Plan Review Details - Permit 19050603
Plan Review Stops For Permit 19050603
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2019-07-30 Cont ID  
Sent By shill Date 2019-07-30 Time 12:19 Rev Time 0.00
Received By shill Date 2019-07-30 Time 12:19 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2019-07-26 Cont ID  
Sent By shill Date 2019-07-26 Time 17:11 Rev Time 0.00
Received By shill Date 2019-07-26 Time 09:00 Sent To  
Notes
2019-07-26 17:11:38SEE NFIP REVIEW
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-07-09 Cont ID  
Sent By shill Date 2019-07-09 Time 06:25 Rev Time 0.00
Received By shill Date 2019-07-09 Time 06:25 Sent To  
Notes
2019-07-09 06:26:19****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. SEE COMMENTS FROM PREVIOUS REVIEW; NOT ADDRESSED
 (PROVIDE DOCUMENTATION TO DEMONSTRATE THAT THIS IS NOT
 A SUBSTANTIAL IMPROVEMENT). THIS CAN BE SENT VIA EMAIL.
  
 2. A.02 AND OTHER PAGES, PLEASE CLARIFY, CONFERENCE
 ROOM DOOR, PULL SIDE APPEARS TO HAVE A COLUMN
 OBSTRUCTING THE REQUIRED 18" MANEUVERING CLEARANCE
 REQUIRED BY FBC A FIGURE 404.2.4.1(A). IF THIS IS NOT A
 COLUMN, PLEASE ADVISE VIA EMAIL AND THE PLAN WILL BE
 STAMPED WITH REDLINE/PROVISO. IF THIS IS A COLUMN,
 REVISE PLAN.
  
 NOTE THAT THE COPY ROOM ALSO HAS THE SAME CONDITION. IF
 ARCHITECT FEELS THIS IS COVERED BY AN EXCEPTION (WORK
 AREA), PROVIDE RATIONALE IN A LETTER. FEEL FREE TO
 CONTACT ME TO DISCUSS.
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-06-04 Cont ID  
Sent By jwitmer Date 2019-06-04 Time 09:31 Rev Time 0.00
Received By jwitmer Date 2019-06-03 Time 08:43 Sent To  
Notes
2019-06-04 09:31:132017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19050603
 ADD: 1217 S FLAGLER DR. 2ND FLOOR
 CONT: NICK RAICH BUILDING CORP.
 TEL: 561-659-9347
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. JUNE 04/ 2019
 ACTION: DENIED
  
 1) THIS BUILDING IS LOCATED IN A FLOOD ZONE. ARTICLE
 XVII ORDINANCES ARTICLE XVII FLOOD PREVENTION & CONTROL
 FBC BUILDING 1612 AND CITY OF WPB CODE OF SECTION
 94-546. STRUCTURE IS LOCATED IN AN "AE" FLOOD ZONE. A
 FLOOD ELEVATION CERTIFICATE WILL BE REQUIRED. PLEASE
 REVIEW CITY ORDINANCE FOR THE CITY REQUIREMENTS REQUIRE
 AFTER OCT. 11/ 2017 AN ADDITIONAL ONE FOOT OF FREE
 BOARD WILL BE REQUIRED OR (2) FEET ABOVE BASE FLOOD.
 BASE FLOOD ELEVATION (BFE) 6? NAVD88 OR FIS 5.7?. THE
 COMBINED VALUE OF THIS BUILDING AND LOT ACCORDING TO
 THE PALM BEACH COUNTY PROPERTY APPRAISERS OFFICE IS
 $1,300,000.00 DOLLARS.
  
 SUBSTANIAL IMPROVEMENT. SECTION 94-546 PROVISIONS FOR
 FLOOD HAZARD REDUCTION. (A)(3) ANY ALTERATION, REPAIR,
 RECONSTRUCTION, OR IMPROVEMENTS TO A PROPERTY WHICH THE
 CUMULATIVE COST FOR ANY FIVE YEAR PERIOD EQUALS OR
 EXCEEDS 50 % OF THE BUILDING VALUE AT THE COMMENCEMENT
 OF THE FIVE YEAR PERIOD SHALL MEET THE REQUIREMENTS OF
 NEW CONSTRUCTION AS CONTAINED IN THIS ARTICLE.
 TO DETERMINE IF THE SUBSTANTIAL IMPROVEMENT VALUE FOR
 THIS PROJECT HAS BEEN MET WE CANNOT DETERMINE THIS
 SINCE IN THIS CASE THE PALM BEACH COUNTY PROPERTY
 APPRAISERS OFFICE DOES NOT HAVE THE VALUE FOR THE
 BUILDING BROKEN OUT OF THE OVERALL VALUE OF THE
 ASSESSED PROPERTY. THE OWNER OR TENANT OF THE BUILDING
 WILL NEED TO PROVIDE AN ASSESSED VALUE FOR THE BUILDING
 ITSELF.
  
 THE PROPOSED IMPROVEMENT OVER THE LAST 5 YEARS,
 INCLUDING THE CURRENT PROPOSED IMPROVEMENTS
 ($413,740.00) APPEARS TO BE A SUBSTANTIAL IMPROVEMENT
 BASED ON PROPERTY APPRAISER VALUATION FOR THE STRUCTURE
 & LAND VALUE ($1,300,000.00 DALLORS IN VALUE). IF THIS
 IS A SUBSTANTIAL IMPROVEMENT, THE STRUCTURE IS TO BE
 BROUGHT INTO COMPLIANCE (BFE 6.0' + 2.0?) NAVD88 FOR
 THE LOWEST FINISHED FLOOR, & ALL MECHANICAL EQUIPMENT).
 APPLICANT MAY PROVIDE DOCUMENTATION FOR VALUATION OTHER
 THAN PROPERTY APPRAISER; PLEASE SEE FEMA TECHNICAL
 BULLETIN 758, SECTION 4.5:
 HTTPS://WWW.FEMA.GOV/MEDIA-LIBRARY-DATA/20130726-1734-2
 5045-2915/P_758_COMPLETE_R3.PDF
  
 2) THE PROPOSED VALUE OF $45,000.00 DOLLARS SEAMS LOW
 FOR THE SCOPE OF WORK SHOWN FOR THE 2ND FLOOR LEVEL.
 108.3* BUILDING PERMIT VALUATION.
 IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS
 APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE
 PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 THIS MAIN BUILDING PERMIT WILL INCLUDE THE FEES FOR THE
 MECHANICAL, ELECTRICAL, PLUMBING & ROOFING PERMITS.
 WHEN THE GENERAL CONTRACTOR COMES IN FOR A BUILDING
 PERMIT WITH THE SIGNED PERMIT APPLICATION FORM BY THE
 QUALIFIER AND OWNER AND BRINGS IN THE LISTED
 SUB-PERMITS M-E-P & ROOFING PERMITS SIGNED BY THE
 QUALIFIER OF EACH COMPANY, THEIR INSURANCES AND
 LICENSURE UP TO DATE, THE M-E-P AND ROOFING PERMITS ARE
 FREE OF CHARGE. IF THE M-E-P & ROOFING PERMITS COME IN
 LATER THERE WILL BE AN $80.00 ADMINISTRATIVE FEE FOR
 EACH PERMIT.
  
 ALL OTHER PERMITS FIRE SPRINKLER, FIRE ALARM, RACK
 STORAGE, EXHAUST HOODS, ANSUL SYSTEMS OR ALTERNATIVE
 AUTOMATIC FIRE-EXTINGUISHING SYSTEMS, WALK IN COOLERS &
 FREEZERS, ALL LOW VOLTAGE PERMITS, GENERATORS & FUEL
 TANKS, GAS PERMIT, POOL, JACUZZI AND ASSOCIATED
 SUB-PERMITS, AWNING, SCREEN ENCLOSURES, CANOPY, FENCE,
 LANDSCAPE, IRRIGATION, AUGER CAST PILE AND OR
 FOUNDATION OR STRUCTURE ONLY PERMIT WILL BE SEPARATE
 REVIEWS AND ASSOCIATED FEES WITH EACH PERMIT.
 PLEASE PROVIDE AN ITEMIZED LIST AND SUBTRACT THESE LINE
 ITEMS AND THEIR VALUE FROM THE OVERALL BUILDING VALUE
 STATED ON THE PERMIT APPLICATION FOR THIS PROJECT. THE
 REMAINING BALANCE WILL BE AFFECTIVELY THE VALUE OF THE
 BUILDING YOU WILL BE PAYING FOR THIS PERMIT. THE
 BUILDING DEPARTMENT DOES NOT WANT TO COLLECT TWICE FOR
 THE VALUE OF THESE SUB-PERMITS NOT COVERED UNDER THE
 PRIME OR MASTER PERMIT.
  
 3) THE TITLE BLOCK IS CONFUSING AS TO THE LOCATION OF
 WORK TO BE ACCOMPLISHED UNDER THIS PERMIT. AT 1ST
 GLANCE THE COVERSHEET, A.01 IT WOULD APPEAR ALL WORK ON
 ALL 8 ARCHITECTURAL SHEETS WOULD BE ON THE 3RD FLOOR.
 ON SHEETS A.02-A0.4 THESE SHEETS STILL SAY SALES OFFICE
 3RD FLOOR AS WELL AS 2ND FLOOR PLAN. (4) SETS OF PLANS
 WERE BROUGHT IN MAKING IT MORE CONFUSING ALL PLANS
 LABELED THE SAME WAY FOR THE 2 PERMITS THE 2ND FLOOR &
 3RD FLOOR. PLEASE CORRECT THE TITLE BLOCK FOR THE COVER
 SHEET TO INCLUDE THE 2ND FLOOR AND AS TO WHERE THE WORK
 IS GOING TO BE COMPLETED FOR THE 2ND FLOOR FOR SHEETS
 A.02-A0.4, NO REFERENCE TO THE 3RD FLOOR PLEASE.
 2017 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED.
  
 4) SHEET A.02 & A.03 LIFE SAFETY SHEET:
 4A) EXISTING DOORWAY INTO THE COPY ROOM DOES NOT HAVE
 THE 18 INCHES MANEUVERING CLEARANCE ON THE LATCH SIDE
 OF THE DOORWAY.
  
 2017 FBC-ACCESS. CODE 404.2.4 MANEUVERING CLEARANCES.
 DOORS. MINIMUM MANEUVERING CLEARANCES AT DOORS AND
 GATES SHALL COMPLY WITH 404.2.4. MANEUVERING CLEARANCES
 SHALL EXTEND THE FULL WIDTH OF THE DOORWAY AND THE
 REQUIRED LATCH SIDE FOR SIDE CLEARANCE.
 ACCESS CODE 404.2.4.1 SWINGING DOORS AND GATES.
 SWINGING DOORS AND GATES SHALL HAVE MANEUVERING
 CLEARANCES COMPLYING WITH TABLE 404.2.4.1.
  
 4B) THE 2ND ISSUE WITH THE EXISTING DOORWAY INTO THE
 COPY ROOM AND THE LOCATION OF THE COLUMN, THE DOORWAY
 LOCATION CREATES A RECESSED DOORWAY AND NO MANEUVERING
 CLEARANCE PER ACCESSIBILITY CODE SECTION 404.2.4.3 AND
 FIGURE 404.2.4.3.
  
 4C) NEW DOORWAY INTO THE CONFERENCE ROOM HAS THE SAME 2
 ISSUES AS THE COPY ROOM DOOR IN LOCATION TO THE COLUMN.
 2017 FBC-ACCESS. CODE 404.2.4 MANEUVERING CLEARANCES.
 DOORS. MINIMUM MANEUVERING CLEARANCES AT DOORS AND
 GATES SHALL COMPLY WITH 404.2.4. MANEUVERING CLEARANCES
 SHALL EXTEND THE FULL WIDTH OF THE DOORWAY AND THE
 REQUIRED LATCH SIDE FOR SIDE CLEARANCE.
 ACCESS CODE 404.2.4.1 SWINGING DOORS AND GATES.
 SWINGING DOORS AND GATES SHALL HAVE MANEUVERING
 CLEARANCES COMPLYING WITH TABLE 404.2.4.1.
 ACCESSIBILITY CODE SECTION 404.2.4.3 AND FIGURE
 404.2.4.3. THE CONFERENCE ROOM DOOR IN LOCATION TO THE
 COLUMN CREATES A RECESSED DOORWAY.
  
 4D) THE NEW OFFICE # 2 HAS FURNITURE IN THE REQUIRED
 CLEAR MANEUVERING SPACE LATCH SIDE OF THE DOORWAY.
 ACCESS CODE 404.2.4.1 SWINGING DOORS AND GATES.
 SWINGING DOORS AND GATES SHALL HAVE MANEUVERING
 CLEARANCES COMPLYING WITH TABLE 404.2.4.1.
 DISCREPANCY IN PLANS SHEET A.02 VERSES SHEETS P.01 &
 P.02. SHEET A.02 INDICATES IN THE A.02 SHEET A MOP SINK
 IN THE ACCESSIBLE BATHROOM/ RESTROOM, WHEREAS P1 & P2
 CALL THIS FIXTURE OUT AS P-5 AN ADA PREFABRICATED
 SHOWER ENCLOSURE BY OTHERS. DISCREPANCY IN PLANS,
 ADDITIONAL INFORMATION IS REQUIRED. 107.2.1.2.
 4E)(1) THE DETAIL OF THE BREAK ROOM CABINETS AND SINK
 DOES NOT INDICATE THE HEIGHT OF THE BASE CABINETS NOR
 THE HEIGHT OF THE RIM OF THE SINK IN THE BASE CABINETS.
 PLEASE SHOW COMPLIANCE WITH 2017 ACCESSIBILITY CODE
 SECTION 606.3 HEIGHT. SINKS SHALL BE INSTALLED WITH THE
 FRONT OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34
 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 4E)(2) PLEASE ALSO SHOW COMPLIANCE WITH THE 2017
 FBC-ACCESS. CODE SECTION 606.2. A CLEAR FLOOR SPACE
 COMPLYING WITH 305, POSITIONED FOR A FORWARD APPROACH,
 AND KNEE AND TOE CLEARANCE COMPLYING WITH 306 SHALL BE
 PROVIDED.
  
 4F) THE BREAK ROOM SHOWS 4 CHAIRS AND SHELF BUT NO
 HEIGHT IS GIVEN FOR THE HEIGHT OF THE TABLE TOP/ SHELF.
 THE LIFE SAFETY SHEET DOES NOT SHOW COMPLIANCE WITH THE
 2014 FBC-ACCESSIBILITY CODE; 226.1 WHERE DINING
 SURFACES ARE PROVIDED FOR THE CONSUMPTION OF FOOD OR
 DRINK, AT LEAST 5 PERCENT OF THE SEATING SPACES AND
 STANDING SPACES AT THE DINING SURFACES SHALL COMPLY
 WITH 902.
 902.1 .DINING SURFACES AND WORK SURFACES SHALL COMPLY
 WITH 902.2 AND 902.3. ADVISORY 902.1. DINING SURFACES
 INCLUDE, BUT ARE NOT LIMITED TO, BARS, TABLES, LUNCH
 COUNTERS, AND BOOTHS.
  
 4G) NEITHER A.02 OR A.03 GIVE A SECTION THROUGH THE
 CONFERENCE ROOM GLASS WALL OR DOORWAY. PLEASE SHOW
 COMPLIANCE WITH THE 2017 FBC-B SECTIONS:
 2406.4 HAZARDOUS LOCATIONS. THE LOCATIONS SPECIFIED IN
 SECTIONS 2406.4.1 THROUGH 2406.4.7 SHALL BE CONSIDERED
 SPECIFIC HAZARDOUS LOCATIONS REQUIRING SAFETY GLAZING
 MATERIALS.
  
 2406.4.2 GLAZING ADJACENT TO DOORS. GLAZING IN AN
 INDIVIDUAL FIXED OR OPERABLE PANEL ADJACENT TO A DOOR
 WHERE THE NEAREST VERTICAL EDGE OF THE GLAZING IS
 WITHIN A 24-INCH (610 MM) ARC OF EITHER VERTICAL EDGE
 OF THE DOOR IN A CLOSED POSITION AND WHERE THE BOTTOM
 EXPOSED EDGE OF THE GLAZING IS LESS THAN 60 INCHES
 (1524 MM) ABOVE THE WALKING SURFACE SHALL BE CONSIDERED
 A HAZARDOUS LOCATION.
  
 2406.4.1 GLAZING IN DOORS. GLAZING IN ALL FIXED AND
 OPERABLE PANELS OF SWINGING, SLIDING AND BIFOLD DOORS
 SHALL BE CONSIDERED A HAZARDOUS LOCATION.
  
  
 5) ACCESSIBLE RESTROOM/ BATHROOM DETAILS ARE FOUND ON
 SHEET A.08 3RD FLOOR PERMIT.
  
 6) PLEASE PROVIDE A LETTER EITHER FROM THE CONTRACTOR
 OR DESIGNER OF RECORD ON THEIR LETTERHEAD WHERE UP TO
 20 % OF THE CONTRACT VALUE IS GOING TO BE SPENT IN
 ACCESSIBLE UPGRADES TO THE PROJECT. IF ALL EXISTING
 CONDITIONS ARE COMPLETED (COMPLIED) BEFORE
 DISPROPORTIONATION COST IS MET A LETTER IS NOT
 REQUIRED. SHOW COMPLIANCE WITH THE:
  
 2017 FBC-ACCESSIBILITY CODE SECTION 202.4.1
 DISPROPORTIONATE COST.ALTERATIONS MADE TO PROVIDE AN
 ACCESSIBLE PATH OF TRAVEL TO THE ALTERED AREA WILL BE
 DEEMED DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN
 THE COST EXCEEDS 20% OF THE COST OF THE ALTERATION TO
 THE PRIMARY FUNCTION AREA. COSTS THAT MAY BE COUNTED AS
 EXPENDITURES REQUIRED TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL MAY INCLUDE: (I) COSTS ASSOCIATED WITH PROVIDING
 AN ACCESSIBLE ENTRANCE AND AN ACCESSIBLE ROUTE TO THE
 ALTERED AREA; (II) COSTS ASSOCIATED WITH MAKING
 RESTROOMS ACCESSIBLE, SUCH AS INSTALLING GRAB BARS,
 ENLARGING TOILET STALLS, INSULATING PIPES, OR
 INSTALLING ACCESSIBLE FAUCET CONTROLS; (III) COSTS
 ASSOCIATED WITH PROVIDING ACCESSIBLE TELEPHONES, SUCH
 AS RELOCATING THE TELEPHONE TO AN ACCESSIBLE HEIGHT,
 INSTALLING AMPLIFICATION DEVICES, OR INSTALLING A TEXT
 TELEPHONE (TTY); (IV) COSTS ASSOCIATED WITH RELOCATING
 AN INACCESSIBLE DRINKING FOUNTAIN.
  
  
 7A) NEW MECHANICAL UNITS ARE BEING ADDED AS INDICATED
 IN THE MECHANICAL SHEETS, PLEASE SHOW WHERE THE
 LOCATION WILL BE? IF ROOFTOP SHOW COMPLIANCE WITH: 2017
 FBC-B 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA
 DEPARTMENT OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE
 61G20-3.005, RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY
 OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE
 PRODUCT APPROVALS: (31)(G) PRE-ENGINEERED A/C STANDS.
  
 7B) W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
  
 7C) FOR ROOF TOP A/C STAND PRODUCT APPROVAL. THE
 PRODUCT APPROVAL IS TO BE REVIEWED BY THE DESIGNER OF
 RECORD. PLEASE IDENTIFY THE FOLLOWING REQUIREMENTS
 CALCULATING THE AREA (SIDE VIEW) OF THE ROOF TOP
 COMPRESSORS, CONFIGURATION ON STAND, THE MEAN ROOF
 HEIGHT OF THE STAND AND COMPRESSORS, WEIGHT, CIRCLED
 THE DESIGN PARAMETERS IN THE TABLES, ANCHORS AND UPLIFT
 VERSES MOMENT FOR THE UNIT TO THE STAND AND THE STAND
 TO THE ROOF. THE PRODUCT APPROVAL IS TO BE REVIEWED BY
 THE DESIGNER OF RECORD, APPROVED BEFORE SUBMISSION TO
 THE BUILDING DEPARTMENT. 107.2.1.2 ADDITIONAL
 INFORMATION IS REQUIRED.
  
 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
2019-05-16 15:12:531) SHT.A.03 - DETAIL #2 - THE HEIGHT OF THE BREAK ROOM
 SINK ON THE 2ND AND 3RD FLOOR SHALL BE 34 INCHES MAX.
 2017 FBC-ACCESS. SEC.606.3.
 2) CLEAR FLOOR SPACE SHALL BE PROVIDED AT THE BREAK
 ROOM SINKS COMPLYING WITH 2017 FBC-ACCESS.SEC. 606.2.
 3) SHT. A.02 REFERS TO DETAIL 6 ON SHT. A.05 FOR ADA
 BATH DETAIL.THERE IS NO SUCH DETAIL ON SHT. A.05. THE
 DETAIL IS ON SHT. A.08. REVISE THE NOTE.
 4)
  
 REVIEW IS INCOMPLETE.
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2019-07-18 Cont ID  
Sent By jleahy Date 2019-07-18 Time 10:00 Rev Time 0.00
Received By jleahy Date 2019-07-18 Time 10:00 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2019-07-03 Cont ID  
Sent By jleahy Date 2019-07-03 Time 14:49 Rev Time 0.00
Received By jleahy Date 2019-07-03 Time 14:38 Sent To  
Notes
2019-07-03 14:50:52ALL COMMENTS ADDRESSED EXCEPT VALUE OF WORK???? VALUE
 LOOKS LOW
  
 SUBMIT A SIGNED CONTRACT WITH THE OWNER FOR THE TOTAL
 JOB LABOR, MATERIAL ECT. ECT.
  
 JLEAHY 7/3/19

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-05-31 Cont ID  
Sent By jpearson Date 2019-05-31 Time 14:07 Rev Time 0.00
Received By jpearson Date 2019-05-31 Time 07:45 Sent To  
Notes
2019-05-31 14:07:45CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND
 VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS
 IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. WPB FBC
 109.3
 2. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS,
 DAS, LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD
 SYSTEMS, WALK IN COOLERS, SIGNS, SITE LIGHTING, AND
 SWIMMING POOLS (WHERE APPLICABLE) ARE NOT INCLUDED IN
 THE SCOPE OF THIS PLAN REVIEW. PROVIDE A BLOCK NOTE
 INDICATING THE REQUIRED SEPARATE PERMITS AND PLAN
 SUBMITTALS FOR ANY OF THESE SYSTEMS PRESENT. WPB FBC
 105.1, 107.2.1
 3. RISER DIAGRAM SHOWS A THREE PHASE FEEDER BEING
 EXTENDED TO PANEL B. HOWEVER, THE PANEL SCHEDULE FOR
 PANEL B SHOWS IT AS A SINGLE PHASE PANEL. WHICH IS IT?
 PROVIDE CLARIFICATION AND CORRECTIONS AS NEEDED. WPB
 FBC 107.2.1; NEC 408.4, 408.30, 408.36
 4. RISER DIAGRAM SHOWS PANEL A AND PANEL M BEING FED
 FROM THE SAME METER CAN, BUT ONE OF THESE PANELS IS
 SHOWN AS THREE PHASE AND ONE OF THEM IS SHOWN AS SINGLE
 PHASE. IS THIS ACCURATE? PROVIDE CLARIFICATION AND
 CORRECTIONS AS NEEDED. PROVIDE RATING OF EXISTING METER
 CAN AND LOAD CALCULATION TO CONFIRM CAPACITY IS
 ADEQUATE. WPB FBC 107.2.1; NEC 220, 408.30, 408.36
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-06-18 Cont ID  
Sent By pleduc Date 2019-06-18 Time   Rev Time 0.00
Received By pleduc Date 2019-06-18 Time 15:35 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2019-05-22 Cont ID  
Sent By pleduc Date 2019-05-22 Time   Rev Time 0.00
Received By pleduc Date 2019-05-22 Time 15:04 Sent To  
Notes
2019-05-22 15:15:325/22/19
  
 THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET A 05 - THERE IS AN INDICATION OF A
 RANGE/STOVE/VENT WITHIN THE KITCHEN.
  
 IS THIS KITCHEN RANGE/STOVE/VENT FUNCTION OR JUST FOR
 SHOW?
  
 PLEASE PROVIDE A NOTE OF NON-FUNCTIONAL OR DETAILS OF
 FUNCTION AS APPLICABLE.
  
  
  
 3) SHEET M 02 - - THERE ARE INDICATIONS OF 4 A/C UNITS
 OF 2000 CFM
  
 PER NFPA 90 A , CHAPTER 6 CONTROLS
  
 6.4* SMOKE DETECTION FOR AUTOMATIC CONTROL.
 6.4.1 TESTING. ALL AUTOMATIC SHUTDOWN DEVICES SHALL BE
 TESTED AT LEAST ANNUALLY.
 6.4.2* LOCATION.
 6.4.2.1 SMOKE DETECTORS LISTED FOR USE IN AIR
 DISTRIBUTION SYSTEMS SHALL BE LOCATED AS FOLLOWS:
 (1) DOWNSTREAM OF THE AIR FILTERS AND AHEAD OF ANY
 BRANCH CONNECTIONS IN AIR SUPPLY SYSTEMS HAVING A
 CAPACITY GREATER THAN 944 L/SEC (2000 FT3/MIN)
 (2) AT EACH STORY PRIOR TO THE CONNECTION TO A COMMON
 RETURN AND PRIOR TO ANY RECIRCULATION OR FRESH AIR
 INLET CONNECTION IN AIR RETURN SYSTEMS HAVING A
 CAPACITY GREATER THAN 7080 L/SEC (15,000 FT3/MIN) AND
 SERVING MORE THAN ONE STORY
  
 6.4.3* FUNCTION.
 6.4.3.1 SMOKE DETECTORS PROVIDED AS REQUIRED BY 6.4.2
 SHALL AUTOMATICALLY STOP THEIR RESPECTIVE FAN(S) ON
 DETECTING THE PRESENCE OF SMOKE.
  
 6.4.4.2 IN ADDITION TO THE REQUIREMENTS OF 6.4.3, WHERE
 AN APPROVED FIRE ALARM SYSTEM IS INSTALLED IN A
 BUILDING, THE SMOKE DETECTORS REQUIRED BY THE
 PROVISIONS OF SECTION 6.4 SHALL BE CONNECTED TO THE
 FIRE ALARM SYSTEM IN ACCORDANCE WITH THE REQUIREMENTS
 OF NFPA 72, NATIONAL FIRE ALARM AND SIGNALING
 CODE.
  
 6.4.4.2.1 SMOKE DETECTORS USED SOLELY FOR CLOSING
 DAMPERS OR FOR HEATING, VENTILATING, AND
 AIR-CONDITIONING SYSTEM SHUTDOWN SHALL NOT BE REQUIRED
 TO ACTIVATE THE BUILDING EVACUATION ALARM.
  
 6.4.4.3 WHERE SMOKE DETECTORS REQUIRED BY SECTION 6.4
 ARE INSTALLED IN A BUILDING NOT EQUIPPED WITH AN
 APPROVED FIRE ALARM SYSTEM AS SPECIFIED BY 6.4.4.2, THE
 FOLLOWING SHALL OCCUR:
 (1) SMOKE DETECTOR ACTIVATION REQUIRED BY SECTION 6.4
 SHALL CAUSE A VISUAL SIGNAL AND AN AUDIBLE SIGNAL IN A
 NORMALLY OCCUPIED AREA.
 (2) SMOKE DETECTOR TROUBLE CONDITIONS SHALL BE
 INDICATED VISUALLY OR AUDIBLY IN A NORMALLY OCCUPIED
 AREA AND SHALL BE IDENTIFIED AS AIR DUCT DETECTOR
 TROUBLE.
  
  
  
 PLEASE REVIEW AND ENSURE COMPLIANCE AND PROVIDE AN
 APPLICABLE NOTE OF ACKNOWLEDGEMENT.
  
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-07-26 Cont ID  
Sent By shill Date 2019-07-26 Time 17:11 Rev Time 0.00
Received By shill Date 2019-07-16 Time 15:39 Sent To  
Notes
2019-07-17 15:39:28RESUB ROUTED TO JLEAHY

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-07-09 Cont ID  
Sent By shill Date 2019-07-09 Time 06:26 Rev Time 0.00
Received By shill Date 2019-06-14 Time 16:48 Sent To  
Notes
2019-06-17 16:48:46B25

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2019-06-04 Time   Rev Time 0.00
Received By lmarchan Date 2019-05-10 Time 13:39 Sent To  
Notes
2019-05-13 13:39:26B17

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2019-06-04 Cont ID  
Sent By jwitmer Date 2019-06-04 Time 09:31 Rev Time 0.00
Received By jwitmer Date 2019-06-03 Time 08:43 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2019-06-28 Cont ID  
Sent By ccole Date 2019-06-28 Time 16:15 Rev Time 0.00
Received By ccole Date 2019-06-28 Time 15:34 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-05-30 Cont ID  
Sent By ccole Date 2019-05-30 Time 17:12 Rev Time 0.00
Received By ccole Date 2019-05-30 Time 17:12 Sent To  
Notes
2019-05-30 17:22:301ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19050603
 5/30/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR THE
 NEW SYSTEMS- SECTION C403.2.1 FBC EC.
  
 2) SHOW THE LOCATIONS OF THE NEW AC CONDENSERS ON THE
 ROOF AND INDICATE HOW ACCESS WILL BE PROVIDED- SECTION
 107.2.1 WPB.
  
 3) SHEET M0.1: REFER TO SECTION 306.1 FBC M AND VERIFY
 THE NEW ACCESS PANELS WILL BE SIZED LARGE ENOUGH TO
 REPLACE THE ABOVE CEILING AIR HANDLERS- SECTION 306.1
 FBC M.
  
 4) THE $45,000.00 JOB VALUE FOR THE PROPOSED PROJECT
 APPEARS LOW FOR THE SCOPE OF WORK. PLEASE SEE SECTION
 109.3 WPB AND VERIFY COSTS BY SUBMITTING SIGNED
 CONTRACTS AND/OR ESTIMATES AND INVOICES FOR ALL WORK
 INCLUDING STRUCTURAL, ARCHITECTURAL, INTERIOR FINISHES,
 MECHANICAL, ELECTRICAL, PLUMBING, DESIGN FEES, AND
 OVERHEAD AND PROFIT.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 3 Status P Date 2019-07-30 Cont ID  
Sent By shill Date 2019-07-30 Time 12:19 Rev Time 0.00
Received By shill Date 2019-07-30 Time 12:19 Sent To  
Notes
2019-07-30 15:47:26REPLACEMENT COST VALUE LESS DEPRECIATION $1,239,438;
 CUMULATIVE 5 YEAR IMPROVEMENTS $575,055 (46%); NOT A
 SUBSTANTIAL IMPROVEMENT
  
  
 PERMIT 18090764 SCOPE WAS SAME AS 19050603; REVOKED
  

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 2 Status F Date 2019-07-26 Cont ID  
Sent By shill Date 2019-07-25 Time 17:24 Rev Time 0.00
Received By shill Date 2019-07-25 Time 17:24 Sent To  
Notes
2019-07-25 17:25:01****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 SEND ADDITIONAL INFORMATION VIA EMAIL AS DISCUSSED
  
 1. SEE PREVIOUS BUILDING COMMENTS REGARDING FLOOD
 PREVENTION REQUIREMENTS.
  
 BASED ON INFORMATION PROVIDED:
  
 DEPRECIATED BUILDING VALUE ESTIMATE: $1,239,438
  
 CUMULATIVE 5 YEAR IMPROVEMENTS, INCLUDING THE TWO
 PERMITS UNDER REVIEW: $650,055 (SEE BELOW)
  
 SINCE THIS THE 5 YEAR CUMULATIVE IMPROVEMENTS EXCEED
 50%, THIS IS CONSIDERED A SUBSTANTIAL IMPROVEMENT AND
 THE BUILDING NEEDS TO BE BROUGHT INTO COMPLIANCE.
 ALTERNATIVELY, PLEASE REFER TO THE FEMA DOCUMENTS FOR
 ALTERNATE METHODS FOR DETERMINING VALUE OF THE
 STRUCTURE.
  
  
 $326,480.00 19050604 APPLIED COM-INT
 $240,075.00 19050603 APPLIED COM-INT
  19040350 PRINTED MECH-SUB
  19030731 PRINTED ELEC-SUB
 $8,500.00 19030481 PRINTED DEMO-INT
  19030417 PRINTED PLUMB-SUB
 $75,000.00 18090764 PRINTED COM-REMOD
  18040653 CLOSED RECORDS
 $650,055.00
  
 $1,721,442.00 REPLACEMENT COST (INCLUDE 1ST FLOOR
 PARKING LOT INTEGRAL TO THE FIRST FLOOR)
 $482,003.76 DEPRECIATION, 28%
  
 $1,239,438.24 DEPRECIATED VALUE OF BUILDING
  
 52%
  

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 1 Status F Date 2019-07-09 Cont ID  
Sent By shill Date 2019-07-09 Time 13:26 Rev Time 0.00
Received By shill Date 2019-07-09 Time 13:26 Sent To  
Notes
2019-07-09 13:26:20SEE BUILDING COMMENTS
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-06-24 Cont ID  
Sent By tklarge Date 2019-06-24 Time 07:20 Rev Time 0.00
Received By tklarge Date 2019-06-21 Time 06:42 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-05-22 Cont ID  
Sent By tklarge Date 2019-05-22 Time 13:05 Rev Time 0.00
Received By tklarge Date 2019-05-16 Time 11:48 Sent To  
Notes
2019-05-22 10:24:261) SHT. A.08 - DETAIL #6 - THE LAVATORY IN THE
 ACCESSIBLE TOILET ROOM CANNOT ENCROACH INTO THE CLEAR
 FLOOR SPACE FOR THE WATER CLOSET. 2017 FBC- ACCESS.
 SEC. 604.3.2.
 2) SHT. A.08 - DETAIL #2 - THE TOILET PAPER DISPENSER
 SHALL BE LOCATED 7-9 INCHES FROM THE FRONT OF THE
 TOILET BOWL TO THE CENTERLINE OF THE TOILET PAPER
 DISPENSER.THE DISPENSER SHALL BE LOCATED A MINIMUM OF
 15 INCHES AND A MAXIMUM OF 48 INCHES ABOVE THE
 FLOOR2017 FBC-ACCESS. SEC.604.7.
 3) SHT. A.08 - THE COAT HOOK SHALL BE LOCATED A MAXIMUM
 OF 48 INCHES ABOVE THE FINISH FLOOR PER 2017
 FBC-ACCESS. SEC. 603.4. THE PLAN SHOWS 54 INCHES.
 4) SHT. A.08 - THE GRAB BARS SHALL BE MEASURED TO THE
 TOP OF THE GRIPPING SURFACE FROM THE FINISH FLOOR. 2017
 FBC-ACCESS. SEC.609.4.
 5) SHT. A.08 - ADA KEY NOTE #11 - THE PLASTIC LAMINATE
 SHALL BE AT A HEIGHT NOT LESS THAN 4 FEET. 2017 FBC
 S3C. 2110.2.2.
 6) THE LOCATION OF THE REAR AND SIDE GRAB BARS SHALL
 COMPLY WITH 2017 FBC-ACCESS. SEC. 604.5.SHOW THE
 DIMENSIONS ON THE PLANS.
 7) SHOW THE LENGTH AND WIDTH DIMENSIONS OF THE HANDICAP
 ACCESSIBLE TOILET ROOMS ON THE PLANS. WPB AMEND. TO FBC
 SEC. 107.2.1.
 8) SHOW THE LENGTH AND WIDTH DIMENSIONS OF THE CLEAR
 FLOOR SPACES FOR THE HANDICAP ACCESSIBLE PLUMBING
 FIXTURES ON THE FLOOR PLAN.2017 FBC-ACCESS. SEC.305,
 306,
 9) TEMPERED WATER IS REQUIRED TO THE LAVATORIES PER
 2017 FBC-PLUMBING SEC.416.5. TEMPERED WATER SHALL BE
 SUPPLIED THROUGH A WATER TEMPERATURE LIMITING DEVICE
 THAT CONFORMS TO ASSE 1070
 10) THIS OCCUPANCY REQUIRES A MOP SINK PER TABLE 403.1
 OF THE 2017 FBC-PLUMBING. THE "MOP SINK" SHOWN ON THE
 PLANS IS ACTUALLY A SHOWER SHOWN IN THE NEW
 BATHROOM.SEE SHTS. A.08 & P.02. PROVIDE A MOP SINK AND
 SHOW THE LOCATION ON THE PLANS AND SHOW THE MOP SINK ON
 THE WATER AND SANITARY RISERS. WPB AMEND. TO FBC SEC.
 107.2.1.
 11) SHT A.08 CALLS OUT A MOP SINK DETAIL BUT THE
 PLUMBING DRAWINGS CALL OUT A SHOWER. WHICH IS IT? IF IT
 IS A SHOWER IT SHALL BE HANDICAP ACCESSIBLE WITHOUT A
 CURB AND COMPLY WITH THE 2017 FBC-ACCESS. CODE
 SECS.608.2.1, 608.3.1, 608.5.1, 610.3. WHICH IT DOES
 NOT. CLARIFY.
 12) THE MAIMUM HEIGHT OF THE SINK CABINET IN THE BREAK
 ROOMS SHALL BE 34 INCHES ABOVE THE FINISH FLOOR. 2017
 FBC-ACCESS. SEC.606.3.
 13) THE BREAK ROOM SINK ON THE 2ND FLOOR IS NOT SHOWN
 ON THE SANITARY OR WATER RISER.WPB AMEND. TO FBC SEC.
 107.2.1.
 14) THE WATER HEATER SHALL BE SHOWN ON THE WATER RISER.
 WPB AMEND. TO FBC SEC. 107.2.1.
 15) THE DRINKING FOUNTAINS SHALL COMPLY WITH 2017
 FBC-ACCESS. SECS.602.2, 602.4, 602.7, 306.3, 306.2.1.
 16) FLUSH CONTROLS FOR THE ACCESSIBLE WATER CLOSET
 SHALL COMPLY WITH 2017 FBC-ACCESS. SEC. 604.6.
 17) THE BREAK ROOM SINKS SHALL BE PROVIDED WITH CLEAR
 FLOOR SPACE COMPLYING WITH 2017 FBC-ACCESS. SECS.
 606.2, 305.
 18) A BACKFLOW DEVICE IS REQUIRED FOR THE ICE MACHINE
 IN REFRIGERATOR IF ONE PROVIDED. PER FBC PL 608.3
 19) THE WATER FOUNTAIN ON THE 2ND FLOOR SHALL CONNECT
 TO BUILDING DRAIN DOWN STREAM OF THE BATHROOM GROUP.
 PER FBC- PLUMBING SEC. 912.1
 20) SHT. A.08 DETAIL #2 SHOWS A MOP SINK BUILT IN PLACE
 WITH LATICRETE HYDROBAN WATER PROOFING BUT THE PLUMBING
 SCHEDULE IS LISTING A PRE FAB SHOWER UNIT. CLARIFY
  
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  
  
  
  
  
  
  
  
  
 11. SHT. A.08 DETAIL #2 SHOWS A MOP SINK BUILT IN PLACE
 WITH LATICRETE HYDROBAN WATER PROOFING THE PLUMBING
 SCHEDULE IS LISTING P-5 PRE FAB SHOWER PLEASE
 CLARIFY.PER WPB AMEND TO FBC 107.2.1
  
 .
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status P Date 2019-07-11 Cont ID  
Sent By jroach Date 2019-07-11 Time 08:53 Rev Time 0.00
Received By jroach Date 2019-07-11 Time 08:53 Sent To  
Notes
***NONE***