Plan Review Details - Permit 19050681
Plan Review Stops For Permit 19050681
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-05-31 Cont ID  
Sent By shill Date 2019-05-31 Time 12:08 Rev Time 0.00
Received By shill Date 2019-05-31 Time 12:08 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2019-05-21 Cont ID  
Sent By shill Date 2019-05-21 Time 11:51 Rev Time 0.00
Received By shill Date 2019-05-21 Time 11:10 Sent To  
Notes
2019-05-21 11:10:15****PROVISOS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. PRODUCT APPROVALS REVIEWED BY DESIGNER OF RECORD ARE
 TO BE SUBMITTED TO THE BUILDING DIVISION, REVIEWED AND
 ISSUED PRIOR TO INSTALLATION.
  
 2. A SEPARATE ROOF PERMIT IS REQUIRED. SUBMIT
 APPLICATION WITH ROOF PRODUCT APPROVAL AND ENGINEERING
 IF APPLICABLE. PRODUCT APPROVAL IS TO BE REVIEWED BY
 DESIGNER OF RECORD PRIOR TO SUBMITTAL.
  
 3. CANOPY ENGINEERING IS TO BE REVIED BY STRUCTURAL
 ENGINEER OF RECORD AND SUBITTED TO THE BUILDING
 DIVISION, REVIEWED AND ISSUED PRIOR TO INSTALLATION.
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-05-29 Cont ID  
Sent By jpearson Date 2019-05-29 Time 07:23 Rev Time 0.00
Received By jpearson Date 2019-05-29 Time 07:23 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-05-24 Cont ID  
Sent By jpearson Date 2019-05-24 Time 07:12 Rev Time 0.00
Received By jpearson Date 2019-05-24 Time 07:03 Sent To I
Notes
2019-05-24 07:03:21CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. THE ADDITIONAL LOAD ADDED HAS INCREASED THE LOAD ON
 A PHASE OF PANEL MDP PAST THE RATING OF THE PANEL. NOW,
 A PHASE SHOWS A LOAD OF APPROXIMATELY 1201.75 AMPS ON A
 1200 AMP PANEL. PROVIDE CORRECTION. NEC 408.30, 408.36
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2019-05-31 Cont ID  
Sent By rrossano Date 2019-05-31 Time   Rev Time 0.00
Received By rrossano Date 2019-05-31 Time   Sent To I
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2019-05-21 Cont ID  
Sent By rrossano Date 2019-05-21 Time   Rev Time 0.00
Received By rrossano Date 2019-05-21 Time   Sent To I
Notes
2019-05-21 10:04:23PLEASE PROVIDE REVISED IMPERVIOUS CALCULATIONS.
  
 FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR
 CONCERNS, THANKS.
  
 RICK ROSSANO
 PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1098
 FAX: (561) 494-1116
 MOBILE: (561) 246-9525
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
 MANNY GONZALEZ
 SENIOR ENGINEERING PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
 CENTRAL OPERATIONS CENTER (DISPATCH):
 24-HOUR EMERGENCY RESPONSE SERVICES TO PUBLIC
 UTILITIES, PUBLIC WORKS, PARKS, ETC. 561-822-2210
  
  
2019-05-14 09:22:53ENGINEERING REVIEW IS REQUIRED FOR THIS REVISION PER
 VINCE NOEL AND HEATHER DANFORTH
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-05-31 Cont ID  
Sent By pleduc Date 2019-05-31 Time   Rev Time 0.00
Received By pleduc Date 2019-05-31 Time 09:50 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2019-05-22 Cont ID  
Sent By pleduc Date 2019-05-22 Time   Rev Time 0.00
Received By pleduc Date 2019-05-22 Time 12:37 Sent To  
Notes
2019-05-22 13:14:075/22/19
  
 THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET T 1.1 - THERE IS AN INDICATION OF AN INCORRECT
 EDITION OF THE FLORIDA FIRE PREVENTION CODE; 3RD.
  
 THE CURRENT EDITION OF THE FFPC IS THE 6TH.
  
 PLEASE REVIEW AND CORRECT.
  
  
  
 2) SHEETS ASP 1.0 & C 2.0 - THERE IS AN INDICATION OF A
 PASS THRU LANE WITH A WIDTH DIMENSION OF 13'6" FROM
 CURB TO CANOPY EDGE WITH A HEIGHT OF 9'6".
  
 FIRE DEPARTMENT ACCESS AROUND THE BUILDING REQUIRES A
 WIDTH OF 20' AND HEIGHT OF 13'6".
  
 THE EXISTING PARKING AREA ACCOMODATED FIRE DEPARTMENT
 20'; HOWEVER, THE DEMO C 1.2 PLAN REMOVES IT.
  
 PER NFPA 1, CH 18
  
 18.2.3.2 ACCESS TO BUILDING.
  
 18.2.3.2.1 A FIRE DEPARTMENT ACCESS ROAD SHALL EXTEND
 TO WITHIN 50 FT
 (15 M) OF AT LEAST ONE EXTERIOR DOOR THAT CAN BE OPENED
 FROM THE
 OUTSIDE AND THAT PROVIDES ACCESS TO THE INTERIOR OF THE
 BUILDING.
  
 18.2.3.4 SPECIFICATIONS.
 18.2.3.4.1 DIMENSIONS.
 18.2.3.4.1.1 FIRE DEPARTMENT ACCESS ROADS SHALL HAVE AN
 UNOBSTRUCTED
 WIDTH OF NOT LESS THAN 20 FT (6.1 M).
 18.2.3.4.1.2 FIRE DEPARTMENT ACCESS ROADS SHALL HAVE AN
 UNOBSTRUCTED
 VERTICAL CLEARANCE OF NOT LESS THAN 13 FT 6 IN. (4.1
 M).
 18.2.3.4.1.2.1 VERTICAL CLEARANCE SHALL BE PERMITTED TO
 BE REDUCED,
 PROVIDED SUCH REDUCTION DOES NOT IMPAIR ACCESS BY FIRE
 APPARATUS, AND
 APPROVED SIGNS ARE INSTALLED AND MAINTAINED INDICATING
 THE ESTABLISHED
 VERTICAL CLEARANCE WHEN APPROVED.
 18.2.3.4.1.2.2 VERTICAL CLEARANCES OR WIDTHS SHALL BE
 INCREASED WHEN
 VERTICAL CLEARANCES OR WIDTHS ARE NOT ADEQUATE TO
 ACCOMMODATE FIRE
 APPARATUS.
  
 PLEASE REVIEW AND CORRECT RAODWAY WIDTH/CANOPY HEIGHT
 AND/OR PROVIDE DIMENSIONS FROM EDGE OF EAST PARKING LOT
 TO FRONT ENTRANCE DOOR MEETING THE ABOVE50 FT.
  
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2019-06-04 Cont ID  
Sent By gjohnson Date 2019-06-04 Time 10:27 Rev Time 0.00
Received By gjohnson Date 2019-06-04 Time 10:27 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2019-05-17 Cont ID  
Sent By gjohnson Date 2019-05-17 Time 16:47 Rev Time 0.00
Received By gjohnson Date 2019-05-17 Time 16:47 Sent To  
Notes
2019-05-17 16:47:411ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1.REMOVE OLD CLOUDS AND SHOW ONLY NEW REVISION I COULD
 NOT LOCATE ANY NEW PLUMBING PLACE NOTES ON THE PLAN
 INDICATING REVISIONS. PER WPB AMEND TO FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-06-04 Cont ID  
Sent By gjohnson Date 2019-06-04 Time 10:28 Rev Time 0.00
Received By gjohnson Date 2019-05-28 Time 15:59 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2019-05-24 Time   Rev Time 0.00
Received By lmarchan Date 2019-05-15 Time 12:55 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2019-05-31 Cont ID  
Sent By shill Date 2019-05-31 Time 12:09 Rev Time 0.00
Received By shill Date 2019-05-31 Time 12:09 Sent To  
Notes
2019-05-31 12:09:36IMPACT FEE NOT REQUIRED FOR ADDITIONAL DRIVE THRU LANE
 PER EMAIL FROM W.SWOOPE
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2019-05-21 Cont ID  
Sent By ccole Date 2019-05-21 Time 09:39 Rev Time 0.00
Received By ccole Date 2019-05-21 Time 09:39 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-06-04 Cont ID  
Sent By gjohnson Date 2019-06-04 Time 10:27 Rev Time 0.00
Received By gjohnson Date 2019-06-04 Time 10:27 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-05-16 Cont ID  
Sent By gjohnson Date 2019-05-16 Time 18:11 Rev Time 0.00
Received By gjohnson Date 2019-05-16 Time 15:57 Sent To  
Notes
2019-05-16 18:11:011ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1.REMOVE OLD CLOUDS AND SHOW ONLY NEW REVISION I COULD
 NOT LOCATE ANY NEW PLUMBING PLACE NOTES ON THE PLAN
 INDICATING REVISIONS. PER WPB AMEND TO FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2019-05-31 Cont ID  
Sent By shill Date 2019-05-31 Time 11:41 Rev Time 0.00
Received By shill Date 2019-05-31 Time 11:41 Sent To  
Notes
2019-05-29 06:52:48ELECTRICAL SHEET OK.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2019-05-21 Cont ID  
Sent By shill Date 2019-05-21 Time 09:28 Rev Time 0.00
Received By shill Date 2019-05-21 Time 09:20 Sent To  
Notes
2019-05-21 09:29:06ALL TRADES VERIFIED - SIGNATURES/SEALS OK
 NEW PAGES SUBMITTED NEXT REVIEW CYCLE REQUIRE
 VERIFICATION
 [email protected]
  

Review Stop Z ZONING
Rev No 2 Status P Date 2019-05-31 Cont ID  
Sent By hdanfort Date 2019-05-31 Time 14:30 Rev Time 0.00
Received By hmtribou Date 2019-05-31 Time 14:30 Sent To  
Notes
2019-05-31 14:30:491. PRIOR TO ISSUANCE OF CERTIFICATE OF COMPLETION ALL
 LANDSCAPING AS SHOWN ON APPROVED PLANS FOR AFFECTED
 AREA, SHALL BE INSTALLED, INSPECTED, AND ACCEPTED.
 ADDITIONALLY, ALL EXISTING LANDSCAPING SHALL BE
 INSPECTED FOR COMPLIANCE WITH THE PREVIOUSLY APPROVED
 PLANS.

Review Stop Z ZONING
Rev No 1 Status P Date 2019-05-16 Cont ID  
Sent By hdanfort Date 2019-05-16 Time 15:09 Rev Time 0.00
Received By hmtribou Date 2019-05-16 Time 15:09 Sent To  
Notes
2019-05-16 15:10:451. PRIOR TO ISSUANCE OF CERTIFICATE OF COMPLETION ALL
 LANDSCAPING AS SHOWN ON APPROVED PLANS FOR AFFECTED
 AREA, SHALL BE INSTALLED, INSPECTED, AND ACCEPTED.
 ADDITIONALLY, ALL EXISTING LANDSCAPING SHALL BE
 INSPECTED FOR COMPLIANCE WITH THE PREVIOUSLY APPROVED
 PLANS.