| Plan Review Stops For Permit 19050683 |
| Review Stop |
AD |
ADDRESSING |
| Rev No |
1 |
Status |
N |
Date |
2019-07-18 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2019-07-18 |
Time |
09:20 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2019-07-18 |
Time |
08:34 |
Sent To |
|
|
| Notes |
| 2019-07-18 09:21:51 | ADDRESS PREVIOUSLY ASSIGNED BY MICHEAL ORIO. | | | PCN: 74434332020020000 1510 BELVEDERE RD |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2019-11-12 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2019-11-12 |
Time |
12:52 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2019-11-12 |
Time |
12:51 |
Sent To |
|
|
| Notes |
| 2019-11-12 12:50:55 | PROVISOS: | | | 1. PROVIDE PRODUCT APPROVALS FOR WINDOWS, STOREFRONT | | | AND DOORS. | | | 2. ROOF TRUSS SHOP DRAWINGS TO BE PROVIDED TO THE | | | INSPECTOR PRIOR TO INSTALLATION. | | | 3. PROVIDE PRODUCT APPROVALS AND ENGINEERING, IF | | | APPLICABLE, WITH SUB PERMIT APPLICATION FOR FLAT ROOF. | | | 4. SEPARATE PERMITS WILL BE REQUIRED FOR SOME ITEMS AS | | | WELL. AWNINGS, TRASH ENCLOSURE, FIRE ALARM, FIRE | | | SPRINKLERS, LOW VOLTAGE, LANDSCAPING, PARKING LOT AND | | | SITE LIGHTING | | | 5. PROVIDE TRUSS ENGINEERING TO BUILDING INSPECTOR | | | REVIEW PRIOR TO INSTALLATION. | | | 6. CONSTRUCTION HOURS - 7AM TO 7PM MON-FRI, 8AM TO 8PM | | | SAT-SUN | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2019-09-18 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2019-09-18 |
Time |
10:37 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2019-09-17 |
Time |
12:41 |
Sent To |
|
|
| Notes |
| 2019-09-18 10:38:04 | BUILDING REVIEW COMMENTS: | | | | | | W.P.B. PERMIT: 19050683 | | | REVIEWED: JULY 19, 2019 | | | 2 ND REVIEW: SEPTEMBER 18, 2019 | | | | | | DYLAN BATTLES | | | BUILDING PLANS EXAMINER PX4191 | | | [email protected] | | | 561-805-6718 | | | | | | FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017) | | | FBC[B] = FBC BUILDING | | | FBC[A] = FBC ACCESSIBILITY | | | FBC[E] = FBC ENERGY CONSERVATION | | | | | | ADDITIONAL COMMENT: | | | IN REVIEWING THE GEOTECHNICAL REPORT IT APPEARS THAT | | | THE RECOMMENDATIONS ARE NOT BEING IMPLEMENTED (SEE PAGE | | | 6 OF 14 IN GEO REPORT). | | | ALSO, SEE CODE REQUIRMENTS FOR DEPTH OF FOOTING. | | | 1809.4 FBC[B] DEPTH AND WIDTH OF FOOTINGS. THE MINIMUM | | | DEPTH OF FOOTINGS BELOW THE UNDISTURBED GROUND SURFACE | | | SHALL BE 12 INCHES. WHERE APPLICABLE, THE REQUIREMENTS | | | OF SECTION. | | | FOOTER IS SHOWN AT 18 DEEP, BUT IT SHOWS ONLY 8 INCHES | | | BELOW GRADE. | | | PLEASE REVIEW FOOTER GRADE DEPTH AND PROVIDE RESPONSE | | | FOR WHAT IS THE DEPTH OF FOOTER INTO GRADE. | | | | | | PROVISOS: | | | - NO RESPONSE REQUIRED. THESE WILL BE ADDED TO THE | | | PLANS AT FINAL STAMPING. | | | | | | 1. PROVIDE PRODUCT APPROVALS FOR WINDOWS, STOREFRONT | | | AND DOORS. | | | 2. ROOF TRUSS SHOP DRAWINGS TO BE PROVIDED TO THE | | | INSPECTOR PRIOR TO INSTALLATION. | | | 3. PROVIDE PRODUCT APPROVALS AND ENGINEERING, IF | | | APPLICABLE, WITH SUB PERMIT APPLICATION FOR FLAT ROOF. | | | 4. SEPARATE PERMITS WILL BE REQUIRED FOR SOME ITEMS AS | | | WELL. AWNINGS, TRASH ENCLOSURE, FIRE ALARM, FIRE | | | SPRINKLERS, LOW VOLTAGE, LANDSCAPING, PARKING LOT AND | | | SITE LIGHTING | | | 5. CONSTRUCTION HOURS - 7AM TO 7PM MON-FRI, 8AM TO 8PM | | | SAT-SUN | | | | | | IF THERE ARE MORE DEFFERED SUBMITTALS THAN LISTED | | | ABOVE, PLEASE PUT IN A RESPONSE AND I WILL ADD THEM TO | | | FINAL LIST. | | | | | | PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F | | | 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME | | | [email protected] | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2019-07-19 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2019-07-19 |
Time |
16:04 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2019-07-18 |
Time |
08:34 |
Sent To |
|
|
| Notes |
| 2019-07-19 16:04:38 | BUILDING REVIEW COMMENTS: | | | | | | W.P.B. PERMIT: 19050683 | | | REVIEWED: JULY 19, 2019 | | | | | | DYLAN BATTLES | | | BUILDING PLANS EXAMINER PX4191 | | | [email protected] | | | 561-805-6718 | | | | | | FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017) | | | FBC[B] = FBC BUILDING | | | FBC[A] = FBC ACCESSIBILITY | | | FBC[E] = FBC ENERGY CONSERVATION | | | | | | 1) 401.2 FBC[CE] | | | THE REQUIREMENTS OF ANSI/ASHRAE/IESNA 90.1, EXCLUDING | | | SECTION 9.4.1.1(G) OF THE STANDARD. | | | -PLEASE ADJUST THE DOOR SECTION TO MEET WHAT IS | | | PROVIDED IN THE PLANS. CURRENTLY THE ENERGY CALCS SHOW | | | SOLID CORE DOORS ON N, E AND S SIDES. | | | PLANS SHOW GLASS DOORS ON THE N AND W SIDES AND | | | MULTIPLE HOLLOW METAL ON THE S SIDE. | | | - ALSO, THE ROOF SECTION STATES METAL ROOF, BUT THE | | | PLANS SHOW WOOD TRUSSES WITH PLYWOOD. COORDINATE THE | | | PLANS WITH THE ENERGY CALCS. | | | | | | 2) SHEET A503 DETAIL 12 SHOWS R-19 BATTS AT THE 1 5/8 | | | METAL FURRING. THAT DOES NOT MATCH THE ENERGY | | | CALCULATION STHAT CALL FOR 6.9 AT THE MASONRY WALLS. | | | ENERGY CALC AT 6.9 SEEMS TO BE THE CORRECT R VALUE. | | | A) PLEASE CO-ORDINATE THE ENERGY CALS AND PLANS. | | | ALSO, THERE IS A BREAK IN THERMAL ENVELOPE BETWEEN THE | | | TOP OF 1 5/8 METAL FURRING AND THE ROOF SUSPENDED R39 | | | BATT INSULATION. PLEASE SHOW ON PLANS HOW THERMAL | | | ENVELOPE IS | | | B) SHOW ON PLANS HOW THERMAL ENVELOPE IS MAINTAINED. | | | | | | 3) PLEASE PROVIDE BASE FLOOD ELEVATION CERTIFICATE FEMA | | | FORM 086-0-33 TO SHOW WHAT PROPOSED BASE ELEVATION IS | | | GOING TO BE. | | | - DUE TO THE PROXIMITY OF THE BUILDING TO AE FLOOD ZONE | | | , A BASE FLOOD ELEVATION CERTIFICATE WILL BE NEEDED TO | | | DOCUMENT THAT THE FINISHED FLOOR ELEVATION MEETS THE | | | BFE 12.7 NAVD PLUS 2 FOOT FREEBOARD ESTABLISHED BY THE | | | CITY OF WEST PALM BEACH. | | | | | | 4) 110.3(A)1.1 FBC[AMENDED] A FOUNDATION/FORM BOARD | | | SURVEY PREPARED AND CERTIFIED BY A REGISTERED SURVEYOR | | | MAY BE REQUIRED, PRIOR TO APPROVAL OF THE SLAB | | | INSPECTION. THE SURVEY SHALL CERTIFY PLACEMENT OF THE | | | BUILDING ON THE SITE, ILLUSTRATE ALL SURROUNDING | | | SETBACK DIMENSIONS AND SHALL BE AVAILABLE AT THE JOB | | | SITE FOR REVIEW BY THE BUILDING INSPECTOR. | | | PROVIDE BASE FLOOD ELEVATION(B.F.E.) IN CERTIFICATE | | | WITH DESIGN FLOOD ELEVATIONS TO INCLUDE ANY MECHANICAL | | | EQUIPMENT AS APPLICABLE. ALL ELEVATION CERTIFICATES | | | CERTIFIED OCTOBER 5, 2017 AND LATER ARE TO UTILIZE | | | NAVD88 AND INCLUDE A CONVERSION TO NGVD29. | | | | | | 5) 602.3 TYPE III CONSTRUCTION. | | | - PLEASE CONVEY THAT THIS CONSTRUCTION TYPE REQUIRES | | | TWO HOUR EXTERIOR WALL AND THE EXECPTION IN NOTE A | | | WOULD APPLY TO REDUSE IT TO ONE HOUR. | | | | | | 6) 401.4 FBC[R] PROVIDE SOIL REPORT TO SHOW BEARING | | | CAPACITY AND FOUNDATION RECOMMENDATIONS. | | | -ADD MULTI PAGE PDF TO SUPPORTING DOCUMENT IN PROJECT | | | DOX. | | | | | | 7) [FBC 107.5][FBC 110.9][FBC R401.3][THE CIVIL PLANS | | | PROVIDED ARE BASED IN NGVD 29. THE CITY OF WEST PALM | | | BEACH HAS BEEN UTILZING NAVD 88. | | | - PLEASE PROVIDE CIVIL PLAN ELEVATIONS IN NAVD, OR | | | PROVIDE CONVERSION SO THAT ELEVATION CERTIFICATE CIVIL | | | PLANS CAN BE COMPARED WITH PROPER CONVENTION. | | | | | | 8) 1803.5.8 FBC[B] COMPACTED FILL MATERIAL. WHERE | | | SHALLOW FOUNDATIONS WILL BEAR ON COMPACTED FILL | | | MATERIAL MORE THAN 12 INCHES (305 MM) IN DEPTH, A | | | GEOTECHNICAL INVESTIGATION SHALL BE CONDUCTED AND SHALL | | | INCLUDE ALL OF THE FOLLOWING: | | | - (SEE 1803.5.8 FOR REQUIREMENTS) | | | | | | 9) 1203.3 UNVENTED ATTIC AND UNVENTED ENCLOSED RAFTER | | | ASSEMBLIES. | | | - IS THE CEILING SPACE VENTED? | | | | | | 10) 5.1.2. WHERE AIR-PERMEABLE INSULATION IS PROVIDED | | | INSIDE THE BUILDING THERMAL ENVELOPE, IT SHALL BE | | | INSTALLED IN ACCORDANCE WITH ITEM 5.1. IN ADDITION TO | | | THE AIR-PERMEABLE INSULATION INSTALLED DIRECTLY BELOW | | | THE STRUCTURAL SHEATHING, RIGID BOARD OR SHEET | | | INSULATION SHALL BE INSTALLED DIRECTLY ABOVE THE | | | STRUCTURAL ROOF SHEATHING IN ACCORDANCE WITH THE R | | | VALUES IN TABLE 1203.3 FOR CONDENSATION CONTROL. | | | - REVIEW THIS SECTION FOR AIR PERMEABLE INSULATION IN | | | REGARDS TO CONDENSATION CONTROL. | | | | | | 11) 107.3.4.1 FBC[AMENDED] DEFERRED SUBMITTALS. FOR THE | | | PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS ARE | | | DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE NOT | | | SUBMITTED AT THE TIME OF THE APPLICATION AND THAT ARE | | | TO BE SUBMITTED TO THE BUILDING OFFICIAL WITHIN A | | | SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL | | | HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE | | | REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE | | | SHALL LIST THE DEFERRED SUBMITTALS ON THE CONSTRUCTION | | | DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL. | | | - PLEASE PROVIDE A LIST OF DEFERRED SUBMITTALS SO THAT | | | I WILL NOT ASK FOR ITEMS THAT WILL BE SUPPLIED AT A | | | LATER DATE, OR INDICATE WHICH PAGE A LIST CAN BE FOUND. | | | SOME ITEMS ON THE LIST MAY INCLUDE: STOREFRONT, DOORS, | | | ROOFING, WOOD TRUSSES. | | | | | | 11A) SEPARATE PERMITS WILL BE REQUIRED FOR SOME ITEMS | | | AS WELL. | | | - AWNINGS, TRASH ENCLOSURE, FIRE ALARM, FIRE | | | SPRINKLERS, LOW VOLTAGE , LANDSCAPING, PARKING LOT AND | | | SITE LIGHTING | | | | | | 12) 107.3.4.1 FBC[AMENDED] PROVIDE PRODUCT APPROVALS | | | FOR WINDOWS, STOREFRONT AND DOORS. | | | - OR PUT IN THE DEFERRED SUBMITTAL LIST. | | | | | | 13) 107.3.4.1 FBC[AMENDED] PROVIDE PRODUCT APPROVALS. | | | PLEASE PROVIDE FOR FLAT ROOF. | | | - OR PUT IN THE DEFERRED SUBMITTAL LIST. | | | | | | NOTES: | | | | | | -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW | | | EACH COMMENT IS BEING ADDRESSED. | | | | | | -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS | | | OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) | | | SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT | | | DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER | | | SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" | | | OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS | | | APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE | | | NEED "VOID", RENDERING THEM NOT USABLE. | | | | | | PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F | | | 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME | | | [email protected] | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2019-09-17 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2019-09-17 |
Time |
14:54 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2019-09-17 |
Time |
08:11 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2019-07-18 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2019-07-18 |
Time |
14:07 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2019-07-18 |
Time |
12:49 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
3 |
Status |
P |
Date |
2019-10-16 |
|
|
Cont ID |
|
| Sent By |
rrossano |
Date |
2019-10-16 |
Time |
|
Rev Time |
0.00 |
| Received By |
rrossano |
Date |
2019-10-16 |
Time |
|
Sent To |
|
|
| Notes |
| 2019-10-16 12:00:35 | REVIEWED UNDER FORMAL ENGINEERING SUBMITTAL E19030032. |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
2 |
Status |
F |
Date |
2019-10-11 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2019-10-11 |
Time |
06:17 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2019-10-11 |
Time |
06:17 |
Sent To |
|
|
| Notes |
| 2019-10-11 06:20:03 | CONTACT ENGINEERING DEPARTMENT DIRECTLY AND SUBMIT | | | APPLICATION IF REQUIRED | | | HTTP://WWW.WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS | | | /FORMS,-PERMITS-APPLICATIONS | | | | | | ENGINEERING APPROVAL REQUIRED PRIOR TO PERMIT ISSUANCE | | | | | | MAIN PHONE: (561) 822-1200 | | | | | | IF YOU HAVE AN ISSUED ENGINEERING PERMIT, OR A PENDING | | | APPLICATION, PLEASE ADVISE VIA EMAIL ([email protected]) | | | |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
F |
Date |
2019-07-18 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2019-07-18 |
Time |
08:08 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2019-07-18 |
Time |
08:08 |
Sent To |
|
|
| Notes |
| 2019-07-18 08:09:21 | FOR ADDRESSING, PLEASE CONTACT (PREFERABLY VIA EMAIL): | | | | | | MICHAEL ORIO | | | GIS SUPPORT SPECIALIST | | | [email protected] | | | CITY OF WEST PALM BEACH | | | INFORMATION TECHNOLOGY DEPARTMENT | | | 401 CLEMATIS STREET, WEST PALM BEACH, FLORIDA 33401 | | | P: 561.494.1080 | | | | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2019-09-04 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2019-09-04 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2019-09-04 |
Time |
10:02 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2019-06-11 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2019-06-11 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2019-06-11 |
Time |
14:23 |
Sent To |
|
|
| Notes |
| 2019-06-11 15:21:40 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | | | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE | | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | | INSPECTION. | | | | | | | | | 1) THERE ARE INDICATION OF A KITCHEN HOOD AND EXHAUST | | | SYSTEM. | | | | | | THIS SYSTEM SHALL BE INSTALLED IN COMPLIANCE WITH NFPA | | | 96 UNDER SEPARATE PERMIT AND SHOP DRAWINGS. | | | | | | | | | 2) A FIRE SUPPRESSION SYSTEM IS REQUIRED FOR THE HOOD | | | SYSTEM. | | | | | | THIS SYSTEM SHALL BE INSTALLED IN COMPLIANCE WITH THE | | | APPLICABLE NFPA STANDARD UNDER SEPARATE PERMIT AND SHOP | | | DRAWINGS. | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
P |
Date |
2019-09-17 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2019-09-17 |
Time |
16:54 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2019-09-16 |
Time |
08:58 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2019-07-18 |
|
|
Cont ID |
|
| Sent By |
jesmith |
Date |
2019-07-18 |
Time |
15:24 |
Rev Time |
0.00 |
| Received By |
jesmith |
Date |
2019-07-18 |
Time |
13:03 |
Sent To |
|
|
| Notes |
| 2019-07-18 15:23:51 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL | | | MANUAL REVISED 2017 | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION | | | FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH | | | EDITION | | | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION | | | FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION | | | NFPA 96= STANDARD FOR VENTILATION CONTROLAND FIRE | | | PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017 | | | FAC= FLORIDA ADMINISTRATIVE CODE | | | FS = FLORIDA STATUTES | | | | | | | | | 1ST REVIEW | | | GAS COMMENTS: DENIED | | | 1. PER WPB FBC 107.2.1, SUBMIT CALCULATIONS FOR | | | COMBUSTION AIR KITCHEN EQUIPMENT PER FBC FG 304.1 | | | 2. P201 | | | A. GAS ISOMETRIC | | | 1) PER WPB FBC 107.2.1, ISOMETRIC DRAWING SHALL CLEARLY | | | SHOW THE LENGTH OF ALL CUT SECTIONS OF PIPE AND CONFIRM | | | THAT SIZING IS IN ACCORDANCE WITH FBC PL 402.4.1, | | | 402.4.2. | | | 2) PROVIDE UNION BETWEEN MANUAL VALVE AND THE AUTOMATIC | | | SHUT OFF VALVE FOR THE EMERGENCY SHUT DOWN TO THE | | | COOKING LINE PER NFPA 96, SECS. 10.4, 10.5. | | | B. NOTE 1: PER WPB FBC 107.2.1, PROVIDE A SPECIFICATION | | | FOR FLEXIBLE GAS CONNECTORS COMPLYING WITH FBC FG | | | 411.1. | | | 3. P301 | | | A. P301 WATER HEATER DETAIL; RESEARCH OF THE CONCENTRIC | | | VENT SEEMS TO INDICATE THAT THIS PRODUCT IS FOR | | | SIDEWALL INSTALLATION ONLY. PER WPB FBC 107.2.1, | | | PROVIDE MANUFACTURER AND MODEL # FOR CONCENTRIC VENT | | | WITH DOCUMENTATION THAT ALLOWS VERTICAL INSTALLATION | | | FOR ROOF PENETRATION AND IS NOT LIMITED TO SIDEWALL | | | INSTALLATION. IF SIDEWALL INSTALLATION IS TO BE USED | | | THEN PROVIDE LOCATION ON BUILDING WALL AND INCLUDE AN | | | ELEVATION DETAIL SHOWING COMPLIANCE WITH FBC FG 502 | | | THROUGH 505. IF THROUGH THE ROOF VENTING IS TO BE USED | | | THEN PROVIDE A DETAIL FOR THAT INSTALLATION SHOWING | | | COMPLIANCE WITH FBC FG 502 THROUGH 505. EITHER DETAIL | | | SHALL SHOW TYPE, LOCATION, SIZE, TERMINATION POINT, | | | HEIGHT ABOVE THE ROOF AND ANCHORING DETAILS OF THE GAS | | | VENT(S) AS ARE APPLICABLE. | | | B. DETAIL 3 SHOWS GAS PIPING ABOVE ROOF. FLOOR PLAN | | | SHOWS PIPING BELOW ROOF ABOVE THE CEILING. PLEASE | | | CLARIFY PER WPB FBC 107.2.1. | | | C. DETAIL 10 SHOWS GAS PIPING TO ABOVE ROOF. FLOOR PLAN | | | SHOWS PIPING BELOW ROOF ABOVE THE CEILING. PLEASE | | | CLARIFY PER WPB FBC 107.2.1. | | | 4. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS / | | | INSTALLATION MANUAL FOR ALL GAS EQUIPMENT INCLUDING THE | | | WATER HEATER TO VERIFY COMPLIANCE WITH STANDARDS NFPA | | | 54, NFPA 58, AND FBC FG SEC. 402.2, AND 301.3. | | | | | | END OF COMMENTS. | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED | | | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. | | | | | | | | | | | | JERALD SMITH | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | EMAIL [email protected] | | | PHONE 561-805-6715 | | | | | | 19050683 1510 BELVEDERE RD | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2019-11-12 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2019-11-12 |
Time |
12:51 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2019-10-30 |
Time |
13:29 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2019-10-15 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2019-10-15 |
Time |
09:25 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2019-08-28 |
Time |
09:07 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2019-07-19 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2019-07-19 |
Time |
16:05 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2019-06-10 |
Time |
13:19 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2019-07-18 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2019-07-18 |
Time |
09:22 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2019-07-18 |
Time |
08:34 |
Sent To |
|
|
| Notes |
| 2019-07-18 09:22:39 | 109 FBC[AMENDED] PLANS WILL BE REVIEWED BY THE PBC | | | IMPACT FEE OFFICE DIGITALLY VIA PROJECTDOX UPON | | | NOTIFICATION BY THIS OFFICE. NOTIFICATION MAY OCCUR | | | WHEN PLANS ARE NEAREST FINAL FORM. YOU MAY COORDINATE | | | WITH THE IMPACT FEE OFFICE AT (561) 233-5025 OR SIMPLY | | | UPLOAD THE MUNICIPAL IMPACT FEE QUESTIONNAIRE FORM TO | | | YOUR PROJECT AND NAME THE FILE MUNICIPAL IMPACT FEE | | | QUESTIONNAIRE. THE FORM CAN BE FOUND AT: HTTP://DISCOVE | | | R.PBCGOV.ORG/PZB/ADMINISTRATION/PDF/IMPACTFEES/FORMS/QU | | | ESTIONNAIRE.PDF UPON APPROVAL AND FEE PAYMENT, PLEASE | | | UPLOAD THE RECEIPT TO YOUR PROJECT OR EMAIL IT TO | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2019-10-11 |
|
|
Cont ID |
|
| Sent By |
cmontell |
Date |
2019-10-11 |
Time |
14:42 |
Rev Time |
0.00 |
| Received By |
cmontell |
Date |
2019-10-11 |
Time |
14:41 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2019-07-19 |
|
|
Cont ID |
|
| Sent By |
cmontell |
Date |
2019-07-19 |
Time |
10:49 |
Rev Time |
0.00 |
| Received By |
cmontell |
Date |
2019-07-19 |
Time |
10:49 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
NFIP |
NFIP REVIEW ACTIVITY |
| Rev No |
2 |
Status |
P |
Date |
2019-10-11 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2019-10-11 |
Time |
10:03 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2019-09-17 |
Time |
12:42 |
Sent To |
|
|
| Notes |
| 2019-10-11 10:19:09 | FLOOD ZONE = AE | | | BFE = 12.7 NAVD 1988 | | | LOWEST FLOOR LEVED DFE = 19 FEET NAVD 1988 (ELEVATION | | | CERTIFICATE PROVIDED) | | | |
|
|
| Review Stop |
NFIP |
NFIP REVIEW ACTIVITY |
| Rev No |
1 |
Status |
F |
Date |
2019-07-19 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2019-07-19 |
Time |
16:03 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2019-07-18 |
Time |
08:34 |
Sent To |
|
|
| Notes |
| 2019-07-19 16:03:41 | SEE BUILDING COMMENTS 3 AND 4. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2019-09-17 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2019-09-17 |
Time |
16:54 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2019-09-16 |
Time |
08:58 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2019-07-18 |
|
|
Cont ID |
|
| Sent By |
jesmith |
Date |
2019-07-18 |
Time |
10:22 |
Rev Time |
0.00 |
| Received By |
jesmith |
Date |
2019-07-16 |
Time |
07:40 |
Sent To |
|
|
| Notes |
| 2019-07-18 10:22:34 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL | | | MANUAL REVISED 2017 | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION | | | FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH | | | EDITION | | | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION | | | FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION | | | NFPA 96= STANDARD FOR VENTILATION CONTROLAND FIRE | | | PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017 | | | FAC= FLORIDA ADMINISTRATIVE CODE | | | FS = FLORIDA STATUTES | | | | | | | | | 1ST REVIEW | | | PLUMBING COMMEMTS: DENIED | | | 1. C-6 PAVING, DRAINAGE AND GRADING PLAN | | | A. PER WPB FBC 107.2.1, COORDINATE WITH PLUMBING PLAN | | | P101, NOTE 8, WHICH INDICATES STORM WATER DISCHARGING | | | TO THE SITE STORM. | | | 2. C-8 UTILITY PLAN | | | A. WATER METER AND BACKFLOW PREVENTER ARE LOCATED | | | OUTSIDE OF THE PROPERTY IN WHAT APPEARS TO BE THE | | | UTILITY EASEMENT. PER WPB CCCM STANDARD DETAIL WS-11, | | | BACKFLOW ASSEMBLY SHALL BE LOCATED DIRECTLY AFTER THE | | | METER ON PRIVATE PROPERTY OUTSIDE OF THE UTILITY | | | EASEMENT. PER WPB FBC 107.2.1, PROVIDE COMPLETE | | | CLARIFICATION OF PRIVATE PROPERTY AND PUBLIC EASEMENT. | | | B. PER WPB FBC 107.2.1, AT THE GREASE INTERCEPTOR | | | LOCATION, ELIMINATE NOTE REFERRING TO PBCWUD STANDARDS | | | AND REPLACE WITH NOTE ?SHALL COMPLY WITH CITY OF WPB | | | UTILITIES DEPT. STANDARD DETAIL GS-7.? | | | C. PER WPB FBC 107.2.1, COORDINATE WITH PLUMBING PLAN | | | P002 WHICH CALLS FOR THREE (3) 1250 GALLON GREASE | | | INTERCEPTORS. | | | 3. REGARDING ALL PBC WUD SHEETS, PLEASE BE ADVISED THAT | | | UTILITIES DETAILS SHEETS SHALL BE SUBMITTED WITH THE | | | ENGINEER OF RECORD SEAL/STAMP AND SIGNATURE (ELECTRONIC | | | CERTIFIED BY A CERTIFICATE AUTHORITY) AND SHALL COMPLY | | | WITH WPB PUBLIC UTILITIES REQUIREMENTS. THE FOLLOWING | | | COMMENTS CONCERNING PBC WUD SHEETS SHALL BE ADDRESSED | | | ON PLANS AS NOTED ABOVE. | | | A. PBC WUD SHEET 1 OF 4 | | | 1) DETAIL 7W: PBCWUD IS NOT THE AUTHORITY HAVING | | | JURISDICTION IN THE CITY OF WEST PALM BEACH. PER WPB | | | FBC 107.2.1, ADD TO NOTE 1 THAT REDUCED PRESSURE | | | BACKFLOW PREVENTER ASSEMBLY SHALL COMPLY WITH WPB CCCM | | | STANDARD DETAIL WS-11. | | | B. PBC WUD SHEET 4 OF 4 (POTABLE WATER DETAILS) | | | 1) DETAIL 33W/42W: WHAT DO THESE DETAILS PERTAIN TO? | | | PER WPB FBC 107.2.1, PLEASE CLARIFY AND SHOW LOCATION | | | ON C-8 UTILITY PLAN. | | | 4. A004 DUMPSTER DETAILS | | | A. A FLOOR DRAIN IS SHOWN. WHAT IS THE PURPOSE OF THIS | | | DRAIN? PLEASE NOTE THAT IF IT DRAINS TO SANITARY, IT | | | WILL ALLOW STORM WATER TO ENTER THE SANITARY WHICH IS | | | PROHIBITED. IF THE DRAIN IS TO REMAIN, PROVIDE DETAILS | | | AND COORDINATE WITH PLUMBING AND CIVIL. CITY OF WPB | | | DOES NOT REQUIRE A FLOOR DRAIN IN THIS STRUCTURE. | | | 5. A402 ACCESSIBILITY STANDARDS | | | A. GRAB BARS SHALL BE 33? TO 36? TO TOP GRIPPING | | | SURFACE OF GRAB BAR, NOT TO CENTERLINE PER FBC ACC | | | 609.3. CORRECT DETAILS 10 AND 5 TO REFLECT THE SAME. | | | B. WATER CLOSET SHALL BE 16?MIN/18? MAX CENTER FROM | | | SIDE WALL PER FBC ACC 604.2. CORRECT DETAIL 10 AND | | | DETAIL 4 TO REFLECT THE SAME. | | | 6. A501: DETAIL 21; 4? PRIMARY DOWNSPOUT IS INCORRECTLY | | | TITLED ?COOLER BASE DETAIL 21?. PER WPB FBC 107.2.1, | | | PLEASE CORRECT TO READ ?PRIMARY DOWNSPOUT SECTION | | | DETAIL 25?. INDICATE ON DETAIL 25 WHETHER OR NOT STORM | | | DISCHARGE IS TO TERMINATE ABOVE GRADE OR CONNECT | | | DIRECTLY TO THE SITE STORM WATER. COORDINATE WITH C-6 | | | PAVING, DRAINAGE AND GRADING PLAN. | | | 7. PLAN SHEET P101 NOTE 13 AND 14: PROVIDE INSULATION | | | OF GREASY WASTE LINES WHICH ARE PROVIDED WITH HEAT | | | TRACE | | | 8. P002 GREASE INTERCEPTOR: REVIEW CITY OF WPB | | | UTILITIES DEPT. STANDARD DETAIL GS-7 AND MODIFY | | | INTERCEPTOR DETAIL AS APPLICABLE. | | | 9. P301 | | | A. DETAIL 15 WATER HEATER; PROVIDE VACUUM RELIEF VALVE | | | (VRV) AT COLD WATER SUPPLY IN LIEU OF ATMOSPHERIC | | | VACUUM BREAKER (AVB) TO CONFORM TO THE VERBAGE OF FBC | | | PL 504.2. | | | B. DETAIL 11 IS NOT APPLICABLE. PLEASE REMOVE PER WPB | | | FBC 107.2.1. | | | 9. P001 | | | A. PLUMBING FIXTURE SCHEDULE CALLS OUT FD (FLOOR DRAIN) | | | IN RESTROOMS WITH TRAP PRIMER. P101 AND P201 DO NOT | | | SHOW FLOOR DRAINS IN THE RESTROOMS. PER WPB FBC | | | 107.2.1, PLEASE CLARIFY. | | | B. PER WPB FBC 107.2.1, PROVIDE DETAIL FOR MIXING | | | VALVES AT HAND SINKS AND LAVATORIES | | | 10. P201, PROVIDE TWO WAY CO DOWNSTREAM OF EACH GREASE | | | INTERCEPTOR TO COMPLY WITH CITY OF WPB UTILITIES DEPT. | | | STANDARD DETAIL GS-7. | | | 11. P202 | | | A. WATER RISER DIAGRAM SEEMS TO INDICATE TRAP PRIMERS | | | FOR ALL FLOOR SINKS AND FLOOR DRAINS. PLEASE INDICATE | | | THE SAME IN P001 PLUMBING SCHEDULE REMARKS. AT A | | | MINIMUM, PER FBC PL 1002.4.1, TRAP SEAL PROTECTION FOR | | | THE ANY FLOOR DRAIN AND FOR THE FLOOR SINK SERVING THE | | | WATER HEATER IN ROOM #116 IS REQUIRED. | | | B. PER WPB FBC 107.2.1, PLEASE IDENTIFY BACKFLOW | | | PREVENTERS ON P202 WATER RISER DIAGRAM | | | C. PROVIDE FULL OPEN VALVES ON ALL DOWN FEED PIPES PER | | | FBC PL 606.1(5). | | | 12. A SEPARATE PERMIT IS REQUIRED FOR THE GREASE | | | INTERCEPTOR(S). | | | 13. A SEPARATE PERMIT IS REQUIRED FOR THE BACKFLOW | | | PREVENTER. | | | 14. P102/NOTE 9 DOES NOT MATCH P103/NOTE 2. PER WPB FBC | | | 107.2.1, CLARIFY AND CORRECT. | | | | | | END OF COMMENTS. | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED | | | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. | | | | | | JERALD SMITH | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | EMAIL [email protected] | | | PHONE 561-805-6715 | | | | | | 19050683 1510 BELVEDERE RD | | | |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
2 |
Status |
N |
Date |
2019-10-11 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2019-10-11 |
Time |
10:21 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2019-10-11 |
Time |
10:21 |
Sent To |
|
|
| Notes |
| 2019-10-11 10:22:09 | ROOFING PRODUCT APPROVALS AND APPLICABLE ENGINEERING TO | | | BE PROVIDED WITH SUB PERMIT APPLICATION. |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2019-07-19 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2019-07-19 |
Time |
16:04 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2019-07-18 |
Time |
08:34 |
Sent To |
|
|
| Notes |
| 2019-07-19 16:05:06 | SEE BUILDING COMMENT #13. |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
P |
Date |
2019-11-12 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2019-11-12 |
Time |
12:51 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2019-11-12 |
Time |
12:51 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
P |
Date |
2019-09-18 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2019-09-18 |
Time |
10:40 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2019-09-18 |
Time |
10:40 |
Sent To |
|
|
| Notes |
| 2019-09-18 10:40:56 | ANY ADDITIONAL SHEETS UPLOADED TO DRAWINGS FOLDER WILL | | | NEED TO BE DIGITALLY SIGNED. |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2019-06-17 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2019-06-17 |
Time |
17:30 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2019-06-17 |
Time |
17:30 |
Sent To |
|
|
| Notes |
| 2019-06-17 17:30:24 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | 1. NONE OF THE PAGES SUBMITTED ARE DIGITALLY SIGNED. | | | PLEASE BE ADVISED THAT YOU MAY PROVIDE ONE PAPER | | | ORIGINAL AFTER ALL REVIEWS HAVE PASSED, BUT THIS WILL | | | CAUSE A DELAY IN PERMIT ISSUANCE AS A SEPARATE | | | SIGNATURE REVIEW WOULD BE REQUIRED AT THAT TIME, FS471, | | | FS481. WE STRONGLY RECOMMEND THAT ALL PAGES BE | | | DIGITALLY SIGNED IN ACCORDANCE WITH FS471, FS481. | | | | | | 2. CIVIL PAGES PREPARED BY CHRISTOPHER A. ROGERS, PE | | | STATE "NOT FOR CONSTRUCTION". PROVIDE FINAL | | | CONSTRUCTION DRAWINGS. | | | | | | 3. ELECTRICAL PAGES PERPARED BY JOEVEN M. VALENZUELA, | | | PE, BEACON CONSULTING ENGINEERS, TITLE BLOCK LACKS THE | | | CERTIFICATE OF AUTHORIZATION (29530), PLEASE REVISE TO | | | INCLUDE. | | | | | | THIS COMMENT APPLIES TO OTHER PAGES PREPARED BY OTHER | | | ENGINEERS IN THE FIRM (PLUMBING, MECHANICAL). | | | | | | 4. STRUCTURAL PAGES PREPARED BY JORGE D. NOVOA, PE, J&C | | | ENGINEERING & INVESTMENTS, TITLE BLOCK LACKS THE | | | CERTIFICATE OF AUTHORIZATION (31389), PLEASE ADD. | | | | | | | | | | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2019-10-15 |
|
|
Cont ID |
|
| Sent By |
llouie |
Date |
2019-10-15 |
Time |
|
Rev Time |
0.00 |
| Received By |
llouie |
Date |
2019-10-15 |
Time |
|
Sent To |
|
|
| Notes |
| 2019-10-15 08:51:42 | SEPARATE PERMITS REQUIRED FOR: LANDSCAPING, SITE | | | LIGHTING AND SIGNAGE. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2019-06-20 |
|
|
Cont ID |
|
| Sent By |
pgreilic |
Date |
2019-06-20 |
Time |
|
Rev Time |
|
| Received By |
llouie |
Date |
2019-06-20 |
Time |
|
Sent To |
|
|
| Notes |
| 2019-06-20 13:08:08 | SEPARATE PERMITS REQUIRED FOR THE FOLLOWING: LANDSCAPE, | | | SIGNAGE AND LIGHTING/PHOTOMETRICS. | | | | | | (REFERENCE: PB 1670I AND RESOLUTION NO. 233-18) |
|
|