Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2019-07-23 Cont ID  
Sent By jwitmer Date 2019-07-23 Time 10:45 Rev Time 0.00
Received By jwitmer Date 2019-07-23 Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-07-03 Cont ID  
Sent By shill Date 2019-07-03 Time 15:53 Rev Time 0.00
Received By shill Date 2019-07-03 Time 15:53 Sent To  
Notes
2019-07-03 15:54:33****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. SEE PREVIOUS BUILDING REVIEW; NO NEW INFORMATION
 SUBMITTED. IF YOU SELECT A FLOORING UNDERLAYMENT FOR
 WHICH WE HAVE TEST REPORTS ON FILE, ONLY SPEC SHEETS
 ARE NEEDED. IF WE DO NOT HAVE THE TEST REPORTS ON FILE,
 PLEASE PROVIDE.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-06-05 Cont ID  
Sent By jwitmer Date 2019-06-05 Time 07:25 Rev Time 0.00
Received By jwitmer Date 2019-06-04 Time 14:40 Sent To  
Notes
2019-06-05 07:24:582017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19050673
 ADD: 4500 N. FLAGLER DR. SUITE: D24
 CONT: BLUE WATER VENTURES OF PALM BEACH
 TEL: 561-339-6128
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. JUNE 5, 2019
 ACTION: DENIED
  
 1) SHEET A1 INDICATES THE REMOVAL OF FLOOR FINISHES IN
 VARIOUS ROOMS. THE PROPOSED FLOOR PLAN INDICATES NEW
 FLOOR FINISHES TO BE INSTALLED IN SELECTED ROOMS. THE
 PLAN IS SILENT AS TO WHAT THE FLOOR FINISHES ARE IN
 EACH ROOM. THE FLOOR FINISHES HAVE TO BE A KNOWN
 ELEMENT FOR THE FLOOR SOUND INSULATION HAS TO BE TESTED
 INSULATION AND THE FLOOR FINISH. SEE THE (3) REQUIRED
 TEST THAT WILL NEED TO BE SUBMITTED, NOT A SALES
 BROCHURE.
  
 BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION (FBC-B
 2017)
 FOR TILE, STONE, MARBLE, VINYL AND WOOD FLOORING ALL
 NEED TO HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR
 ASSEMBLIES TO THE FOLLOWING STANDARDS AND MEET THE
 QUALIFICATIONS LISTED UNDER EACH OF THE STANDARDS FOR A
 6 INCH CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING:
 PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH:
  
 1A) FBC-B 2017 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 1B) FBC-B 2017 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 1C) FLAME SPREAD- FBC-B 2017 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-06-22 Cont ID  
Sent By jpearson Date 2019-06-22 Time 15:57 Rev Time 0.00
Received By jpearson Date 2019-06-22 Time 15:57 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-06-03 Cont ID  
Sent By jpearson Date 2019-06-03 Time 15:41 Rev Time 0.00
Received By jpearson Date 2019-06-03 Time 06:52 Sent To  
Notes
2019-06-03 15:41:13CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE RISER DIAGRAM OF EXISTING SERVICE, AS WELL
 AS PROPOSED CHANGE. NEC 215.5; WPB FBC 107.2.1
 2. TO INCREASE THE SERVICE SIZE TO THE UNIT, WE WILL
 NEED TO SEE THE EXISTING SERVICE IS ADEQUATE FOR THIS.
 PROVIDE LOAD CALCULATION FOR ENTIRE PORTION OF SERVICE
 THIS UNIT IS FED FROM, INCLUDE EXISTING AND NEW LOADS
 TO CONFIRM CAPACITY OF SERVICE IS ADEQUATE. NEC 215.2,
 220, 408.30
 3. PROVIDE ACCURATE LOAD CALCULATION, LAUNDRY WASHER
 AND DRYER IS NOT INCLUDED. GFCI CIRCUITS FOR BATHROOMS
 ARE NOT COUNTED AS A SMALL APPLIANCE CIRCUIT. NEC 220
 4. PROVIDE CALCULATION FOR AVAILABLE SHORT CIRCUIT
 CURRENT AT NEW PANEL TO CONFIRM AIC RATING IS ADEQUATE.
 NEC 110.10
 5. PROVIDE AIC RATING OF PANEL. NEC 110.3, 110.9
 6. NOTE STATES THAT 50% OF LIGHTING SHALL BE ENERGY
 EFFICIENT. THIS IS NOT THE CURRENT CODE. PROVIDE
 CORRECTION. FBC EC C405.1, R404.1
 7. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC 210.8(D)
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2019-07-16 Cont ID  
Sent By pleduc Date 2019-07-16 Time   Rev Time 0.00
Received By pleduc Date 2019-07-16 Time 13:04 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-06-20 Cont ID  
Sent By pleduc Date 2019-06-20 Time   Rev Time 0.00
Received By pleduc Date 2019-06-20 Time 14:16 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2019-05-17 Cont ID  
Sent By pleduc Date 2019-05-17 Time   Rev Time 0.00
Received By pleduc Date 2019-05-17 Time 14:47 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2019-07-23 Time   Rev Time 0.00
Received By lmarchan Date 2019-07-11 Time 14:41 Sent To  
Notes
2019-07-12 14:41:52B33

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-07-03 Cont ID  
Sent By shill Date 2019-07-03 Time 15:54 Rev Time 0.00
Received By shill Date 2019-06-17 Time 14:41 Sent To  
Notes
2019-06-18 14:41:50B20

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2019-06-05 Time   Rev Time 0.00
Received By lmarchan Date 2019-05-13 Time 15:15 Sent To  
Notes
2019-05-14 15:15:56B20

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2019-07-15 Cont ID  
Sent By ccole Date 2019-07-15 Time 09:34 Rev Time 0.00
Received By ccole Date 2019-07-15 Time 09:25 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2019-06-28 Cont ID  
Sent By ccole Date 2019-06-28 Time 09:47 Rev Time 0.00
Received By ccole Date 2019-06-28 Time 08:06 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2019-05-31 Cont ID  
Sent By ccole Date 2019-05-31 Time 16:36 Rev Time 0.00
Received By ccole Date 2019-05-31 Time 16:36 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2019-07-19 Cont ID  
Sent By gjohnson Date 2019-07-19 Time 13:33 Rev Time 0.00
Received By gjohnson Date 2019-07-19 Time 13:01 Sent To  
Notes
2019-07-19 13:34:22PREVIOUSLY APPROVED BYTIM LARGE

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-06-25 Cont ID  
Sent By tklarge Date 2019-06-25 Time 08:23 Rev Time 0.00
Received By tklarge Date 2019-06-20 Time 10:44 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-05-22 Cont ID  
Sent By thunt Date 2019-05-22 Time 17:09 Rev Time 0.00
Received By thunt Date 2019-05-22 Time 07:08 Sent To  
Notes
2019-05-22 17:12:58PLUMBING 1ST REVIEW**DEINIED**
  
 1) WASHING MACHINE IS NOT PERMITTED TO DISCHARGE INTO
 THE BATHROOM GROUP HORIZONTAL WET VENT AS SHOWN ON SHT
 2. FBC-PLB 912.1, 912.2.1
  
 2) WASHING MACHINE HORIZONTAL BRANCH PIPE SHALL BE MIN
 3". FBC-PLB 406.2
  
 3) PROVIDE COMPLETE MANUFACTURES INSTALLATION MANUAL
 FOR THE WASHER/DRYER. FBC 107.2.1
  
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR
 BUILDING DIVISION
 CITY OF WEST PALM BEACH
 401 CLEMATIS STREET, 1ST FLOOR
 WEST PALM BEACH, FL 33401
 561-248-2703
 [email protected]
 [email protected]
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved