Plan Review Details - Permit 19050860
Plan Review Stops For Permit 19050860
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-07-01 Cont ID  
Sent By jwitmer Date 2019-07-01 Time 10:30 Rev Time 0.00
Received By jwitmer Date 2019-07-01 Time 09:45 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-06-05 Cont ID  
Sent By jwitmer Date 2019-06-05 Time 10:14 Rev Time 0.00
Received By jwitmer Date 2019-06-05 Time 07:39 Sent To  
Notes
2019-06-05 10:14:01 
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19050860
 ADD: 901 45TH ST. ST. MARY?S MEDICAL CENTER
 CONT: WESTBROOKE CORPORATION
 TEL: 561-395-4126
 E-MAIL:
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. JUNE 06/ 2019
 ACTION: DENIED
  
 1) SHEET AD3.2 INDICATES WITH NOTES 1 & 2 DEMOLITION
 WORK OF AN EXTERIOR WALL (NOTE # 1 REMOVE AN EXISTING
 PORTION OF WALL, PREPARE FOR LOUVER INSTALLATION. NOTE
 # 2 INDICATES THE REMOVAL OF FLOORING.
 SHEET A3.2 NOTE # 3 INDICATES A NEW HVAC PENETRATION
 THROUGH THE FLOOR SYSTEM. THE ARCHITECTURAL SHEETS GIVE
 NO FURTHER INFORMATION ON THE NEW OPENING IN THE WALL
 SYSTEM HOW TO PREPARE THE WALL OPENING FOR THE NEW
 LOUVER. NOR DOES THE ARCHITECTURAL SHEETS PROVIDE
 INFORMATION AS TO THE STEPS INVOLVED FOR THE NEW FLOOR
 PENETRATION, TYPE OF FLOOR SYSTEM, NOR IF ANY
 ADDITIONAL BRACING WILL BE REQUIRED THE NEW OPENING.
  
 THE COVERSHEET A0.0 DOES HAVE A INDEX OF DRAWINGS AN IT
 APPEARS THAT THE S-100 STRUCTURAL SHEET WAS LEFT OUT OF
 BOTH SETS OF PLANS. THE UNKNOWN SHEET WOULD HAVE TO
 ANSWER BOTH THE QUESTIONS STATED ABOVE PLUS PROVIDE THE
 WIND DESIGN CRITERIA FOR 180 VULT, MEAN ROOF HEIGHT AND
 THE ASSOCIATED PRESSURES FOR THE NEW WALL LOUVER.
 ADDITIONAL INFORMATION IS REQUIRED. 107.2.1.2.
  
 2017 FBC-B 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
 1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR AND NOMINAL DESIGN WIND SPEED, VASD, AS
 DETERMINED IN ACCORDANCE WITH SECTION 1609.3.1.
 2. RISK CATEGORY.
 3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2.
 HEIGHT AND EXPOSURE.
 4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
 5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENTS AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF.
 TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING. 1609.3.1 WIND SPEED CONVERSION VULT TO VASD.
  
 2) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2019-06-17 Cont ID  
Sent By jleahy Date 2019-06-17 Time 12:53 Rev Time 0.00
Received By jleahy Date 2019-06-17 Time 12:53 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2019-05-22 Cont ID  
Sent By pleduc Date 2019-05-22 Time   Rev Time 0.00
Received By pleduc Date 2019-05-22 Time 14:59 Sent To  
Notes
2019-05-22 15:00:58THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 1) ANY REMOVAL AND/OR CONSTRUCTION OF WALLS AND /OR
 CEILINGS REQUIRE AN EVALUATION OF THE FIRE ALARM AND/OR
 SPRINKLER SYSTEM FOR CODE COVERAGE AND COMPLIANCE BY
 CERTIFIED CONTRACTORS.
  
 2) ANY AND ALL WORK ON THE FIRE ALARM AND/OR FIRE
 SPRINKLER SYSTEMS SHALL BE DONE UNDER SEPARATE PERMIT
 AND SHOP DRAWINGS AND BY CERTIFIED CONTRACTORS.
  
 3) THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE
 SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE DEMO AND
 CONSTRUCTION PERIOD.
  
  
 PETER LEDUC
 FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-07-01 Cont ID  
Sent By jwitmer Date 2019-07-01 Time 10:30 Rev Time 0.00
Received By jwitmer Date 2019-06-25 Time 13:46 Sent To  
Notes
2019-06-27 13:46:50RESUB ROUTED TO JWITMER

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-06-17 Cont ID  
Sent By jleahy Date 2019-06-17 Time 12:53 Rev Time 0.00
Received By jleahy Date 2019-05-17 Time 15:14 Sent To  
Notes
2019-05-20 15:14:38B34

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2019-06-05 Cont ID  
Sent By ccole Date 2019-06-05 Time 17:32 Rev Time 0.00
Received By ccole Date 2019-06-05 Time 17:31 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date   Cont ID  
Sent By pgrehili Date 2019-06-13 Time   Rev Time 0.00
Received By pgreilic Date 2019-06-13 Time 15:43 Sent To  
Notes
2019-06-13 15:43:22PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]