING BUILDING. REVISE AS REQUIRED. |
| | |
| | C) SITE PLAN STATES THAT THE REAR STRUCTURE IS |
| | "EXISTING GUEST HOUSE". THIS IS INCORRECT. THIS AN |
| | EXISTING GARAGE NOT EXISTING GUEST HOUSE. REVISE AS |
| | REQUIRED. SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | 3- GUEST HOUSE PROPOSED FLOOR PLAN ON SHEET A-2: |
| | A)TYPICALLY ZONING DOESN'T ALLOW SEPARATE COOKING |
| | FACILITIES ON SINGLE FAMILY RESIDENCES. COORDINATE WITH |
| | ZONING REVIEW COMMENTS. IF ZONING DOESN'T ALLOW THE |
| | KITCHENETTE, THEN NEED TO REVISE PLANS ACCORDINGLY, |
| | INCLUDING CHANGING THE NAME OF THE AREA SO IT DOESN'T |
| | IMPLY THAT ANY KIND OF COOKING IS APPROVED. |
| | SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | B) THIS IS A WOOD FRAMED BUILDING NOT CONCRETE BLOCK. |
| | SEE ITEM #2(A) ABOVE. REVISE DETAILS AND SPECIFICATIONS |
| | SHOWN ON THE FLOOR PLAN, PARTITION ASSEMBLY LEGEND AND |
| | RESPECTIVE LEGEND AND KEY NOTES ON SHEET A-2. AND, |
| | PROVIDE WOOD FRAMING REINFORCEMENT |
| | DETAILS/SPECIFICATIONS AT EXTERIOR DOORS OPENINGS. SEC. |
| | R301.2.1 FBC-RESIDENTIAL. |
| | |
| | C) THIS IS A CHANGE OF USE FROM GARAGE TO LIVABLE |
| | SPACE. THEREFORE, THE RISK CATEGORY IS HIGHER. ENGINEER |
| | OF RECORD TO PROVIDE ANALYSIS THAT THE EXISTING |
| | STRUCTURE COMPLIES WITH THE APPLICABLE WIND LOADS AS |
| | REQUIRED BY SEC. 1007.2 FBC-EXISTING BUILDING. |
| | |
| | D)BASED ON THE LOCATION OF THE EXISTING STRUCTURE |
| | OPENINGS IN THE REAR WALL (SOUTH WALL) ARE NOT ALLOWED. |
| | REVISE AS REQUIRED . SEC. R302.1 AND TABLE R302.1 |
| | FBC-RESIDENTIAL. PROVIDE DETAILS AND SPECIFICATIONS FOR |
| | INFILL OF EXISTING OPENINGS. SEC. R301.2.1 |
| | FBC-RESIDENTIAL. |
| | |
| | E) BASED ON THE LOCATION OF THE EXISTING STRUCTURE THE |
| | SOUTH WALL NEEDS TO BE ONE HOUR FIRE RATED WALL AS |
| | REQUIRED BY TABLE R302.1 FBC-RESIDENTIAL. PROVIDE |
| | COMPLETE DETAILS AND SPECIFICATIONS FOR ONE HOUR FIRE |
| | RATED WALL. |
| | |
| | F) THIS IS A CHANGE OF USE FROM GARAGE TO LIVABLE |
| | SPACE. TYPICALLY, GARAGES ARE BUILT WITHOUT A FLOOR |
| | VAPOR BARRIER. ENGINEER OF RECORD TO PROVIDE |
| | SPECIFICATIONS FOR THE CONCRETE SLAB VAPOR BARRIER AS |
| | REQUIRED BY SEC. R506.2.3 FBC-RESIDENTIAL. |
| | |
| | G)PROVIDE DETAILS AND SPECIFICATIONS FOR THE INSULATION |
| | ON WALLS AND CEILINGS AS REQUIRED BY SEC. R103.2 |
| | FBC-ENERGY CONSERVATION. NOTE: COORDINATE WITH THE |
| | ENERGY CALCULATIONS TO AVOID CONFLICTS/DELAYS. |
| | |
| | 4- SHEET S-1: |
| | A) EXISTING BUILDINGS ARE WOOD FRAMED BUILDINGS NOT |
| | CONCRETE BLOCK. REVISE ALL PLANS AND DETAILS THAT ARE |
| | REFERENCING CONCRETE BLOCK CONSTRUCTION. SEC. 107.2.1 |
| | CITY AMENDMENTS. COORDINATE WITH ITEM #3(B) ABOVE. |
| | |
| | B)NEW COVERED TERRACE ROOFING MATERIAL IS NOT CLEAR. |
| | SECTION A ON SHEET S-1 SPECIFIES MODIFIED BITUMEN, |
| | WHILE EXTERIOR ELEVATIONS ON SHEET A-3 SHOW SOME KIND |
| | OF ROOF TILE. REVISE AS REQUIRED TO MATCH. SEC. 107.2.1 |
| | CITY AMENDMENTS. |
| | NOTE: TO AVOID CONFLICTS/DELAYS KEEP IN MIND THAT THERE |
| | ARE LIMITATIONS ON THE MINIMUM ROOF SLOPE AS REQUIRED |
| | BY SEC. R905.3.2 FBC-RESIDENTIAL AND PRODUCT APPROVALS. |
| | |
| | 5- ENERGY CALCULATIONS SUBMITTED: |
| | A)THE ENERGY FORM R405-2017 IS REQUIRED TO BE CERTIFIED |
| | AT THE BOTTOM BY THE OWNER OR THE OWNER LEGALLY |
| | DESIGNATED AGENT AS REQUIRED BY SEC. R103.1.1.2 |
| | FBC-ENERGY CONSERVATION, 6TH EDITION (2017). |
| | |
| | B) CALCULATIONS HAVE A COPY OF A DIGITAL SIGNATURE. |
| | THIS IS NOT A DIGITAL SUBMITTAL. CALCULATIONS NEED TO |
| | HAVE THE ORIGINAL SEAL AND SIGNATURE OF THE ENGINEER OF |
| | RECORD AS REQUIRED BY SEC. 61G15-23.003 FAC AND CHAPTER |
| | 471 F.S. WHEN SUBMITTING PLANS/DOCUMENTS FOR PUBLIC |
| | RECORDS. |
| | |
| | C)PROVIDE COMPLETE AND CORRECT INFORMATION ON TOP OF |
| | FORM, INCLUDING THE OWNER'S NAME, BUILDER'S NAME, |
| | PERMIT OFFICE AND JURISDICTION SEC. R101.5.1.1.2 FBC- |
| | ENERGY CONSERVATION. |
| | NOTE: DESIGN LOCATION AND JURISDICTION NUMBER ARE |
| | INCORRECT. PROVIDE CORRECT INFORMATION. |
| | |
| | D) MISSING ALL THE WINDOWS INFORMATION ON ITEM #7 OF |
| | PAGE 1 OF 4. NEED TO SPECIFY ALL GLASS AREA OF ENTRY |
| | DOOR AND AND SLIDING GLASS DOORS AS REQUIRED BY SEC. |
| | R405.5.3.1 AND SEC. R405.5.33 FBC-ENERGY CONSERVATION. |
| | |
| | E) REVISE ITEM #10 ON PAGE 1 OF 4. PLANS DON'T SPECIFY |
| | ANY UNDER ATTIC VENTING. REVISE AS REQUIRED TO MATCH |
| | PLANS OR PROVIDE DETAILS AND SPECIFICATIONS SHOWING |
| | COMPLIANCE WITH THE VENTING REQUIREMENTS. SEC. |
| | R101.5.1.1.2 FBC- ENERGY CONSERVATION. |
| | |
| | F)DESIGN LOCATION SHOWN ON PAGE 2 OF 4 IS INCORRECT. |
| | REVISE AS REQUIRED. |
| | SEC. R101.5.1.1.2 FBC- ENERGY |
| | |
| | G)PAGE 2 OF 4 INDICATES THAT THERE IS A KITCHEN IN THE |
| | GUEST HOUSE. THIS NEEDS TO BE COORDINATED WITH ITEM |
| | #3(A) ABOVE. IF ZONING DOESN'T ALLOW THE KITCHENETTE, |
| | THEN ENERGY CALCULATIONS WOULD NEED TO BE REVISED. SEC. |
| | R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| | |
| | H)REVISE TYPE OF ROOF AND ROOF MATERIAL SPECIFIED ON |
| | PAGE 2 OF 4 TO MATCH PLANS. SEE PLANS AND REVISE AS |
| | REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| | |
| | I)REVISE THE ATTIC VENT RATIO ON PAGE 2 OF 5. |
| | TYPICALLY, THE RATIO IS 1/150 NOT 1/300. SEC. R806.2 |
| | FBC-RESIDENTIAL. OR, PERSON PREPARING THE ENERGY |
| | CALCULATIONS TO PROVIDE COMPLETE DOCUMENTATION SHOWING |
| | COMPLIANCE WITH THE 1/300 RATIO AS REQUIRED BY THE |
| | EXCEPTION ON SEC. R806.2. |
| | NOTE: COORDINATE WITH ITEM #5(E) ABOVE. |
| | |
| | J)REVISE DOOR INFORMATION PAGE 3 OF 4. THERE ARE NOT |
| | DOORS ON THE EAST SIDE. AND, THERE ARE NO WOOD DOORS |
| | EITHER. SEE PLANS AND PRODUCT APPROVALS AND REVISE AS |
| | REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| | NOTE: GLAZING IN DOORS NEEDS TO BE INCLUDED IN THE |
| | WINDOW GLAZING AREA. SEE SEC. R405.5.3 FBC-ENERGY |
| | CONSERVATION. |
| | |
| | K)REVISE WINDOWS ORIENTATION SHOWN ON PAGE 3 OF 4. THE |
| | ORIENTATION OF THE WINDOWS DON'T MATCH PLANS (NOTE: |
| | PLANS ARE DRAWN WITH THE NORTH ARROW FACING DOWN. KEEP |
| | THIS IN MIND WHEN REVISING THE CALCULATIONS). SEC. |
| | R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| | |
| | L) REVISE WINDOWS OVERHANG DEPTH AND SEPARATION ON PAGE |
| | 3 OF 4 TO MATCH PLANS. SEE PLANS AND REVISE AS |
| | REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| | |
| | M)REVISE WINDOWS INFORMATION ON PAGE 3 OF 4 TO MATCH |
| | PLANS. COORDINATE WITH ITEM #3(D) ABOVE AND WITH |
| | GLAZING IN DOORS. SEC. R101.5.1.1.2 FBC-ENERGY |
| | CONSERVATION. |
| | |
| | N)BUILDER TO COMPLETE THE ENERGY PERFORMANCE LEVEL |
| | (EPL) DISPLAY CARD. SEC. R405.4.3 FBC- ENERGY |
| | CONSERVATION. |
| | |
| | NOTE: |
| | LABEL FOR WINDOWS AND DOORS SHOWING THE U-FACTOR AND |
| | SHGC FACTOR IS REQUIRED WHEN THE ENERGY CALCULATIONS |
| | ARE NOT USING THE DEFAULT FACTOR. |
| | |
| | 6- WIND LOAD CALCULATIONS SUBMITTED HAVE A COPY OF A |
| | DIGITAL SIGNATURE. THIS IS NOT A DIGITAL SUBMITTAL. |
| | CALCULATIONS NEED TO HAVE THE ORIGINAL SEAL AND |
| | SIGNATURE OF THE ENGINEER OF RECORD AS REQUIRED BY SEC. |
| | 61G15-23.003 FAC AND CHAPTER 471 F.S. WHEN SUBMITTING |
| | PLANS/DOCUMENTS FOR PUBLIC RECORDS. |
| | |
| | 7- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | FAC 61G20-3.001 FOR ROOFING AT NEW COVERED TERRACE. |
| | NOTE: COORDINATE WITH ITEM #4(B) ABOVE. |
| | |
| | A)IF FLAT ROOF, THEN PROVIDE THE FOLLOWING: |
| | PROVIDE PRODUCT APPROVAL (2 COPIES) FOR FLAT ROOF AS |
| | REQUIRED BY FAC 61G20-3.001 AND CLEARLY MARK WHICH |
| | APPROVED ASSEMBLY IS GOING TO BE INSTALLED TO VERIFY |
| | COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. R301.2.1 |
| | FBC-RESIDENTIAL. NOTE: IF THE SELECTED ASSEMBLY DOESN'T |
| | MEET THE DESIGN PRESSURES FOR ALL ROOF ZONES, THEN |
| | SIGNED AND SEALED RAS 117 CALCULATIONS ARE REQUIRED. |
| | |
| | B)IF TILE ROOF, THEN PROVIDE THE FOLLOWING: |
| | - ENGINEER OF RECORD TO SPECIFY ROOF TILE FASTENING IN |
| | THE CONSTRUCTION DOCUMENTS. SEC. 107.2.1.1 CITY |
| | AMENDMENTS. IF SPECIFYING ROOF TILE ADHESIVE, THEN |
| | PROVIDE PRODUCT APPROVAL. IF SPECIFYING SCREWS, THEN |
| | SPECIFY SCREW SIZE AND NUMBER OF SCREWS. |
| | -ROOF TILE PRODUCT APPROVAL AND CLEARLY MARK ROOF TILE |
| | FASTENING METHOD AS REQUIRED BY CITY POLICY FOR ALL |
| | ROOFING PERMITS. |
| | |
| | 8- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO |
| | LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS, |
| | CONTRACTOR'S OVERHEAD AND PROFIT AND DESIGN |
| | PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY |
| | AMENDMENTS. UPDATE VALUATION AND INCLUDE THE DESIGN |
| | PROFESSIONAL FEES. |
| | |
| | |
| | 9- OWNER/BUILDER NEEDS TO COMPLETE ROOFING PERMIT |
| | APPLICATION ALSO. SEC/ 105.1 CITY AMENDMENTS. |
| | |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | PLEASE, INSERT CORRECTED PAGES INTO THE SUBMITTAL AND |
| | REMOVE/VOID THE PREVIOUSLY REVIEWED SHEETS. PLEASE |
| | DON'T STAPLE OLD DRAWINGS/DOCUMENTS . SUBMIT OLD |
| | DRAWINGS/DOCUMENTS FOR REFERENCE. |
| | |