Plan Review Details - Permit 19050721
Plan Review Stops For Permit 19050721
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2019-08-08 Cont ID  
Sent By cthroop Date 2019-08-08 Time 17:20 Rev Time 0.00
Received By cthroop Date 2019-08-08 Time 15:15 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2019-08-06 Cont ID  
Sent By cthroop Date 2019-08-06 Time 16:37 Rev Time 0.00
Received By cthroop Date 2019-08-06 Time 15:48 Sent To  
Notes
2019-08-06 16:38:08SIGNATURE AND SEAL.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-07-26 Cont ID  
Sent By cthroop Date 2019-07-26 Time 14:00 Rev Time 0.00
Received By cthroop Date 2019-07-19 Time 07:06 Sent To  
Notes
2019-07-26 14:04:02BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 2ND REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. SEE COMMENT #8 FROM 1ST REVIEW - GUTTERS. DESIGNERS
 RESPONSE NOTED. PROVIDE CODE REFERENCE OR REFERENCE
 STANDARD EXEMPTING THE REQUIREMENTS OF R318.5.
  
 R318.5PROTECTION AGAINST DECAY AND TERMITES.
 GUTTERS WITH DOWNSPOUTS ARE REQUIRED ON ALL BUILDINGS
 WITH EAVES OF LESS THAN 6 INCHES (152 MM) HORIZONTAL
 PROJECTION EXCEPT FOR GABLE END RAKES OR ON A ROOF
 ABOVE ANOTHER ROOF.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-05-21 Cont ID  
Sent By cthroop Date 2019-05-21 Time 11:59 Rev Time 0.00
Received By cthroop Date 2019-05-16 Time 13:03 Sent To  
Notes
2019-05-21 12:31:04BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC M = FLORIDA BUILDING CODE MECHANICAL 2017 6TH
 EDITION
 FBC P = FLORIDA BUILDING CODE PLUMBING 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 1. VALUE HAS BEEN ADJUSTED FROM $105,000 TO $129,257
 BASED ON THE ICC BUILDING VALUATION DATA PUBLISHED FEB.
 2019.
  
 2. PROVIDE SITE DRAINAGE PLAN.
 FBC R401.3 SITE DRAINAGE
 PROVIDE TWO SETS OF A SITE DRAINAGE PLAN SHOWING
 COMPLIANCE WITH FBC R401.3 DRAINAGE.
  
 3. ROOFING PERMIT REQUIRED. NOA 14-1030.01 FOR FLAT
 ROOF HAS EXPIRED. PROVIDE NOA FOR PITCHED ROOF.
 FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE ROOFING SUBMITTALS.
  
 4. PRODUCT APPROVALS FOR PROPOSED EXTERIOR DOORS IS
 PENDING. PROVIDE CURRENT APPROVED PRODUCT APPROVALS.
 FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE DOOR SUBMITTALS.
  
 5. PROVIDE CONNECTION DETAIL BETWEEN CONTAINER AND
 FOUNDATION METAL PLATE EMBEDS. IF THIS IS A WELDED
 CONNECTION, PROVIDE WELD DETAILS. ALSO PROVIDE ON-SITE
 WELDER CERTIFICATIONS AT TIME OF INSPECTION.
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 6. PROVIDE CONNECTION DETAIL BETWEEN CONTAINERS. IF
 THIS IS A WELDED CONNECTION, PROVIDE WELD DETAILS. ALSO
 PROVIDE ON-SITE WELDER CERTIFICATIONS AT TIME OF
 INSPECTION.
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 7. PROVIDE FASTNER SCHEDULE FOR EXTERIOR HIGH RIB METAL
 LATH TO CONTAINER.
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 8. PROVIDE GUTTERS.
 R318.5PROTECTION AGAINST DECAY AND TERMITES.
 GUTTERS WITH DOWNSPOUTS ARE REQUIRED ON ALL BUILDINGS
 WITH EAVES OF LESS THAN 6 INCHES (152 MM) HORIZONTAL
 PROJECTION EXCEPT FOR GABLE END RAKES OR ON A ROOF
 ABOVE ANOTHER ROOF.
  
 9. PROVIDE PRODUCT SPECIFICATIONS FOR SPRAY FOAM
 INSULATION.
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 10. REF. PLAN PAGE S-1. THERE ARE TWO DETAILS MARKED 4.
 PLEASE CLARIFY.
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 11. PROVIDE FRAMING DETAIL FOR ALL WINDOW AND EXTERIOR
 DOOR OPENINGS.
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 12. REF. PLAN PAGE A-2 FOR THE FOLLOWING:
 12A. SPECIFY SIZE OF ROOF RAFTERS.
 12B. SPECIFY FASTENERS FOR 2X6 PT PLATE TO CONTAINER
 TOP RAIL.
 12C. SPECIFY BOLTS AT H33 TO RAFTER CONNECTION.
 12D. SOLID BLOCKING IS REQUIRED BETWEEN 2X6 TOP PLATE
 AND TOP OF CONTAINER.
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 13. FOUNDATION PLAN PAGE S-1 SHOWS C2 COLUMN PADS IN
 INTERIOR OF FLOOR SPACE. DETAIL 2 PLAN PAGE A-2 SHOWS
 16X16 CONTINUOS GRADE BEAMS. PLEASE CLARIFY.
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 14. PROVIDE DETAIL FOR TOP OF POST CONNECTION FOR C2
 COLUMN.
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED OR MARK VOID.
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2019-08-06 Cont ID  
Sent By cthroop Date 2019-08-06 Time 16:37 Rev Time 0.00
Received By cthroop Date 2019-08-06 Time 15:48 Sent To  
Notes
2019-08-06 16:37:40SIGNATURE AND SEAL.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-07-26 Cont ID  
Sent By cthroop Date 2019-07-26 Time 13:59 Rev Time 0.00
Received By cthroop Date 2019-07-19 Time 07:07 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-05-21 Cont ID  
Sent By cthroop Date 2019-05-21 Time 15:14 Rev Time 0.00
Received By cthroop Date 2019-05-16 Time 13:03 Sent To  
Notes
2019-05-21 15:27:41ELECTRICAL PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE SECOND GROUND AT SERVICE.
 RISER DIAGRAM SHOWS A SINGLE GROUND ROD AS A
 SUPPLEMENTAL GROUNDING ELECTRODE. THIS SUPPLEMENTAL
 GROUNDING ELECTRODE NEEDS TO BE AUGMENTED BY AN
 ADDITIONAL ELECTRODE AT LEAST 6 FEET AWAY OR PROVIDE
 EVIDENCE OF RESISTANCE TO GROUND OF 25 OHMS OR LESS.
 NEC 250.53(A)(2); FBC RE E3608.4
  
 2. PROVIDE INTER SYSTEM BONDING TERMINATION POINT.
 PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT
 SERVICE. SHOW ON PLAN. NEC 250.94; FBC RE E3609.3
  
 3. INSTALL SMOKE DETECTORS PER R314.3.
 R314.3 LOCATION.
 SMOKE ALARMS SHALL BE INSTALLED IN THE FOLLOWING
 LOCATIONS:
 1.IN EACH SLEEPING ROOM.
 2.OUTSIDE EACH SEPARATE SLEEPING AREA IN THE IMMEDIATE
 VICINITY OF THE BEDROOMS.
  
 4. DISHWASHER SHALL BE GFCI PROTECTED.
 PROVIDE GFCI PROTECTION FOR DISHWASHERS. NEC 210.8(D);
 FBC RE E3902.10
  
 5. SERVICE EQUIPMENT SHALL BE LABELED WITH AIC RATING.
 PROVIDE NOTE THAT THE SERVICE EQUIPMENT SHALL BE MARKED
 WITH THE MAXIMUM AVAILABLE SHORT CIRCUIT CURRENT
 AVAILABLE PER NEC 110.24 & FBC RE E3606.4.
  
 6. PROVIDE AFCI PROTECTION PER E3902.16.
 BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15-
 AND 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY
 ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES,
 DENS, BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS,
 HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS
 SHALL BE AFCI PROTECTED. PROVIDE COMPLIANCE. NEC
 210.12; FBC RE E3902.16.
  
 7. PROVIDE TAMPER RESISTANT RECEPTACLES.
 PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A NOTE
 WILL SUFFICE. NEC 406.12; FBC RE E4002.14.
  
 8. PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE.
 FBC EC R404.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2019-08-08 Cont ID  
Sent By cthroop Date 2019-08-08 Time 17:20 Rev Time 0.00
Received By cthroop Date 2019-08-08 Time 13:25 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-08-06 Cont ID  
Sent By cthroop Date 2019-08-06 Time 16:38 Rev Time 0.00
Received By cthroop Date 2019-08-01 Time 09:04 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-07-26 Cont ID  
Sent By cthroop Date 2019-07-26 Time 13:59 Rev Time 0.00
Received By cthroop Date 2019-07-08 Time 11:01 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-06-03 Cont ID  
Sent By lmarchan Date 2019-06-03 Time 15:54 Rev Time 0.00
Received By lmarchan Date 2019-05-15 Time 15:17 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2019-08-14 Cont ID  
Sent By lmarchan Date 2019-08-14 Time 09:35 Rev Time 0.00
Received By lmarchan Date 2019-08-09 Time 07:58 Sent To  
Notes
2019-08-14 09:35:31RECEIPT - MU2019-025471-0000 - $0.00 DUE
2019-08-09 07:58:448/9/19 SENT EMAIL TO IMPACT FEE OFFICE. LEM

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2019-05-21 Cont ID  
Sent By cthroop Date 2019-05-21 Time 12:57 Rev Time 0.00
Received By cthroop Date 2019-05-16 Time 13:03 Sent To  
Notes
2019-05-21 13:00:21IMPACT FEES - DIGITAL SUBMITTALS
  
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected] .
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2019-07-26 Cont ID  
Sent By cthroop Date 2019-07-26 Time 13:59 Rev Time 0.00
Received By cthroop Date 2019-07-19 Time 07:06 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-05-21 Cont ID  
Sent By cthroop Date 2019-05-21 Time 15:07 Rev Time 0.00
Received By cthroop Date 2019-05-16 Time 13:03 Sent To  
Notes
2019-05-21 15:14:36MECHANICAL PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE CU TIE DOWN NOA.
 FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE TIE DOWN SUBMITTALS.
  
 2. MECHANICAL PLAN ON PLAN PAGE M-1 IS FLIPPED AND
 INVERTED. PLEASE CLARIFY.
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 3. PROVIDE BATH EXHAUST DETAIL FOR A FLAT ROOF.
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 4. OVERCURRENT PROTECTION FOR AIR HANDLER ASPT30C14A IS
 OVERSIZED. PROVIDE OVERCURRENT PROTECTION PER
 MANUFACTURERS SPCIFICATIONS.
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  
  
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-07-26 Cont ID  
Sent By cthroop Date 2019-07-26 Time 13:59 Rev Time 0.00
Received By cthroop Date 2019-07-19 Time 07:07 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-05-21 Cont ID  
Sent By cthroop Date 2019-05-21 Time 15:30 Rev Time 0.00
Received By cthroop Date 2019-05-16 Time 13:03 Sent To  
Notes
2019-05-21 15:53:36PLUMBING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE A CODE COMPLIANT RISER DIAGRAHM.
 PLUMBING RISER - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1 ADMINISTRATION SECTION
 107.3.5.3 (12)
  
 2. PROVIDE PAN FOR WATER HEATER.
 P2801.6REQUIRED PAN.
 WHERE A STORAGE TANK-TYPE WATER HEATER OR A HOT WATER
 STORAGE TANK IS INSTALLED IN A LOCATION WHERE WATER
 LEAKAGE FROM THE TANK WILL CAUSE DAMAGE, THE TANK SHALL
 BE INSTALLED IN A PAN CONSTRUCTED OF ONE OF THE
 FOLLOWING:
 1. 1.GALVANIZED STEEL OR ALUMINUM OF NOT LESS THAN
 0.0236 INCH (0.6010 MM) IN THICKNESS.
 2. 2.PLASTIC NOT LESS THAN 0.036 INCH (0.9 MM) IN
 THICKNESS.
 3. 3.OTHER APPROVED MATERIALS.
  
 3. PROVIDE DETAIL FOR WATER HEATER DISCHARGE.
 P2804.6.1REQUIREMENTS FOR DISCHARGE PIPE.
 THE DISCHARGE PIPING SERVING A PRESSURE-RELIEF VALVE,
 TEMPERATURE RELIEF VALVE OR COMBINATION VALVE SHALL:
 DISCHARGE TO THE FLOOR, TO THE PAN SERVING THE WATER
 HEATER OR STORAGE TANK, TO A WASTE RECEPTOR OR TO THE
 OUTDOORS.
 P2801.6.2PAN DRAIN TERMINATION.
 THE PAN DRAIN SHALL EXTEND FULL-SIZE AND TERMINATE OVER
 A SUITABLY LOCATED INDIRECT WASTE RECEPTOR OR SHALL
 EXTEND TO THE EXTERIOR OF THE BUILDING AND TERMINATE
 NOT LESS THAN 6 INCHES (152 MM) AND NOT MORE THAN 24
 INCHES (610 MM) ABOVE THE ADJACENT GROUND SURFACE.
  
 4. PROVIDE DETAIL FOR SHOWER PAN.
 P2709.1 SHOWER PAN CONSTRUCTION.
 P2709.3 SHOWER PAN LINING INSTALLATION.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  
  
  

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2019-07-26 Cont ID  
Sent By cthroop Date 2019-07-26 Time 13:59 Rev Time 0.00
Received By cthroop Date 2019-07-19 Time 07:07 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2019-05-21 Cont ID  
Sent By cthroop Date 2019-05-21 Time 15:27 Rev Time 0.00
Received By cthroop Date 2019-05-16 Time 13:03 Sent To  
Notes
2019-05-21 15:30:20BUILDING PLAN REVIEW - ROOFING
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. ROOFING PERMIT REQUIRED.
 NOA 14-1030.01 FOR FLAT ROOF HAS EXPIRED. PROVIDE NOA
 FOR PITCHED ROOF.
 FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE ROOFING SUBMITTALS.
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2019-08-08 Cont ID  
Sent By cthroop Date 2019-08-08 Time 17:20 Rev Time 0.00
Received By cthroop Date 2019-08-08 Time 15:15 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2019-08-06 Cont ID  
Sent By cthroop Date 2019-08-06 Time 16:37 Rev Time 0.00
Received By cthroop Date 2019-08-06 Time 15:48 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2019-07-17 Cont ID  
Sent By cthroop Date 2019-07-17 Time 17:06 Rev Time 0.00
Received By cthroop Date 2019-07-17 Time 17:06 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2019-05-21 Cont ID  
Sent By cthroop Date 2019-05-21 Time 12:55 Rev Time 0.00
Received By cthroop Date 2019-05-16 Time 13:03 Sent To  
Notes
2019-05-21 12:57:41BUILDING PLAN REVIEW - DIGITAL SIGNATURES AND SEALS
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
  
 DIGITAL REVIEW
  
 1. DIGITAL SIGNATURES/SEALS ARE NOT IN ACCORDANCE WITH
 FS 471, FS 481 AS NOTED. NEW SHEETS SUBMITTED IN THE
 NEXT REVIEW CYCLE REQUIRE REVIEW.
  
 2. UPLOAD VIA THE PROJECTDOX PORTAL WITH DIGITAL
 SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE
 THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT.
  
  
  

Review Stop Z ZONING
Rev No 3 Status P Date 2019-08-02 Cont ID  
Sent By llouie Date 2019-08-02 Time   Rev Time 0.00
Received By llouie Date 2019-08-02 Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2019-07-19 Cont ID  
Sent By llouie Date 2019-07-19 Time   Rev Time 0.00
Received By llouie Date 2019-07-19 Time   Sent To  
Notes
2019-07-19 12:08:47** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) A SURVEY OF THE PROPERTY WAS NOT PROVIDED WITH THE
 PERMIT SUBMITTAL. PLEASE PROVIDE. [6/3/2019 REPEAT
 COMMENT]
  
 2.) A SEPARATE PERMIT FOR LANDSCAPING IS REQUIRED PRIOR
 TO THE APPROVAL OF THIS PERMIT. PLEASE SUBMIT.
 [6/3/2019 REPEAT COMMENT]
  
  
 NOTES:
  
 * SEPARATE PERMITS AND REVIEWS REQUIRED FOR:
 LANDSCAPING AND HARDSCAPES (I.E. DRIVEWAY AND WALKWAYS,
 PATIOS, ETC.).
  
 * REVISION MAY RESULT IN ADDITIONAL COMMENTS.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  
 * ZONE: SF7
  

Review Stop Z ZONING
Rev No 1 Status F Date 2019-06-03 Cont ID  
Sent By llouie Date 2019-06-03 Time   Rev Time  
Received By llouie Date 2019-06-03 Time   Sent To  
Notes
2019-06-03 14:49:13** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) A SURVEY OF THE PROPERTY WAS NOT PROVIDED WITH THE
 PERMIT SUBMITTAL. PLEASE PROVIDE.
  
 2.) WILL A WALKWAY FROM THE SIDEWALK TO THE COVERED
 ENTRANCE BE PROVIDED? IF SO, PLEASE ILLUSTRATE IN THE
 SITE PLAN.
  
 3.) STRUCTURAL OVERHANGS (I.E. EAVES, ROOF OVERHANGS,
 ETC.) SHALL NOT EXTEND MORE THAN 3 FT. INTO ANY
 REQUIRED SETBACK. PLEASE SHOW DIMENSIONS FOR COMPLIANCE
 WITH THIS REQUIREMENT. [ZLDR S.94-305(B)(2)]
  
 4.) SHOW SETBACK DISTANCE FROM THE PROPOSED A/C UNIT
 COMPRESSOR PAD TO THE PROPERTY LINE. PLEASE NOTE THAT
 ALL MECHANICAL EQUIPMENT MAY NOT PROJECT MORE THAN 4
 FT. INTO A REQUIRED SETBACK. SHOW SETBACK DISTANCE FOR
 CONSISTENCY. [ZLDR S.94-305(B)(4)]
  
 5.) BUILDING ELEVATIONS DO NOT SEEM TO MATCH FLOOR PLAN
 (I.E. DIRECTION). PLEASE ADDRESS FOR CONSISTENCY.
  
 6.) A SEPARATE PERMIT FOR LANDSCAPING IS REQUIRED PRIOR
 TO THE APPROVAL OF THIS PERMIT. PLEASE SUBMIT.
  
 NOTES:
  
 * SEPARATE PERMITS AND REVIEWS REQUIRED FOR:
 LANDSCAPING AND HARDSCAPES (I.E. DRIVEWAY AND WALKWAYS,
 PATIOS, ETC.).
  
 * REVISION MAY RESULT IN ADDITIONAL COMMENTS.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  
 * ZONE: SF7