Plan Review Details - Permit 19050849
Plan Review Stops For Permit 19050849
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2019-10-10 Cont ID  
Sent By cthroop Date 2019-10-10 Time 09:04 Rev Time 0.00
Received By cthroop Date 2019-10-10 Time 08:51 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-09-19 Cont ID  
Sent By cthroop Date 2019-09-19 Time 11:32 Rev Time 0.00
Received By cthroop Date 2019-09-19 Time 10:54 Sent To  
Notes
2019-09-19 11:36:26BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 2ND REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. RESPONSE TO COMMENT #4 FROM 1ST REVIEW DIRECTS
 REVIEWER TO PAGE A0.1, NOTE 1.30. THERE IS NO PLAN PAGE
 A0.1 IN THIS RE-SUBMITTAL.
 PLEASE CORRECT.
  
 2. THERE ARE TWO (2) PAGE A10.1 IN THIS RE-SUBMITTAL.
 PLEASE REMOVE ONE PAGE A10.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-06-04 Cont ID  
Sent By cthroop Date 2019-06-04 Time 10:03 Rev Time 0.00
Received By cthroop Date 2019-05-31 Time 14:09 Sent To  
Notes
2019-06-04 10:21:25ADDRESS: 346 NOTTINGHAM BLVD. TYPE: BLD-RES NEW SFR
  
 BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC M = FLORIDA BUILDING CODE MECHANICAL 2017 6TH
 EDITION
 FBC P = FLORIDA BUILDING CODE PLUMBING 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 1. PROVIDE SITE DRAINAGE PLAN.
 FBC R401.3 SITE DRAINAGE
 PROVIDE TWO SETS OF A SITE DRAINAGE PLAN SHOWING
 COMPLIANCE WITH FBC R401.3 DRAINAGE.
 SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER
 CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION THAT
 DOES NOT CREATE A HAZARD.
 LOTS SHALL BE GRADED TO DRAIN SURFACE WATER AWAY FROM
 FOUNDATION WALLS. THE GRADE SHALL FALL A MINIMUM OF 6
 INCHES WITHIN THE FIRST 10 FEET.
 EXCEPTION: WHERE LOT LINES, WALLS, SLOPES OR OTHER
 PHYSICAL BARRIERS PROHIBIT 6 INCHES OF FALL WITHIN 10
 FEET, DRAINS OR SWALES SHALL BE CONSTRUCTED TO ENSURE
 DRAINAGE AWAY FROM THE STRUCTURE.
 IMPERVIOUS SURFACES WITHIN 10 FEET OF THE BUILDING
 FOUNDATION SHALL BE SLOPED A MINIMUM OF
 2 PERCENT AWAY FROM THE BUILDING.
  
 2. PROVIDE PROPERLY COMPLETED ENERGY SUBMITTAL.
 OWNER/AGENT TO SIGN FORM MR405. BUILDER TO SIGN EPL
 CARD.
 FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405
 (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE
 SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE
 COMPLIANCE BY SECTION 405.
  
 R401.3 ENERGY PERFORMANCE LEVEL (EPL) DISPLAY CARD
 (MANDATORY).
  
 3. PROVIDE PRODUCT APPROVALS FOR EXTERIOR DOORS, OHD
 AND TYPE D HORIZONTAL SLIDER WINDOW.
 FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE WINDOW AND DOOR SUBMITTALS.
  
 4. REFERENCE PLAN PAGE A0.1 NOTE 1.30 STATES THIS BLDG.
 IS TYPE 1 W/APPROVED SPRINKLER. BLDG. IS TYPE V-B
 UN-SPROINKLED. PLEASE CLARIFY.
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 5. REFERENCE PLAN PAGE A0.2 DEMOLITION PLAN IS NOT
 APPLICABLE. SFR & GARAGE HAS BEEN REMOVED UNDER PERMIT
 # 17010312. REMOVE FROM PLAN.
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 6. REFERENCE PLAN PAGE A2.2 ROOF PLAN. NOTE STATES TOP
 OF BEAM IS 10' 00". TOP OF BEAM IS 20'00" PER PLAN PAGE
 A5.1. PLEASE CLARIFY.
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 7. REFERENCE PLAN PAGE A10.1 WINDOW SCHEDULE TYPE D
 WINDOW IS A HORIZONTAL SLIDER. PROVIDE PRODUCT
 APPROVALS.
 FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, WINDOW & WINDOW MULLION SUBMITTALS.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-09-16 Cont ID  
Sent By ppetty Date 2019-09-16 Time 13:58 Rev Time 0.00
Received By ppetty Date 2019-09-16 Time 13:58 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-06-04 Cont ID  
Sent By cthroop Date 2019-06-04 Time 10:30 Rev Time 0.00
Received By cthroop Date 2019-05-31 Time 14:09 Sent To  
Notes
2019-06-04 10:52:24ADDRESS: 346 NOTTINGHAM BLVD. TYPE: BLD-RES NEW SFR
  
 ELECTRICAL PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC M = FLORIDA BUILDING CODE MECHANICAL 2017 6TH
 EDITION
 FBC P = FLORIDA BUILDING CODE PLUMBING 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 1. AIC RATING OF SERVICE DISCONNECT AND PANEL
 FBC R E3606.3AVAILABLE SHORT-CIRCUIT CURRENT.
 SERVICE EQUIPMENT SHALL BE SUITABLE FOR THE MAXIMUM
 FAULT CURRENT AVAILABLE AT ITS SUPPLY TERMINALS, BUT
 NOT LESS THAN 10,000 AMPERES. (110.9)
  
 PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10; FBC RE E3404.2 & FBC RE E3606.3
  
 2. RISER DIAGRAM SHOWS A SINGLE GROUND ROD AS A
 SUPPLEMENTAL GROUNDING ELECTRODE. THIS SUPPLEMENTAL
 GROUNDING ELECTRODE NEEDS TO BE AUGMENTED BY AN
 ADDITIONAL ELECTRODE AT LEAST 6 FEET AWAY OR PROVIDE
 EVIDENCE OF RESISTANCE TO GROUND OF 25 OHMS OR LESS.
 NEC 250.53(A)(2); FBC RE E3608.4.
  
 3. REFERENCE PLAN PAGE E-1. NOTES USES THE WORD TEMPER
 WHEN NREFERING TO TAMPER RESISTANT RECEPTACLES. PLEASE
 CORRECT.
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 4. OUTLET SPACING IN KITCHEN NOT PER CODE.
 THE WALL SPACING REQUIREMENTS FOR KITCHEN COUNTER SPACE
 STATE THAT RECEPTACLE OUTLETS SHALL BE INSTALLED SO
 THAT NO POINT ALONG THE WALL LINE IS MORE THAN 24
 INCHES MEASURED HORIZONTALLY FROM A RECEPTACLE OUTLET
 IN THAT SPACE. THE PLAN PROVIDED DOES NOT MEET THIS
 CODE IN SOME AREAS. PROVIDE CORRECTION. NEC
 210.52(C)(1); FBC RE E3901.4
  
 5. GFCI OUTLET REQUIRED FOR DISHWASHER.
 PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC 210.8(D);
 FBC RE E3902.10.
  
 6. OUTLET SPACING FOR KITCHEN PENINSULA NOT PER CODE.
 E3901.4.3 PENINSULAR COUNTERTOP SPACE.
 AT LEAST ONE RECEPTACLE OUTLET SHALL BE INSTALLED AT
 EACH PENINSULAR COUNTERTOP SPACE WITH A LONG DIMENSION
 OF 24 INCHES (610 MM) OR GREATER AND A SHORT DIMENSION
 OF 12 INCHES (305 MM) OR GREATER. A PENINSULAR
 COUNTERTOP IS MEASURED FROM THE CONNECTING EDGE.
 [210.52(C)(3)]
  
 7. IDENTIFY ALL GFCI PROTECTED OUTLETS.
 SECTION E3902
 GROUND-FAULT AND ARC-FAULT
 CIRCUIT-INTERRUPTER PROTECTION
  
 8. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC
 210.8(D); FBC RE E3902.10.E3902.10 KITCHEN DISHWASHER
 BRANCH CIRCUIT.
 GROUND-FAULT CIRCUIT-INTERRUPTER PROTECTION SHALL BE
 PROVIDED FOR OUTLETS THAT SUPPLY DISHWASHERS IN
 DWELLING UNIT LOCATIONS. [210.8(D)]
  
 9. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT
 SERVICE. SHOW ON PLAN. NEC 250.94; FBC RE E3609.3
  
 10. SMOKE DETECTORS SHALL BE SMOKE/CO COMBINATION
 DEVICES.
 R315.1 CARBON MONOXIDE PROTECTION.
 EVERY SEPARATE BUILDING OR AN ADDITION TO AN EXISTING
 BUILDING FOR WHICH A PERMIT FOR NEW CONSTRUCTION IS
 ISSUED AND HAVING A FOSSIL-FUEL-BURNING HEATER OR
 APPLIANCE, A FIREPLACE, AN ATTACHED GARAGE, OR OTHER
 FEATURE, FIXTURE, OR ELEMENT THAT EMITS CARBON MONOXIDE
 AS BYPRODUCT OF COMBUSTION SHALL HAVE AN OPERATIONAL
 CARBON MONOXIDE ALARM INSTALLED WITHIN 10 FEET OF EACH
 ROOM USED FOR SLEEPING PURPOSES.
 R314.5 COMBINATION ALARMS.
 COMBINATION SMOKE AND CARBON MONOXIDE ALARMS SHALL BE
 PERMITTED TO BE USED IN LIEU OF SMOKE ALARMS.
  
 11. PROVIDE SERVICE OUTLET AT EXTERIOR MECHANICAL
 EQUIPMENT.
 E3901.12 HVAC OUTLET.
 A 125-VOLT, SINGLE-PHASE, 15- OR 20-AMPERE-RATED
 RECEPTACLE OUTLET SHALL BE INSTALLED AT AN ACCESSIBLE
 LOCATION FOR THE SERVICING OF HEATING, AIR-CONDITIONING
 AND REFRIGERATION EQUIPMENT. THE RECEPTACLE SHALL BE
 LOCATED ON THE SAME LEVEL AND WITHIN 25 FEET (7620 MM)
 OF THE HEATING, AIR-CONDITIONING AND REFRIGERATION
 EQUIPMENT. THE RECEPTACLE OUTLET SHALL NOT BE CONNECTED
 TO THE LOAD SIDE OF THE HVAC EQUIPMENT DISCONNECTING
 MEANS. (210.63)
  
 12 . PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF
 THE LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES
 SHALL BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT
 OF THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE.
 FBC EC R404.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2019-12-11 Cont ID  
Sent By cpuell Date 2019-12-11 Time 11:03 Rev Time 0.00
Received By cpuell Date 2019-12-05 Time 15:33 Sent To  
Notes
2019-12-06 15:33:53RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-10-10 Cont ID  
Sent By cthroop Date 2019-10-10 Time 09:04 Rev Time 0.00
Received By cthroop Date 2019-09-27 Time 14:27 Sent To  
Notes
2019-10-01 14:27:24R23

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-09-19 Cont ID  
Sent By cthroop Date 2019-09-19 Time 11:36 Rev Time 0.00
Received By cthroop Date 2019-08-26 Time 15:58 Sent To  
Notes
2019-09-17 08:13:37WITH TIM LARGE
2019-08-26 15:58:23R23

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-06-07 Cont ID  
Sent By cpuell Date 2019-06-07 Time 09:29 Rev Time 0.00
Received By cpuell Date 2019-05-16 Time 10:44 Sent To  
Notes
2019-05-17 10:45:01R23

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2020-02-12 Cont ID  
Sent By cthroop Date 2020-02-12 Time 12:58 Rev Time 0.00
Received By cthroop Date 2020-02-12 Time 11:47 Sent To  
Notes
2020-02-12 12:58:40MU-2020-004598-0000. CT

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2019-05-31 Cont ID  
Sent By cthroop Date 2019-05-31 Time 16:23 Rev Time 0.00
Received By cthroop Date 2019-05-31 Time 14:09 Sent To  
Notes
2019-05-31 16:24:10PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 (561) 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE
 PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW. PLEASE
 RETURN STAMPED AND WITH A COPY OF THE RECEIPT AS
 APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE
 FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD
 MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2019-09-11 Cont ID  
Sent By cmontell Date 2019-09-11 Time 14:32 Rev Time 0.00
Received By cmontell Date 2019-09-11 Time 14:32 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-05-25 Cont ID  
Sent By cmontell Date 2019-05-25 Time 05:32 Rev Time 0.00
Received By cmontell Date 2019-05-25 Time 05:23 Sent To  
Notes
2019-05-25 05:32:25MECHANICAL PLAN REVIEW FAIL
  
 1 - NEED OWNERS SIGNATURE ON ENERGY REPORT PER 2017 -
 FLORIDA BUILDING CODE - ENERGY CONSERVATION SEC.
 R103.1.1.2 CODE COMPLIANCE CERTIFICATION.
  
 CHRIS MONTELLO
 805-6733

Review Stop P PLUMBING
Rev No 3 Status P Date 2019-10-03 Cont ID  
Sent By lcrespo Date 2019-10-03 Time 07:23 Rev Time 0.00
Received By lcrespo Date 2019-10-03 Time 07:21 Sent To  
Notes
2019-10-03 07:25:1410/03/19 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6720
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2019-09-19 Cont ID  
Sent By tklarge Date 2019-09-19 Time 10:24 Rev Time 0.00
Received By tklarge Date 2019-09-19 Time 10:24 Sent To B
Notes
2019-09-18 15:03:461) SUBMIT TWO COPIES OF ENERGY CODE CALCULATIONS THAT
 SHOW THE EF RATING OF THE WATER HEATER AS .96.
 2) SHT. P-1 - WATER HEATER SCHEDULE SHOWS THE EF RATING
 OF THE WATER HEATER AS .90. THE EF RATING SHALL BE A
 MINIMUM OF .96.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-05-22 Cont ID  
Sent By thunt Date 2019-05-22 Time 15:55 Rev Time 0.00
Received By thunt Date 2019-05-22 Time 07:09 Sent To  
Notes
2019-05-22 15:55:34PLUMBING 1ST REVIEW**DENIED**
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 1) ENERGY EFFICIENCY FORM SHOULD BE 2017 NOT 2014 AS
 PROVIDED. ALSO THE WATER HEATER EF OF .90 IS BELOW MIN
 FEDERAL STANDARD. THE MIN IS .96 EF OR .93 U.E.F PER
 FEDERAL REGISTER VOL 81, NO 250 POSTED ON 12/29/2016.
 FBC-ENGERY C101.4.2.1
  
 2) THE WASHING MACHINE IS SHOWN TO BE VENTED BE AN AAV
 DEVICE. AAV ARE ONLY PERMITTED ON WASHING MACHINES WHEN
 THE HORIZONTAL BRANCH IS MIN 3". SEE STUDOR VENT
 INSTALLATION MANUAL PAGE 19.
  
 3) PLEASE ADD NOTED TO P-01 THAT ALL HOT WATER PIPING
 OUTSIDE OF THE CONDITIONED SPACED SHALL BE INSULATED
 WITH A MIN R-3 INSULATION. FBC-ENERGY R403.5.3
  
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR
 BUILDING DIVISION
 CITY OF WEST PALM BEACH
 401 CLEMATIS STREET, 1ST FLOOR
 WEST PALM BEACH, FL 33401
 561-248-2703
 [email protected]
 [email protected]

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status N Date 2019-10-10 Cont ID  
Sent By cthroop Date 2019-10-10 Time 09:02 Rev Time 0.00
Received By cthroop Date 2019-10-10 Time 08:51 Sent To  
Notes
2019-10-10 09:04:01PROVISO: ALL ROOFING SYSTEM COMPONENTS SHALL BE
 REVIEWED AND APPROVED BY DESIGNER PRIOR TO SUBMITTAL
 FOR REVIEW. CT

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2019-09-19 Cont ID  
Sent By cthroop Date 2019-09-19 Time 10:56 Rev Time 0.00
Received By cthroop Date 2019-09-19 Time 10:54 Sent To  
Notes
2019-09-19 10:57:01BUILDING PLAN REVIEW - ROOFING
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 2ND REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC M = FLORIDA BUILDING CODE MECHANICAL 2017 6TH
 EDITION
 FBC P = FLORIDA BUILDING CODE PLUMBING 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 1. PROVIDE PRODUCT APPROVALS FOR NEW ROOFING SYSTEM
 COMPONENTS.
 FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE ROOFING SUBMITTALS.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2019-05-31 Cont ID  
Sent By cthroop Date 2019-05-31 Time 16:49 Rev Time 0.00
Received By cthroop Date 2019-05-31 Time 14:09 Sent To  
Notes
2019-05-31 16:53:11BUILDING PLAN REVIEW - ROOFING
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC M = FLORIDA BUILDING CODE MECHANICAL 2017 6TH
 EDITION
 FBC P = FLORIDA BUILDING CODE PLUMBING 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 1. PROVIDE PRODUCT APPROVALS FOR NEW ROOFING SYSTEM
 COMPONENTS.
 FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE ROOFING SUBMITTALS.
  
  
  
  

Review Stop Z ZONING
Rev No 5 Status P Date 2020-01-30 Cont ID  
Sent By awooten Date 2020-01-30 Time   Rev Time 0.00
Received By awooten Date 2020-01-30 Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 4 Status F Date   Cont ID  
Sent By   Date 2019-12-11 Time   Rev Time 0.00
Received By   Date 2019-12-11 Time   Sent To  
Notes
2019-12-11 10:05:58*******************************ZONING REVIEW FAILED
 (REPEAT COMMENT)***************************************
  
 PLEASE SUBMIT A SEPARATE LANDSCAPE AND IRRIGATION
 PERMIT, IN ADDITION TO THIS PERMIT. SHOWING THE
 FOLLOWING:
 RESIDENTIAL LANDSCAPE REQUIREMENTS CITY OF WEST PALM
 BEACH
 SECTION 94-442(C)(2)A. SINGLE FAMILY DWELLING UNITS
  
 O GROSS LOT SQUARE FOOTAGE MINUS
 O BUILDING FOOTPRINT SQUARE FOOTAGE EQUALS
 O OPEN SPACE SQUARE FOOTAGE (ALL NON-BUILDING AREA)
 O ONE TREE REQUIRED FOR EACH 1,000 SQ FT OF OPEN SPACE
 OR PORTION THEREOF
 O ONE SHRUB REQUIRED FOR EACH 500 SQ FT OF OPEN SPACE
 OR PORTION THEREOF
  
 YOU CAN SUBMIT FOR A CONDITIONAL APPROVAL FOR THE
 LANDSCAPING. A FINAL LANDSCAPE PLAN MUST BE SUBMITTED,
 APPROVED AND PASS LANDSCAPE INSPECTION PRIOR TO
 OBTAINING CO FOR HOME. PLEASE CONTACT ME FOR MORE
 INFORMATION.
  
 PROPOSED DRIVEWAYS, MECHANICAL EQUIPMENT, POOLS, AND
 FENCES REQUIRE SEPARATE PERMITS.
  
 ALANA WOOTEN
 ASSOICATE PLANNER
 PLANNING DIVISION
 561-822-1449
 [email protected]

Review Stop Z ZONING
Rev No 3 Status F Date 2019-10-08 Cont ID  
Sent By awooten Date 2019-10-08 Time   Rev Time 0.00
Received By awooten Date 2019-10-08 Time   Sent To B
Notes
2019-10-08 16:03:20*******************************ZONING REVIEW FAILED
 (REPEAT COMMENT)***************************************
  
 PLEASE SUBMIT A SEPARATE LANDSCAPE AND IRRIGATION
 PERMIT, IN ADDITION TO THIS PERMIT. SHOWING THE
 FOLLOWING:
 RESIDENTIAL LANDSCAPE REQUIREMENTS CITY OF WEST PALM
 BEACH
 SECTION 94-442(C)(2)A. SINGLE FAMILY DWELLING UNITS
  
 O GROSS LOT SQUARE FOOTAGE MINUS
 O BUILDING FOOTPRINT SQUARE FOOTAGE EQUALS
 O OPEN SPACE SQUARE FOOTAGE (ALL NON-BUILDING AREA)
 O ONE TREE REQUIRED FOR EACH 1,000 SQ FT OF OPEN SPACE
 OR PORTION THEREOF
 O ONE SHRUB REQUIRED FOR EACH 500 SQ FT OF OPEN SPACE
 OR PORTION THEREOF
  
 PROPOSED DRIVEWAYS, MECHANICAL EQUIPMENT, POOLS, AND
 FENCES REQUIRE SEPARATE PERMITS.
  
 ALANA WOOTEN
 ASSOICATE PLANNER
 PLANNING DIVISION
 561-822-1449
 [email protected]

Review Stop Z ZONING
Rev No 2 Status F Date 2019-09-05 Cont ID  
Sent By awooten Date 2019-09-05 Time   Rev Time 0.00
Received By awooten Date 2019-09-05 Time   Sent To  
Notes
2019-09-05 15:39:08*******************************ZONING REVIEW FAILED
 (REPEAT COMMENT)***************************************
  
 PLEASE SUBMIT A SEPARATE LANDSCAPE AND IRRIGATION
 PERMIT, IN ADDITION TO THIS PERMIT. SHOWING THE
 FOLLOWING:
 RESIDENTIAL LANDSCAPE REQUIREMENTS CITY OF WEST PALM
 BEACH
 SECTION 94-442(C)(2)A. SINGLE FAMILY DWELLING UNITS
  
 O GROSS LOT SQUARE FOOTAGE MINUS
 O BUILDING FOOTPRINT SQUARE FOOTAGE EQUALS
 O OPEN SPACE SQUARE FOOTAGE (ALL NON-BUILDING AREA)
 O ONE TREE REQUIRED FOR EACH 1,000 SQ FT OF OPEN SPACE
 OR PORTION THEREOF
 O ONE SHRUB REQUIRED FOR EACH 500 SQ FT OF OPEN SPACE
 OR PORTION THEREOF
  
 PROPOSED DRIVEWAYS, MECHANICAL EQUIPMENT, POOLS, AND
 FENCES REQUIRE SEPARATE PERMITS.
  
 ALANA WOOTEN
 ASSOICATE PLANNER
 PLANNING DIVISION
 561-822-1449
 [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2019-06-06 Cont ID  
Sent By awooten Date 2019-06-06 Time   Rev Time  
Received By awooten Date 2019-06-06 Time   Sent To  
Notes
2019-06-06 15:07:17*******************************ZONING REVIEW
 FAILED***************************************
  
 PLEASE SUBMIT A SEPARATE LANDSCAPE AND IRRIGATION
 PERMIT. SHOWING THE FOLLOWING:
 RESIDENTIAL LANDSCAPE REQUIREMENTS CITY OF WEST PALM
 BEACH
 SECTION 94-442(C)(2)A. SINGLE FAMILY DWELLING UNITS
  
 O GROSS LOT SQUARE FOOTAGE MINUS
 O BUILDING FOOTPRINT SQUARE FOOTAGE EQUALS
 O OPEN SPACE SQUARE FOOTAGE (ALL NON-BUILDING AREA)
 O ONE TREE REQUIRED FOR EACH 1,000 SQ FT OF OPEN SPACE
 OR PORTION THEREOF
 O ONE SHRUB REQUIRED FOR EACH 500 SQ FT OF OPEN SPACE
 OR PORTION THEREOF
  
 PROPOSED DRIVEWAYS, MECHANICAL EQUIPMENT, POOLS, AND
 FENCES REQUIRE SEPARATE PERMITS.
  
 ALANA WOOTEN
 ASSOICATE PLANNER
 PLANNING DIVISION
 561-822-1449
 [email protected]
  