Plan Review Details - Permit 19050683
Plan Review Stops For Permit 19050683
Review Stop AD ADDRESSING
Rev No 1 Status N Date 2019-07-18 Cont ID  
Sent By dbattles Date 2019-07-18 Time 09:20 Rev Time 0.00
Received By dbattles Date 2019-07-18 Time 08:34 Sent To  
Notes
2019-07-18 09:21:51ADDRESS PREVIOUSLY ASSIGNED BY MICHEAL ORIO.
 PCN: 74434332020020000 1510 BELVEDERE RD

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2019-11-12 Cont ID  
Sent By dbattles Date 2019-11-12 Time 12:52 Rev Time 0.00
Received By dbattles Date 2019-11-12 Time 12:51 Sent To  
Notes
2019-11-12 12:50:55PROVISOS:
 1. PROVIDE PRODUCT APPROVALS FOR WINDOWS, STOREFRONT
 AND DOORS.
 2. ROOF TRUSS SHOP DRAWINGS TO BE PROVIDED TO THE
 INSPECTOR PRIOR TO INSTALLATION.
 3. PROVIDE PRODUCT APPROVALS AND ENGINEERING, IF
 APPLICABLE, WITH SUB PERMIT APPLICATION FOR FLAT ROOF.
 4. SEPARATE PERMITS WILL BE REQUIRED FOR SOME ITEMS AS
 WELL. AWNINGS, TRASH ENCLOSURE, FIRE ALARM, FIRE
 SPRINKLERS, LOW VOLTAGE, LANDSCAPING, PARKING LOT AND
 SITE LIGHTING
 5. PROVIDE TRUSS ENGINEERING TO BUILDING INSPECTOR
 REVIEW PRIOR TO INSTALLATION.
 6. CONSTRUCTION HOURS - 7AM TO 7PM MON-FRI, 8AM TO 8PM
 SAT-SUN
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-09-18 Cont ID  
Sent By dbattles Date 2019-09-18 Time 10:37 Rev Time 0.00
Received By dbattles Date 2019-09-17 Time 12:41 Sent To  
Notes
2019-09-18 10:38:04BUILDING REVIEW COMMENTS:
  
 W.P.B. PERMIT: 19050683
 REVIEWED: JULY 19, 2019
 2 ND REVIEW: SEPTEMBER 18, 2019
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER PX4191
 [email protected]
 561-805-6718
  
 FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC[B] = FBC BUILDING
 FBC[A] = FBC ACCESSIBILITY
 FBC[E] = FBC ENERGY CONSERVATION
  
 ADDITIONAL COMMENT:
 IN REVIEWING THE GEOTECHNICAL REPORT IT APPEARS THAT
 THE RECOMMENDATIONS ARE NOT BEING IMPLEMENTED (SEE PAGE
 6 OF 14 IN GEO REPORT).
 ALSO, SEE CODE REQUIRMENTS FOR DEPTH OF FOOTING.
 1809.4 FBC[B] DEPTH AND WIDTH OF FOOTINGS. THE MINIMUM
 DEPTH OF FOOTINGS BELOW THE UNDISTURBED GROUND SURFACE
 SHALL BE 12 INCHES. WHERE APPLICABLE, THE REQUIREMENTS
 OF SECTION.
 FOOTER IS SHOWN AT 18 DEEP, BUT IT SHOWS ONLY 8 INCHES
 BELOW GRADE.
 PLEASE REVIEW FOOTER GRADE DEPTH AND PROVIDE RESPONSE
 FOR WHAT IS THE DEPTH OF FOOTER INTO GRADE.
  
 PROVISOS:
 - NO RESPONSE REQUIRED. THESE WILL BE ADDED TO THE
 PLANS AT FINAL STAMPING.
  
 1. PROVIDE PRODUCT APPROVALS FOR WINDOWS, STOREFRONT
 AND DOORS.
 2. ROOF TRUSS SHOP DRAWINGS TO BE PROVIDED TO THE
 INSPECTOR PRIOR TO INSTALLATION.
 3. PROVIDE PRODUCT APPROVALS AND ENGINEERING, IF
 APPLICABLE, WITH SUB PERMIT APPLICATION FOR FLAT ROOF.
 4. SEPARATE PERMITS WILL BE REQUIRED FOR SOME ITEMS AS
 WELL. AWNINGS, TRASH ENCLOSURE, FIRE ALARM, FIRE
 SPRINKLERS, LOW VOLTAGE, LANDSCAPING, PARKING LOT AND
 SITE LIGHTING
 5. CONSTRUCTION HOURS - 7AM TO 7PM MON-FRI, 8AM TO 8PM
 SAT-SUN
  
 IF THERE ARE MORE DEFFERED SUBMITTALS THAN LISTED
 ABOVE, PLEASE PUT IN A RESPONSE AND I WILL ADD THEM TO
 FINAL LIST.
  
 PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F
 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME
 [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-07-19 Cont ID  
Sent By dbattles Date 2019-07-19 Time 16:04 Rev Time 0.00
Received By dbattles Date 2019-07-18 Time 08:34 Sent To  
Notes
2019-07-19 16:04:38BUILDING REVIEW COMMENTS:
  
 W.P.B. PERMIT: 19050683
 REVIEWED: JULY 19, 2019
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER PX4191
 [email protected]
 561-805-6718
  
 FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC[B] = FBC BUILDING
 FBC[A] = FBC ACCESSIBILITY
 FBC[E] = FBC ENERGY CONSERVATION
  
 1) 401.2 FBC[CE]
 THE REQUIREMENTS OF ANSI/ASHRAE/IESNA 90.1, EXCLUDING
 SECTION 9.4.1.1(G) OF THE STANDARD.
 -PLEASE ADJUST THE DOOR SECTION TO MEET WHAT IS
 PROVIDED IN THE PLANS. CURRENTLY THE ENERGY CALCS SHOW
 SOLID CORE DOORS ON N, E AND S SIDES.
 PLANS SHOW GLASS DOORS ON THE N AND W SIDES AND
 MULTIPLE HOLLOW METAL ON THE S SIDE.
 - ALSO, THE ROOF SECTION STATES METAL ROOF, BUT THE
 PLANS SHOW WOOD TRUSSES WITH PLYWOOD. COORDINATE THE
 PLANS WITH THE ENERGY CALCS.
  
 2) SHEET A503 DETAIL 12 SHOWS R-19 BATTS AT THE 1 5/8
 METAL FURRING. THAT DOES NOT MATCH THE ENERGY
 CALCULATION STHAT CALL FOR 6.9 AT THE MASONRY WALLS.
 ENERGY CALC AT 6.9 SEEMS TO BE THE CORRECT R VALUE.
 A) PLEASE CO-ORDINATE THE ENERGY CALS AND PLANS.
 ALSO, THERE IS A BREAK IN THERMAL ENVELOPE BETWEEN THE
 TOP OF 1 5/8 METAL FURRING AND THE ROOF SUSPENDED R39
 BATT INSULATION. PLEASE SHOW ON PLANS HOW THERMAL
 ENVELOPE IS
 B) SHOW ON PLANS HOW THERMAL ENVELOPE IS MAINTAINED.
  
 3) PLEASE PROVIDE BASE FLOOD ELEVATION CERTIFICATE FEMA
 FORM 086-0-33 TO SHOW WHAT PROPOSED BASE ELEVATION IS
 GOING TO BE.
 - DUE TO THE PROXIMITY OF THE BUILDING TO AE FLOOD ZONE
 , A BASE FLOOD ELEVATION CERTIFICATE WILL BE NEEDED TO
 DOCUMENT THAT THE FINISHED FLOOR ELEVATION MEETS THE
 BFE 12.7 NAVD PLUS 2 FOOT FREEBOARD ESTABLISHED BY THE
 CITY OF WEST PALM BEACH.
  
 4) 110.3(A)1.1 FBC[AMENDED] A FOUNDATION/FORM BOARD
 SURVEY PREPARED AND CERTIFIED BY A REGISTERED SURVEYOR
 MAY BE REQUIRED, PRIOR TO APPROVAL OF THE SLAB
 INSPECTION. THE SURVEY SHALL CERTIFY PLACEMENT OF THE
 BUILDING ON THE SITE, ILLUSTRATE ALL SURROUNDING
 SETBACK DIMENSIONS AND SHALL BE AVAILABLE AT THE JOB
 SITE FOR REVIEW BY THE BUILDING INSPECTOR.
 PROVIDE BASE FLOOD ELEVATION(B.F.E.) IN CERTIFICATE
 WITH DESIGN FLOOD ELEVATIONS TO INCLUDE ANY MECHANICAL
 EQUIPMENT AS APPLICABLE. ALL ELEVATION CERTIFICATES
 CERTIFIED OCTOBER 5, 2017 AND LATER ARE TO UTILIZE
 NAVD88 AND INCLUDE A CONVERSION TO NGVD29.
  
 5) 602.3 TYPE III CONSTRUCTION.
 - PLEASE CONVEY THAT THIS CONSTRUCTION TYPE REQUIRES
 TWO HOUR EXTERIOR WALL AND THE EXECPTION IN NOTE A
 WOULD APPLY TO REDUSE IT TO ONE HOUR.
  
 6) 401.4 FBC[R] PROVIDE SOIL REPORT TO SHOW BEARING
 CAPACITY AND FOUNDATION RECOMMENDATIONS.
 -ADD MULTI PAGE PDF TO SUPPORTING DOCUMENT IN PROJECT
 DOX.
  
 7) [FBC 107.5][FBC 110.9][FBC R401.3][THE CIVIL PLANS
 PROVIDED ARE BASED IN NGVD 29. THE CITY OF WEST PALM
 BEACH HAS BEEN UTILZING NAVD 88.
 - PLEASE PROVIDE CIVIL PLAN ELEVATIONS IN NAVD, OR
 PROVIDE CONVERSION SO THAT ELEVATION CERTIFICATE CIVIL
 PLANS CAN BE COMPARED WITH PROPER CONVENTION.
  
 8) 1803.5.8 FBC[B] COMPACTED FILL MATERIAL. WHERE
 SHALLOW FOUNDATIONS WILL BEAR ON COMPACTED FILL
 MATERIAL MORE THAN 12 INCHES (305 MM) IN DEPTH, A
 GEOTECHNICAL INVESTIGATION SHALL BE CONDUCTED AND SHALL
 INCLUDE ALL OF THE FOLLOWING:
 - (SEE 1803.5.8 FOR REQUIREMENTS)
  
 9) 1203.3 UNVENTED ATTIC AND UNVENTED ENCLOSED RAFTER
 ASSEMBLIES.
 - IS THE CEILING SPACE VENTED?
  
 10) 5.1.2. WHERE AIR-PERMEABLE INSULATION IS PROVIDED
 INSIDE THE BUILDING THERMAL ENVELOPE, IT SHALL BE
 INSTALLED IN ACCORDANCE WITH ITEM 5.1. IN ADDITION TO
 THE AIR-PERMEABLE INSULATION INSTALLED DIRECTLY BELOW
 THE STRUCTURAL SHEATHING, RIGID BOARD OR SHEET
 INSULATION SHALL BE INSTALLED DIRECTLY ABOVE THE
 STRUCTURAL ROOF SHEATHING IN ACCORDANCE WITH THE R
 VALUES IN TABLE 1203.3 FOR CONDENSATION CONTROL.
 - REVIEW THIS SECTION FOR AIR PERMEABLE INSULATION IN
 REGARDS TO CONDENSATION CONTROL.
  
 11) 107.3.4.1 FBC[AMENDED] DEFERRED SUBMITTALS. FOR THE
 PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS ARE
 DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE NOT
 SUBMITTED AT THE TIME OF THE APPLICATION AND THAT ARE
 TO BE SUBMITTED TO THE BUILDING OFFICIAL WITHIN A
 SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL
 HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 SHALL LIST THE DEFERRED SUBMITTALS ON THE CONSTRUCTION
 DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL.
 - PLEASE PROVIDE A LIST OF DEFERRED SUBMITTALS SO THAT
 I WILL NOT ASK FOR ITEMS THAT WILL BE SUPPLIED AT A
 LATER DATE, OR INDICATE WHICH PAGE A LIST CAN BE FOUND.
 SOME ITEMS ON THE LIST MAY INCLUDE: STOREFRONT, DOORS,
 ROOFING, WOOD TRUSSES.
  
 11A) SEPARATE PERMITS WILL BE REQUIRED FOR SOME ITEMS
 AS WELL.
 - AWNINGS, TRASH ENCLOSURE, FIRE ALARM, FIRE
 SPRINKLERS, LOW VOLTAGE , LANDSCAPING, PARKING LOT AND
 SITE LIGHTING
  
 12) 107.3.4.1 FBC[AMENDED] PROVIDE PRODUCT APPROVALS
 FOR WINDOWS, STOREFRONT AND DOORS.
 - OR PUT IN THE DEFERRED SUBMITTAL LIST.
  
 13) 107.3.4.1 FBC[AMENDED] PROVIDE PRODUCT APPROVALS.
 PLEASE PROVIDE FOR FLAT ROOF.
 - OR PUT IN THE DEFERRED SUBMITTAL LIST.
  
 NOTES:
  
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
  
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  
 PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F
 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME
 [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-09-17 Cont ID  
Sent By jleahy Date 2019-09-17 Time 14:54 Rev Time 0.00
Received By jleahy Date 2019-09-17 Time 08:11 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2019-07-18 Cont ID  
Sent By jleahy Date 2019-07-18 Time 14:07 Rev Time 0.00
Received By jleahy Date 2019-07-18 Time 12:49 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2019-10-16 Cont ID  
Sent By rrossano Date 2019-10-16 Time   Rev Time 0.00
Received By rrossano Date 2019-10-16 Time   Sent To  
Notes
2019-10-16 12:00:35REVIEWED UNDER FORMAL ENGINEERING SUBMITTAL E19030032.

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2019-10-11 Cont ID  
Sent By shill Date 2019-10-11 Time 06:17 Rev Time 0.00
Received By shill Date 2019-10-11 Time 06:17 Sent To  
Notes
2019-10-11 06:20:03CONTACT ENGINEERING DEPARTMENT DIRECTLY AND SUBMIT
 APPLICATION IF REQUIRED
 HTTP://WWW.WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS
 /FORMS,-PERMITS-APPLICATIONS
  
 ENGINEERING APPROVAL REQUIRED PRIOR TO PERMIT ISSUANCE
  
 MAIN PHONE: (561) 822-1200
  
 IF YOU HAVE AN ISSUED ENGINEERING PERMIT, OR A PENDING
 APPLICATION, PLEASE ADVISE VIA EMAIL ([email protected])
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2019-07-18 Cont ID  
Sent By shill Date 2019-07-18 Time 08:08 Rev Time 0.00
Received By shill Date 2019-07-18 Time 08:08 Sent To  
Notes
2019-07-18 08:09:21FOR ADDRESSING, PLEASE CONTACT (PREFERABLY VIA EMAIL):
  
 MICHAEL ORIO
 GIS SUPPORT SPECIALIST
 [email protected]
 CITY OF WEST PALM BEACH
 INFORMATION TECHNOLOGY DEPARTMENT
 401 CLEMATIS STREET, WEST PALM BEACH, FLORIDA 33401
 P: 561.494.1080
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-09-04 Cont ID  
Sent By pleduc Date 2019-09-04 Time   Rev Time 0.00
Received By pleduc Date 2019-09-04 Time 10:02 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2019-06-11 Cont ID  
Sent By pleduc Date 2019-06-11 Time   Rev Time 0.00
Received By pleduc Date 2019-06-11 Time 14:23 Sent To  
Notes
2019-06-11 15:21:40THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) THERE ARE INDICATION OF A KITCHEN HOOD AND EXHAUST
 SYSTEM.
  
 THIS SYSTEM SHALL BE INSTALLED IN COMPLIANCE WITH NFPA
 96 UNDER SEPARATE PERMIT AND SHOP DRAWINGS.
  
  
 2) A FIRE SUPPRESSION SYSTEM IS REQUIRED FOR THE HOOD
 SYSTEM.
  
 THIS SYSTEM SHALL BE INSTALLED IN COMPLIANCE WITH THE
 APPLICABLE NFPA STANDARD UNDER SEPARATE PERMIT AND SHOP
 DRAWINGS.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2019-09-17 Cont ID  
Sent By gjohnson Date 2019-09-17 Time 16:54 Rev Time 0.00
Received By gjohnson Date 2019-09-16 Time 08:58 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2019-07-18 Cont ID  
Sent By jesmith Date 2019-07-18 Time 15:24 Rev Time 0.00
Received By jesmith Date 2019-07-18 Time 13:03 Sent To  
Notes
2019-07-18 15:23:51CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 NFPA 96= STANDARD FOR VENTILATION CONTROLAND FIRE
 PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
  
 1ST REVIEW
 GAS COMMENTS: DENIED
 1. PER WPB FBC 107.2.1, SUBMIT CALCULATIONS FOR
 COMBUSTION AIR KITCHEN EQUIPMENT PER FBC FG 304.1
 2. P201
 A. GAS ISOMETRIC
 1) PER WPB FBC 107.2.1, ISOMETRIC DRAWING SHALL CLEARLY
 SHOW THE LENGTH OF ALL CUT SECTIONS OF PIPE AND CONFIRM
 THAT SIZING IS IN ACCORDANCE WITH FBC PL 402.4.1,
 402.4.2.
 2) PROVIDE UNION BETWEEN MANUAL VALVE AND THE AUTOMATIC
 SHUT OFF VALVE FOR THE EMERGENCY SHUT DOWN TO THE
 COOKING LINE PER NFPA 96, SECS. 10.4, 10.5.
 B. NOTE 1: PER WPB FBC 107.2.1, PROVIDE A SPECIFICATION
 FOR FLEXIBLE GAS CONNECTORS COMPLYING WITH FBC FG
 411.1.
 3. P301
 A. P301 WATER HEATER DETAIL; RESEARCH OF THE CONCENTRIC
 VENT SEEMS TO INDICATE THAT THIS PRODUCT IS FOR
 SIDEWALL INSTALLATION ONLY. PER WPB FBC 107.2.1,
 PROVIDE MANUFACTURER AND MODEL # FOR CONCENTRIC VENT
 WITH DOCUMENTATION THAT ALLOWS VERTICAL INSTALLATION
 FOR ROOF PENETRATION AND IS NOT LIMITED TO SIDEWALL
 INSTALLATION. IF SIDEWALL INSTALLATION IS TO BE USED
 THEN PROVIDE LOCATION ON BUILDING WALL AND INCLUDE AN
 ELEVATION DETAIL SHOWING COMPLIANCE WITH FBC FG 502
 THROUGH 505. IF THROUGH THE ROOF VENTING IS TO BE USED
 THEN PROVIDE A DETAIL FOR THAT INSTALLATION SHOWING
 COMPLIANCE WITH FBC FG 502 THROUGH 505. EITHER DETAIL
 SHALL SHOW TYPE, LOCATION, SIZE, TERMINATION POINT,
 HEIGHT ABOVE THE ROOF AND ANCHORING DETAILS OF THE GAS
 VENT(S) AS ARE APPLICABLE.
 B. DETAIL 3 SHOWS GAS PIPING ABOVE ROOF. FLOOR PLAN
 SHOWS PIPING BELOW ROOF ABOVE THE CEILING. PLEASE
 CLARIFY PER WPB FBC 107.2.1.
 C. DETAIL 10 SHOWS GAS PIPING TO ABOVE ROOF. FLOOR PLAN
 SHOWS PIPING BELOW ROOF ABOVE THE CEILING. PLEASE
 CLARIFY PER WPB FBC 107.2.1.
 4. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR ALL GAS EQUIPMENT INCLUDING THE
 WATER HEATER TO VERIFY COMPLIANCE WITH STANDARDS NFPA
 54, NFPA 58, AND FBC FG SEC. 402.2, AND 301.3.
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  
 19050683 1510 BELVEDERE RD
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-11-12 Cont ID  
Sent By dbattles Date 2019-11-12 Time 12:51 Rev Time 0.00
Received By dbattles Date 2019-10-30 Time 13:29 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-10-15 Cont ID  
Sent By lmarchan Date 2019-10-15 Time 09:25 Rev Time 0.00
Received By lmarchan Date 2019-08-28 Time 09:07 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-07-19 Cont ID  
Sent By dbattles Date 2019-07-19 Time 16:05 Rev Time 0.00
Received By dbattles Date 2019-06-10 Time 13:19 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2019-07-18 Cont ID  
Sent By dbattles Date 2019-07-18 Time 09:22 Rev Time 0.00
Received By dbattles Date 2019-07-18 Time 08:34 Sent To  
Notes
2019-07-18 09:22:39109 FBC[AMENDED] PLANS WILL BE REVIEWED BY THE PBC
 IMPACT FEE OFFICE DIGITALLY VIA PROJECTDOX UPON
 NOTIFICATION BY THIS OFFICE. NOTIFICATION MAY OCCUR
 WHEN PLANS ARE NEAREST FINAL FORM. YOU MAY COORDINATE
 WITH THE IMPACT FEE OFFICE AT (561) 233-5025 OR SIMPLY
 UPLOAD THE MUNICIPAL IMPACT FEE QUESTIONNAIRE FORM TO
 YOUR PROJECT AND NAME THE FILE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE. THE FORM CAN BE FOUND AT: HTTP://DISCOVE
 R.PBCGOV.ORG/PZB/ADMINISTRATION/PDF/IMPACTFEES/FORMS/QU
 ESTIONNAIRE.PDF UPON APPROVAL AND FEE PAYMENT, PLEASE
 UPLOAD THE RECEIPT TO YOUR PROJECT OR EMAIL IT TO
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2019-10-11 Cont ID  
Sent By cmontell Date 2019-10-11 Time 14:42 Rev Time 0.00
Received By cmontell Date 2019-10-11 Time 14:41 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2019-07-19 Cont ID  
Sent By cmontell Date 2019-07-19 Time 10:49 Rev Time 0.00
Received By cmontell Date 2019-07-19 Time 10:49 Sent To  
Notes
***NONE***

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 2 Status P Date 2019-10-11 Cont ID  
Sent By dbattles Date 2019-10-11 Time 10:03 Rev Time 0.00
Received By dbattles Date 2019-09-17 Time 12:42 Sent To  
Notes
2019-10-11 10:19:09FLOOD ZONE = AE
 BFE = 12.7 NAVD 1988
 LOWEST FLOOR LEVED DFE = 19 FEET NAVD 1988 (ELEVATION
 CERTIFICATE PROVIDED)
  

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 1 Status F Date 2019-07-19 Cont ID  
Sent By dbattles Date 2019-07-19 Time 16:03 Rev Time 0.00
Received By dbattles Date 2019-07-18 Time 08:34 Sent To  
Notes
2019-07-19 16:03:41SEE BUILDING COMMENTS 3 AND 4.

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-09-17 Cont ID  
Sent By gjohnson Date 2019-09-17 Time 16:54 Rev Time 0.00
Received By gjohnson Date 2019-09-16 Time 08:58 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-07-18 Cont ID  
Sent By jesmith Date 2019-07-18 Time 10:22 Rev Time 0.00
Received By jesmith Date 2019-07-16 Time 07:40 Sent To  
Notes
2019-07-18 10:22:34CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 NFPA 96= STANDARD FOR VENTILATION CONTROLAND FIRE
 PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
  
 1ST REVIEW
 PLUMBING COMMEMTS: DENIED
 1. C-6 PAVING, DRAINAGE AND GRADING PLAN
 A. PER WPB FBC 107.2.1, COORDINATE WITH PLUMBING PLAN
 P101, NOTE 8, WHICH INDICATES STORM WATER DISCHARGING
 TO THE SITE STORM.
 2. C-8 UTILITY PLAN
 A. WATER METER AND BACKFLOW PREVENTER ARE LOCATED
 OUTSIDE OF THE PROPERTY IN WHAT APPEARS TO BE THE
 UTILITY EASEMENT. PER WPB CCCM STANDARD DETAIL WS-11,
 BACKFLOW ASSEMBLY SHALL BE LOCATED DIRECTLY AFTER THE
 METER ON PRIVATE PROPERTY OUTSIDE OF THE UTILITY
 EASEMENT. PER WPB FBC 107.2.1, PROVIDE COMPLETE
 CLARIFICATION OF PRIVATE PROPERTY AND PUBLIC EASEMENT.
 B. PER WPB FBC 107.2.1, AT THE GREASE INTERCEPTOR
 LOCATION, ELIMINATE NOTE REFERRING TO PBCWUD STANDARDS
 AND REPLACE WITH NOTE ?SHALL COMPLY WITH CITY OF WPB
 UTILITIES DEPT. STANDARD DETAIL GS-7.?
 C. PER WPB FBC 107.2.1, COORDINATE WITH PLUMBING PLAN
 P002 WHICH CALLS FOR THREE (3) 1250 GALLON GREASE
 INTERCEPTORS.
 3. REGARDING ALL PBC WUD SHEETS, PLEASE BE ADVISED THAT
 UTILITIES DETAILS SHEETS SHALL BE SUBMITTED WITH THE
 ENGINEER OF RECORD SEAL/STAMP AND SIGNATURE (ELECTRONIC
 CERTIFIED BY A CERTIFICATE AUTHORITY) AND SHALL COMPLY
 WITH WPB PUBLIC UTILITIES REQUIREMENTS. THE FOLLOWING
 COMMENTS CONCERNING PBC WUD SHEETS SHALL BE ADDRESSED
 ON PLANS AS NOTED ABOVE.
 A. PBC WUD SHEET 1 OF 4
 1) DETAIL 7W: PBCWUD IS NOT THE AUTHORITY HAVING
 JURISDICTION IN THE CITY OF WEST PALM BEACH. PER WPB
 FBC 107.2.1, ADD TO NOTE 1 THAT REDUCED PRESSURE
 BACKFLOW PREVENTER ASSEMBLY SHALL COMPLY WITH WPB CCCM
 STANDARD DETAIL WS-11.
 B. PBC WUD SHEET 4 OF 4 (POTABLE WATER DETAILS)
 1) DETAIL 33W/42W: WHAT DO THESE DETAILS PERTAIN TO?
 PER WPB FBC 107.2.1, PLEASE CLARIFY AND SHOW LOCATION
 ON C-8 UTILITY PLAN.
 4. A004 DUMPSTER DETAILS
 A. A FLOOR DRAIN IS SHOWN. WHAT IS THE PURPOSE OF THIS
 DRAIN? PLEASE NOTE THAT IF IT DRAINS TO SANITARY, IT
 WILL ALLOW STORM WATER TO ENTER THE SANITARY WHICH IS
 PROHIBITED. IF THE DRAIN IS TO REMAIN, PROVIDE DETAILS
 AND COORDINATE WITH PLUMBING AND CIVIL. CITY OF WPB
 DOES NOT REQUIRE A FLOOR DRAIN IN THIS STRUCTURE.
 5. A402 ACCESSIBILITY STANDARDS
 A. GRAB BARS SHALL BE 33? TO 36? TO TOP GRIPPING
 SURFACE OF GRAB BAR, NOT TO CENTERLINE PER FBC ACC
 609.3. CORRECT DETAILS 10 AND 5 TO REFLECT THE SAME.
 B. WATER CLOSET SHALL BE 16?MIN/18? MAX CENTER FROM
 SIDE WALL PER FBC ACC 604.2. CORRECT DETAIL 10 AND
 DETAIL 4 TO REFLECT THE SAME.
 6. A501: DETAIL 21; 4? PRIMARY DOWNSPOUT IS INCORRECTLY
 TITLED ?COOLER BASE DETAIL 21?. PER WPB FBC 107.2.1,
 PLEASE CORRECT TO READ ?PRIMARY DOWNSPOUT SECTION
 DETAIL 25?. INDICATE ON DETAIL 25 WHETHER OR NOT STORM
 DISCHARGE IS TO TERMINATE ABOVE GRADE OR CONNECT
 DIRECTLY TO THE SITE STORM WATER. COORDINATE WITH C-6
 PAVING, DRAINAGE AND GRADING PLAN.
 7. PLAN SHEET P101 NOTE 13 AND 14: PROVIDE INSULATION
 OF GREASY WASTE LINES WHICH ARE PROVIDED WITH HEAT
 TRACE
 8. P002 GREASE INTERCEPTOR: REVIEW CITY OF WPB
 UTILITIES DEPT. STANDARD DETAIL GS-7 AND MODIFY
 INTERCEPTOR DETAIL AS APPLICABLE.
 9. P301
 A. DETAIL 15 WATER HEATER; PROVIDE VACUUM RELIEF VALVE
 (VRV) AT COLD WATER SUPPLY IN LIEU OF ATMOSPHERIC
 VACUUM BREAKER (AVB) TO CONFORM TO THE VERBAGE OF FBC
 PL 504.2.
 B. DETAIL 11 IS NOT APPLICABLE. PLEASE REMOVE PER WPB
 FBC 107.2.1.
 9. P001
 A. PLUMBING FIXTURE SCHEDULE CALLS OUT FD (FLOOR DRAIN)
 IN RESTROOMS WITH TRAP PRIMER. P101 AND P201 DO NOT
 SHOW FLOOR DRAINS IN THE RESTROOMS. PER WPB FBC
 107.2.1, PLEASE CLARIFY.
 B. PER WPB FBC 107.2.1, PROVIDE DETAIL FOR MIXING
 VALVES AT HAND SINKS AND LAVATORIES
 10. P201, PROVIDE TWO WAY CO DOWNSTREAM OF EACH GREASE
 INTERCEPTOR TO COMPLY WITH CITY OF WPB UTILITIES DEPT.
 STANDARD DETAIL GS-7.
 11. P202
 A. WATER RISER DIAGRAM SEEMS TO INDICATE TRAP PRIMERS
 FOR ALL FLOOR SINKS AND FLOOR DRAINS. PLEASE INDICATE
 THE SAME IN P001 PLUMBING SCHEDULE REMARKS. AT A
 MINIMUM, PER FBC PL 1002.4.1, TRAP SEAL PROTECTION FOR
 THE ANY FLOOR DRAIN AND FOR THE FLOOR SINK SERVING THE
 WATER HEATER IN ROOM #116 IS REQUIRED.
 B. PER WPB FBC 107.2.1, PLEASE IDENTIFY BACKFLOW
 PREVENTERS ON P202 WATER RISER DIAGRAM
 C. PROVIDE FULL OPEN VALVES ON ALL DOWN FEED PIPES PER
 FBC PL 606.1(5).
 12. A SEPARATE PERMIT IS REQUIRED FOR THE GREASE
 INTERCEPTOR(S).
 13. A SEPARATE PERMIT IS REQUIRED FOR THE BACKFLOW
 PREVENTER.
 14. P102/NOTE 9 DOES NOT MATCH P103/NOTE 2. PER WPB FBC
 107.2.1, CLARIFY AND CORRECT.
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  
 19050683 1510 BELVEDERE RD
  

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status N Date 2019-10-11 Cont ID  
Sent By dbattles Date 2019-10-11 Time 10:21 Rev Time 0.00
Received By dbattles Date 2019-10-11 Time 10:21 Sent To  
Notes
2019-10-11 10:22:09ROOFING PRODUCT APPROVALS AND APPLICABLE ENGINEERING TO
 BE PROVIDED WITH SUB PERMIT APPLICATION.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2019-07-19 Cont ID  
Sent By dbattles Date 2019-07-19 Time 16:04 Rev Time 0.00
Received By dbattles Date 2019-07-18 Time 08:34 Sent To  
Notes
2019-07-19 16:05:06SEE BUILDING COMMENT #13.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2019-11-12 Cont ID  
Sent By dbattles Date 2019-11-12 Time 12:51 Rev Time 0.00
Received By dbattles Date 2019-11-12 Time 12:51 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2019-09-18 Cont ID  
Sent By dbattles Date 2019-09-18 Time 10:40 Rev Time 0.00
Received By dbattles Date 2019-09-18 Time 10:40 Sent To  
Notes
2019-09-18 10:40:56ANY ADDITIONAL SHEETS UPLOADED TO DRAWINGS FOLDER WILL
 NEED TO BE DIGITALLY SIGNED.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2019-06-17 Cont ID  
Sent By shill Date 2019-06-17 Time 17:30 Rev Time 0.00
Received By shill Date 2019-06-17 Time 17:30 Sent To  
Notes
2019-06-17 17:30:24****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. NONE OF THE PAGES SUBMITTED ARE DIGITALLY SIGNED.
 PLEASE BE ADVISED THAT YOU MAY PROVIDE ONE PAPER
 ORIGINAL AFTER ALL REVIEWS HAVE PASSED, BUT THIS WILL
 CAUSE A DELAY IN PERMIT ISSUANCE AS A SEPARATE
 SIGNATURE REVIEW WOULD BE REQUIRED AT THAT TIME, FS471,
 FS481. WE STRONGLY RECOMMEND THAT ALL PAGES BE
 DIGITALLY SIGNED IN ACCORDANCE WITH FS471, FS481.
  
 2. CIVIL PAGES PREPARED BY CHRISTOPHER A. ROGERS, PE
 STATE "NOT FOR CONSTRUCTION". PROVIDE FINAL
 CONSTRUCTION DRAWINGS.
  
 3. ELECTRICAL PAGES PERPARED BY JOEVEN M. VALENZUELA,
 PE, BEACON CONSULTING ENGINEERS, TITLE BLOCK LACKS THE
 CERTIFICATE OF AUTHORIZATION (29530), PLEASE REVISE TO
 INCLUDE.
  
 THIS COMMENT APPLIES TO OTHER PAGES PREPARED BY OTHER
 ENGINEERS IN THE FIRM (PLUMBING, MECHANICAL).
  
 4. STRUCTURAL PAGES PREPARED BY JORGE D. NOVOA, PE, J&C
 ENGINEERING & INVESTMENTS, TITLE BLOCK LACKS THE
 CERTIFICATE OF AUTHORIZATION (31389), PLEASE ADD.
  
  
  
  

Review Stop Z ZONING
Rev No 2 Status P Date 2019-10-15 Cont ID  
Sent By llouie Date 2019-10-15 Time   Rev Time 0.00
Received By llouie Date 2019-10-15 Time   Sent To  
Notes
2019-10-15 08:51:42SEPARATE PERMITS REQUIRED FOR: LANDSCAPING, SITE
 LIGHTING AND SIGNAGE.

Review Stop Z ZONING
Rev No 1 Status P Date 2019-06-20 Cont ID  
Sent By pgreilic Date 2019-06-20 Time   Rev Time  
Received By llouie Date 2019-06-20 Time   Sent To  
Notes
2019-06-20 13:08:08SEPARATE PERMITS REQUIRED FOR THE FOLLOWING: LANDSCAPE,
 SIGNAGE AND LIGHTING/PHOTOMETRICS.
  
 (REFERENCE: PB 1670I AND RESOLUTION NO. 233-18)