Plan Review Details - Permit 19050671
Plan Review Stops For Permit 19050671
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-05-14 Cont ID  
Sent By dbattles Date 2019-05-14 Time 08:00 Rev Time 0.00
Received By dbattles Date 2019-05-14 Time 08:00 Sent To  
Notes
2019-05-14 08:01:51****CORRECTIONS****
 W.P.B. PERMIT: 19050671
 REVIEWED: MAY 13, 2019
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER PX4191
 [email protected]
 561-805-6718
  
 FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC[EXISTING] = FBC EXISTING BUILDING
 FBC[E] = FBC ENERGY CONSERVATION
 FBC[R] = FBC RESIDENTIAL
  
 1) PROVIDE WRITTEN NARRITIVE OF WORK TO BE DONE TO THE
 MAIN STRUCTURE AND THEN ONE FOR THE GARAGE IF INCLUDED.
 PERMIT IS BASED ON VALUE OF WORK BEING PERFORMED.
 PLEASE PROVIDE A COPY OF THE CONTRACT FOR WORK, OR
 PROVIDE VALUE BASED ON THE NARRITIVE PROVIDED.
  
 2) 107.3.5 FBC[AMENDED] PLEASE PROVIDE DETAILED
 DRAWINGS TO SHOW THE WORK TO BE PERFORMED.
 A DRAWING WITH NOTES TO SHOW DEMOLITION OF AREAS OF
 WORK, DRAWING TO SHOW NEW CONFIGURATIONS,
 3) ALSO, IF ANY WORK BEING DONE TO THE EXTERIOR PROVIDE
 PRODUCT APPROVALS. CHANGES MAY INCLUDE DOORS, WINDOWS,
 ROOFING OR CLADDING.
  
 4) 501 FBC[EXISTING] STATE THE LEVEL OF ALTERATION FOR
 WORK BEING PERFORMED.
 -PLEASE ADD LEVEL OF ALTERATION TO DESIGN DATA.
  
 5) R314.2.2 FBC[R] ALTERATIONS, REPAIRS AND ADDITIONS.
 WHERE ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A
 PERMIT OCCUR, OR WHERE ONE OR MORE SLEEPING ROOMS ARE
 ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL
 DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS
 LOCATED AS REQUIRED FOR NEW DWELLINGS. EXCEPTIONS:
  -REVIEW THIS CODE SECTION (R314.2.2)FOR EXCEPTIONS AND
 LOCATIONS WHERE SMOKE DETECTORS MAY BE REQUIRED.
  
 6) 501.1.1 FBC[RE] ADDITIONS, ALTERATIONS, OR REPAIRS:
 GENERAL. ADDITIONS, ALTERATIONS, OR REPAIRS TO AN
 EXISTING BUILDING, BUILDING SYSTEM OR PORTION THEREOF
 SHALL COMPLY WITH SECTION R502, R503 OR R504. UNALTERED
 PORTIONS OF THE EXISTING BUILDING OR BUILDING SUPPLY
 SYSTEM SHALL NOT BE REQUIRED TO COMPLY WITH THIS CODE.
  -PLEASE CHOOSE ENERGY CODE COMPLIANCE METHOD AND SHOW
 HOW NEW WORK WILL COMPLY WITH THE METHOD CHOSEN.
  
  
 NOTES:
  
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
  
 -COMMENTS ARE A BRIEF OVERVIEW OF CODE SECTIONS.
 FURTHER REVIEW OF THE REFERENCED CODE SECTIONS WILL BE
 REQUIRED.
  
 -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
  
 -FENCE WOULD BE A SEPARATE PERMIT.
  
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  
 PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F
 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME
 [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-05-14 Cont ID  
Sent By cthroop Date 2019-05-14 Time 10:53 Rev Time 0.00
Received By cthroop Date 2019-05-14 Time 10:18 Sent To  
Notes
2019-05-14 10:56:57ELECTRICAL PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC M = FLORIDA BUILDING CODE MECHANICAL 2017 6TH
 EDITION
 FBC P = FLORIDA BUILDING CODE PLUMBING 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 DUE TO THE DEFICIENCIES OF THIS PLAN, A COMPLETE AND
 THOROUGH REVIEW CANNOT BE PERFORMED AT THIS TIME. UPON
 RE-SUBMITTAL, ADDITIONAL COMMENTS MAY BE MADE.
  
 1. PROVIDE AN ELECTRICAL PLAN.
 2. PROVIDE AN ELECTRICAL RISER DIAGRAHM.
 3. PROVIDE A LOAD CALCULATION FOR EACH SERVICE.
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-05-21 Cont ID  
Sent By mcruz Date 2019-05-21 Time 10:29 Rev Time 0.00
Received By mcruz Date 2019-05-14 Time 08:01 Sent To PC
Notes
2019-05-14 18:05:595/14 TO ZONING
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-05-14 Cont ID  
Sent By cthroop Date 2019-05-14 Time 10:50 Rev Time 0.00
Received By cthroop Date 2019-05-14 Time 10:18 Sent To  
Notes
2019-05-14 10:53:53MECHANICAL PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC M = FLORIDA BUILDING CODE MECHANICAL 2017 6TH
 EDITION
 FBC P = FLORIDA BUILDING CODE PLUMBING 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 DUE TO THE DEFICIENCIES OF THIS PLAN, A COMPLETE AND
 THOROUGH REVIEW CANNOT BE PERFORMED AT THIS TIME. UPON
 RE-SUBMITTAL, ADDITIONAL COMMENTS MAY BE MADE.
  
 1. PROVIDE MECHANICAL PLAN.
 2. PROVIDE AN ENERGY SUBMITTAL.
 3. PROVIDE EQUIPMENT SPECIFICATIONS AND SIZING.
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-05-14 Cont ID  
Sent By cthroop Date 2019-05-14 Time 10:57 Rev Time 0.00
Received By cthroop Date 2019-05-14 Time 10:18 Sent To  
Notes
2019-05-14 11:00:37PLUMBING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC M = FLORIDA BUILDING CODE MECHANICAL 2017 6TH
 EDITION
 FBC P = FLORIDA BUILDING CODE PLUMBING 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 DUE TO THE DEFICIENCIES OF THIS PLAN, A COMPLETE AND
 THOROUGH REVIEW CANNOT BE PERFORMED AT THIS TIME. UPON
 RE-SUBMITTAL, ADDITIONAL COMMENTS MAY BE MADE.
  
 1. PROVIDE A PLUMBING PLAN.
 2. PROVIDE A BUILDING SEWER RISER DIAGRAHM.
 3. PROVIDE A GAS RISER DIAGRAHM, IF APPLICABLE.
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
  

Review Stop Z ZONING
Rev No 1 Status F Date 2019-05-21 Cont ID  
Sent By mcruz Date 2019-05-21 Time 10:29 Rev Time 0.00
Received By mcruz Date 2019-05-21 Time 10:25 Sent To PC
Notes
2019-05-21 10:29:12ZONING REVIEW FAILED, DUE TO THE FOLLOWING:
  
 1) IS THIS REMODEL INTERIOR ONLY? IS THE STRUCTURE
 BEING EXPANDED?
  
 NOTE: THE SUBMITTAL OF THE REQUESTED INFORMATION MAY
 GENERATE ADDITIONAL COMMENTS.
  
 FOR ADDITIONAL INFORMATION, THE ZONING AND LAND
 DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT
 WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH
 PLANNING DEPARTMENT WEBSITE AT
 WWW.CITYOFWPB.COM/PLAN/INDEX.HTM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME. IF YOU WANT TO MEET IN PERSON TO GO OVER
 THE ABOVE COMMENTS, PLEASE CALL OR E-MAIL ME TO
 SCHEDULE AN APPOINTMENT.
  
 MAGGIE CRUZ
 ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: 561-822-1442
 E-MAIL: [email protected]
  