Plan Review Details - Permit 19050628
Plan Review Stops For Permit 19050628
Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2019-06-17 Cont ID  
Sent By ccole Date 2019-06-17 Time 11:56 Rev Time 0.00
Received By ccole Date 2019-06-17 Time 11:56 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-05-17 Cont ID  
Sent By ccole Date 2019-05-17 Time 11:07 Rev Time 0.00
Received By ccole Date 2019-05-17 Time 11:07 Sent To I
Notes
2019-05-17 11:23:351ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19050628
 5/17/19
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE $20,000 VALUE ON THE APPLICATION IS LOW FOR THE
 SCOPE OF WORK. THE SUBMITTED CONTRACT IS FOR LABOR ONLY
 AND DOES NOT INCLUDE THE COST OF THE RTU'S AND CURB
 ADAPTERS ETC. PLEASE PROVIDE A COPY OF THE INVOICE FROM
 WALGREEN AND ADJUST THE TOTAL VALUE- SECTION 109.3 WPB.
  
 2) THE SUBMITTED ENGINEERING FOR INSTALLATION HAS A
 COPIED ENGINEER'S SIGNATUTRE AND SEAL FROM 2017. PLEASE
 NOTE UPDATED SIGNED AND SEALED ENGINEERING IS REQUIRED
 FOR APPROVAL- SECTION 301.15 FBC M AND SECTION
 61G15.23.002 FAC.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  