| 2019-06-17 09:33:56 | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 19050781 |
| | ADD: 1550 PALM BEACH LAKES BLVD. |
| | CONT: 5 STAR ELECTRICAL CONTRACTOR, LLC |
| | TEL: 855-305-7827 |
| | E-MAIL: DENIED |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION. |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: MON. JUNE 17, 2019 |
| | ACTION: DENIED |
| | |
| | 1) PLEASE BE AWARE EITHER A CERTIFIED GENERAL |
| | CONTRACTOR, BUILDING CONTRACTOR AND OR A PALM BEACH |
| | COUNTY BUILDING CONTRACTOR WITH PALM BEACH COUNTY |
| | COMPETENCY LICENSE WILL BE REQUIRED TO SIGN ONTO THIS |
| | PERMIT. 5 STAR ELECTRICAL CONTRACTOR, LLC IS WORKING |
| | OUT OF THE SCOPE OF THEIR LICENSE WITH THE SETTING OF |
| | CASH WRAPS. |
| | PART II |
| | ELECTRICAL AND ALARM SYSTEM |
| | CONTRACTING |
| | 489.505?DEFINITIONS |
| | |
| | |
| | 2) 5 STAR ELECTRICAL CONTRACTOR, LLC PERMIT APPLICATION |
| | THAT WAS SUBMITTED IS A COPY, NOT AN ORIGINAL. THE |
| | SIGNATURES ON THE PERMIT APPLICATION HAVE TO BE |
| | ORIGINAL SIGNATURES, NOT A PHOTOCOPY. |
| | 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION. 105.4 CONDITIONS OF |
| | THE PERMIT. THE ISSUANCE OR GRANTING OF A PERMIT SHALL |
| | NOT BE CONSTRUED TO BE A PERMIT FOR, OR AN APPROVAL OF, |
| | ANY VIOLATION OF ANY OF THE PROVISIONS OF THIS CODE OR |
| | OF ANY FEDERAL, STATE OR LOCAL LAWS, ORDINANCES, CODES |
| | OR REGULATIONS. |
| | |
| | 3) ARCHITECTS SIGNATURE AND SEAL: |
| | 3A) THE SIGNATURE WITHIN THE ARCHITECTS SEAL IS A |
| | PHOTO-COPY. FL ADMIN CODE 61G16.003 (1) ARCHITECTS. |
| | PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS |
| | PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR |
| | PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE |
| | DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT. |
| | |
| | 3B) THE ARCHITECTS PRINTED NAME DAVID ANTHONY JR. THIEL |
| | WITHIN THE SEAL IS DIFFERENT FROM THE WRITTEN NAME J. |
| | JAY. FL ADMIN CODE 61G16.003 (1) ARCHITECTS. |
| | |
| | 3C) WITHIN THE SEAL THE ARCHITECT WHEN SIGNING THEIR |
| | NAME TO THE DOCUMENT IS TO DATE THE PLANS WHEN SIGNED. |
| | FL. ADMIN. CODE 61G1-16.004 TITLE BLOCK. ARCHITECT. (4) |
| | DATE PREPARED. |
| | |
| | 3D) THE TITLEBLOCK IS MISSING THE ARCHITECTS BUSINESS |
| | LICENSE NUMBER THAT SHOULD ALSO BE LISTED WITHIN THE |
| | TITLEBLOCK. 61G1-16.004 TITLE BLOCK. ARCHITECT. (2) |
| | FIRM LICENSE NUMBER. |
| | |
| | 4) THE TITLE SHEET T1.0 UNDER THE HEADING RACKING/ |
| | FIXTURES STATES THAT NO SEPARATE PERMIT IS REQUIRED. |
| | PLEASE REVIEW THE 2017 WEST PALM BEACH AMENDMENTS TO |
| | THE FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATIVE |
| | SECTION 105.2 BUILDING (6). NON FIXED AND MOVABLE |
| | FIXTURES, CASES, RACKS, AND COUNTERS NOT OVER 5 FEET 9 |
| | INCHES IN HEIGHT. |
| | WHEN RACK STORAGE IS OVER 5 FOOT 9 INCHES IN HEIGHT A |
| | SEPARATE PERMIT APPLICATION AND PLANS ARE REQUIRED. |
| | PLEASE NOTE THE CITY HAS NO PROBLEMS WITH THE RACK |
| | STORAGE PLANS BEING PART OF THE OVERALL BUILDING SET OF |
| | PLANS. |
| | |
| | 5) STRUCTURAL CALCULATIONS AND REPORT FOR RACK STORAGE |
| | PREPARED BY PETER HIGGINS. PLEASE NOTE THE COVERAGE OF |
| | THIS REPORT IS SIGNED AND SEALED BUT THERE IS NO INDEX |
| | INDICATING HOW MANY PAGES ARE IN THIS REPORT WHICH ARE |
| | COVERED BY THE SEAL. |
| | FL ADMIN CODE 61G15-23.002 ENGINEERS. EFFECTIVE DATE |
| | 05/06/2009. (2)(A) EVERY SHEET OF PLANS, PRINTS AND |
| | REPORTS WHICH MUST BE SEALED UNDER THE PROVISIONS OF |
| | CHAPTER 471, F.S., SHALL BE SEALED, SIGNED AND DATED BY |
| | THE PROFESSIONAL ENGINEER IN RESPONSIBLE CHARGE. |
| | |
| | 6) SHEET F1.0 FIXTURE PLAN HAS 2 ISSUES: |
| | |
| | 6A) THE WRITTEN PORTION ON THE BOTTOM OF THE SHEET IS |
| | HARDLY VISIBLE, THE SHEET NEEDS TO BE REPRODUCED TO BE |
| | LEGIBLE. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY |
| | TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK |
| | PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE |
| | PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES, |
| | RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING |
| | OFFICIAL. |
| | |
| | 6B) THE PLANS ARE DRAWN TO A 1/16 INCH SCALE. 107.2.1.3 |
| | QUALITY OF BUILDING PLANS. BUILDING PLANS SHALL BE |
| | DRAWN TO A MINIMUM 1/8 INCH SCALE UPON SUBSTANTIAL |
| | PAPER. THE BUILDING OFFICIAL MAY ESTABLISH THROUGH |
| | DEPARTMENTAL POLICY, OTHER STANDARDS FOR PLANS AND |
| | SPECIFICATIONS, IN ORDER TO PROVIDE CONFORMITY TO ITS |
| | RECORD RETENTION PROGRAM. THIS POLICY MAY INCLUDE SUCH |
| | THINGS AS MINIMUM SIZE, SHAPE, CONTRAST, CLARITY, OR |
| | OTHER ITEMS RELATED TO RECORDS MANAGEMENT. ELECTRONIC |
| | MEDIA MUST BE COMPATIBLE WITH THE ARCHIVE |
| | REQUIREMENTS OF FLORIDA STATUTES. |
| | |
| | 6C) THE FIXTURE PLAN IS SO LIGHT IN COLOR AND LITTLE |
| | CONTRAST AS WELL AS 1/16 INCH SCALE IT IS NOT POSSIBLE |
| | TO DETERMINE WHAT AREAS THE WORK IS TO OCCUR FOR RACK |
| | STORAGE. . WITH THE NEXT PLAN REVIEW CYCLE THERE MAYBE |
| | ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS AND |
| | INFORMATION LACKING UNDER THE PRIOR REVIEW. |
| | 6D) THE FIXTURE PLAN F1.0 NEEDS TO SHOW COMPLIANCE |
| | WITH: 61G15-23.002 ENGINEER SEAL SIGNATURE AND DATE |
| | SHALL BE AFFIXED. (2) (B) |
| | 2. IDENTIFICATION OF THE PROJECT, BY ADDRESS OR BY LOT |
| | NUMBER, BLOCK NUMBER, SECTION OR SUBDIVISION AND CITY |
| | OR COUNTY. |
| | 3. IDENTIFICATION OF THE APPLICABLE BUILDING CODE AND |
| | CHAPTER(S) THAT THE DESIGN IS INTENDED TO MEET. |
| | 4. IDENTIFICATION OF ANY COMPUTER PROGRAM USED FOR |
| | ENGINEERING THE SPECIFICATIONS OR CALCULATIONS. |
| | |
| | 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE |
| | THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED |
| | DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE |
| | MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS |
| | AND INFORMATION LACKING UNDER THE PRIOR REVIEW. |
| | |
| | JAMES A. WITMER BN, PX, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |