Plan Review Details - Permit 19050772
Plan Review Stops For Permit 19050772
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2019-10-09 Cont ID  
Sent By shill Date 2019-10-09 Time 06:26 Rev Time 0.00
Received By shill Date 2019-10-09 Time 06:26 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-06-25 Cont ID  
Sent By pvalenti Date 2019-06-25 Time 17:40 Rev Time 0.00
Received By pvalenti Date 2019-06-25 Time 17:40 Sent To  
Notes
2019-06-25 17:51:38***CORRECTIONS***
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 BUILDING 2ND PLAN REVIEW DENIED:
  
 1. FBC R 303.3 THE PROPOSED PLAN CLOSES UP THE EXISTING
 WINDOW OPENING. INDICATE, ON PLANS, HOW COMPLIANCE WITH
 SECTION 303.3 OF THE RESIDENTIAL CODE FOR ARTIFICIAL
 LIGHT AND VENTILATION WILL BE MET AT THE EXISTING
 POWDER ROOM.
  
 PROVISOS:
  
 1. FBC B 107.3.4.1 PROVIDE A SIGNED REVIEW STAMP BY THE
 ENGINEER OF RECORD ON ALL PRODUCT APPROVALS.
 2. FBC R 703.7.3 PROVIDE WATER RESISTIVE BARRIERS (2)
 LAYERS AT EXTERIOR WALL IN-FILL AREAS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-05-24 Cont ID  
Sent By shill Date 2019-05-24 Time 08:45 Rev Time 0.00
Received By shill Date 2019-05-24 Time 08:45 Sent To  
Notes
2019-05-24 08:46:46****CORRECTIONS****
  
 SAMANTHA HILL / JONATHAN BROOKS
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 CHANGE CLASSIFICATION OF WORK FROM LEVEL 1 ALTERATION
 TO LEVEL 2 ALTERATION AS PER 504.1 FBC-EXISTING
 BUILDING
 PROVIDE TWO SETS OF PRODUCT APPROVALS/NOA'S FOR THE
 PROPOSED WINDOWS TO BE USED. AS PER RULE 61G20-3
 PROVIDE DRAWING DETAIL SHOWING CONSTRUCTION METHOD OF
 PROPOSED NEW SHOWER WALLS AND SHOWING COMPLIANCE WITH
 R302.2 AND R702.4.2. AS PER 107.2.1
 PROVIDE DRAWING DETAIL SHOWING CONSTRUCTION METHOD OF
 2"X 6" INFILL FOR WINDOW REMOVAL AND SHOW COMPLIANCE
 WITH SECTION [RE]402 AND SECTION R703. AS PER 107.2.1
 EXISTING POWDER ROOM MUST COMPLY WITH R303.3
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2019-10-07 Cont ID  
Sent By ppetty Date 2019-10-07 Time 10:59 Rev Time 0.00
Received By ppetty Date 2019-10-07 Time 10:59 Sent To  
Notes
2019-10-07 10:59:48PROVISO 210.52-D AND FBC 314+315

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2019-06-26 Cont ID  
Sent By fgiaquin Date 2019-06-26 Time 07:07 Rev Time 0.00
Received By fgiaquin Date 2019-06-26 Time 06:52 Sent To I
Notes
2019-06-26 07:06:22ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. VALUE LOW FOR TOTAL AMOUNT OF WORK SHOWN. PLEASE
 PROVIDE A CONTRACT INCLUDING ALL MATERIALS AND LABOR
 FOR ENTIRE RENOVATION (ALL TRADES) SIGNED BY BOTH OWNER
 AND CONTRACTOR.
  
 FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
 2. AS PER LAST PLAN REVIEW COMMENTS A 20AMP GFCI
 RECEPTACLE ON A 20AMP DEDICATED CIRCUIT FOR BATHROOM
 RECEPTACLES ONLY IS REQUIRED WITHIN 3FT OF EACH BASIN.
 NEC 210.52D PLEASE PROVIDE CORRECTION.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-05-30 Cont ID  
Sent By jpearson Date 2019-05-30 Time 15:52 Rev Time 0.00
Received By jpearson Date 2019-05-30 Time 15:52 Sent To  
Notes
2019-05-30 14:41:52CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. A GFCI PROTECTED RECEPTACLE OUTLET ON A 20 AMP
 CIRCUIT IS REQUIRED WITHIN 3 FEET OF EACH BASIN.
 PROVIDE CORRECTION. NEC 210.11(C)(3), 210.52(D); FBC RE
 E3703.4, E3901.6
 2. NOTE 1 STATES THAT 50% OF LAMPS SHALL BE ENERGY
 EFFICIENT PER FBC R-504. THIS IS NOT THE CURRENT CODE.
 A MINIMUM OF 75 PERCENT OF THE LAMPS IN PERMANENTLY
 INSTALLED LIGHTING FIXTURES SHALL BE HIGH-EFFICACY
 LAMPS OR A MINIMUM OF 75 PERCENT OF THE PERMANENTLY
 INSTALLED LIGHTING FIXTURES SHALL CONTAIN ONLY HIGH
 EFFICACY LAMPS. PROVIDE CORRECTION, A NOTE WILL
 SUFFICE. FBC EC C405.1, R404.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop HIST HISTORICAL
Rev No 3 Status P Date 2019-10-08 Cont ID  
Sent By fmittner Date 2019-10-08 Time 14:43 Rev Time 0.00
Received By fmittner Date 2019-10-08 Time 14:43 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2019-06-25 Cont ID  
Sent By fmittner Date 2019-06-25 Time 15:38 Rev Time 0.00
Received By fmittner Date 2019-06-25 Time 15:38 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2019-06-04 Cont ID  
Sent By fmittner Date 2019-06-04 Time 11:26 Rev Time 0.00
Received By fmittner Date 2019-06-04 Time 11:26 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-10-09 Cont ID  
Sent By shill Date 2019-10-09 Time 06:32 Rev Time 0.00
Received By shill Date 2019-09-26 Time 14:04 Sent To  
Notes
2019-09-27 14:04:16R07

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-06-26 Cont ID  
Sent By fgiaquin Date 2019-06-26 Time 07:07 Rev Time 0.00
Received By fgiaquin Date 2019-06-13 Time 15:31 Sent To  
Notes
2019-06-14 15:35:31R09

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-06-04 Cont ID  
Sent By cpuell Date 2019-06-04 Time 14:34 Rev Time 0.00
Received By cpuell Date 2019-05-15 Time 15:32 Sent To  
Notes
2019-05-16 15:32:41R12

Review Stop P PLUMBING
Rev No 3 Status P Date 2019-10-04 Cont ID  
Sent By gjohnson Date 2019-10-04 Time 10:24 Rev Time 0.00
Received By gjohnson Date 2019-10-02 Time 14:24 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-06-18 Cont ID  
Sent By thunt Date 2019-06-18 Time 09:23 Rev Time 0.00
Received By thunt Date 2019-06-18 Time 09:23 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2019-05-17 Cont ID  
Sent By gjohnson Date 2019-05-17 Time 17:06 Rev Time 0.00
Received By gjohnson Date 2019-05-17 Time 09:02 Sent To  
Notes
***NONE***