| 2019-06-04 09:31:13 | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 19050603 |
| | ADD: 1217 S FLAGLER DR. 2ND FLOOR |
| | CONT: NICK RAICH BUILDING CORP. |
| | TEL: 561-659-9347 |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION. |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: TUES. JUNE 04/ 2019 |
| | ACTION: DENIED |
| | |
| | 1) THIS BUILDING IS LOCATED IN A FLOOD ZONE. ARTICLE |
| | XVII ORDINANCES ARTICLE XVII FLOOD PREVENTION & CONTROL |
| | FBC BUILDING 1612 AND CITY OF WPB CODE OF SECTION |
| | 94-546. STRUCTURE IS LOCATED IN AN "AE" FLOOD ZONE. A |
| | FLOOD ELEVATION CERTIFICATE WILL BE REQUIRED. PLEASE |
| | REVIEW CITY ORDINANCE FOR THE CITY REQUIREMENTS REQUIRE |
| | AFTER OCT. 11/ 2017 AN ADDITIONAL ONE FOOT OF FREE |
| | BOARD WILL BE REQUIRED OR (2) FEET ABOVE BASE FLOOD. |
| | BASE FLOOD ELEVATION (BFE) 6? NAVD88 OR FIS 5.7?. THE |
| | COMBINED VALUE OF THIS BUILDING AND LOT ACCORDING TO |
| | THE PALM BEACH COUNTY PROPERTY APPRAISERS OFFICE IS |
| | $1,300,000.00 DOLLARS. |
| | |
| | SUBSTANIAL IMPROVEMENT. SECTION 94-546 PROVISIONS FOR |
| | FLOOD HAZARD REDUCTION. (A)(3) ANY ALTERATION, REPAIR, |
| | RECONSTRUCTION, OR IMPROVEMENTS TO A PROPERTY WHICH THE |
| | CUMULATIVE COST FOR ANY FIVE YEAR PERIOD EQUALS OR |
| | EXCEEDS 50 % OF THE BUILDING VALUE AT THE COMMENCEMENT |
| | OF THE FIVE YEAR PERIOD SHALL MEET THE REQUIREMENTS OF |
| | NEW CONSTRUCTION AS CONTAINED IN THIS ARTICLE. |
| | TO DETERMINE IF THE SUBSTANTIAL IMPROVEMENT VALUE FOR |
| | THIS PROJECT HAS BEEN MET WE CANNOT DETERMINE THIS |
| | SINCE IN THIS CASE THE PALM BEACH COUNTY PROPERTY |
| | APPRAISERS OFFICE DOES NOT HAVE THE VALUE FOR THE |
| | BUILDING BROKEN OUT OF THE OVERALL VALUE OF THE |
| | ASSESSED PROPERTY. THE OWNER OR TENANT OF THE BUILDING |
| | WILL NEED TO PROVIDE AN ASSESSED VALUE FOR THE BUILDING |
| | ITSELF. |
| | |
| | THE PROPOSED IMPROVEMENT OVER THE LAST 5 YEARS, |
| | INCLUDING THE CURRENT PROPOSED IMPROVEMENTS |
| | ($413,740.00) APPEARS TO BE A SUBSTANTIAL IMPROVEMENT |
| | BASED ON PROPERTY APPRAISER VALUATION FOR THE STRUCTURE |
| | & LAND VALUE ($1,300,000.00 DALLORS IN VALUE). IF THIS |
| | IS A SUBSTANTIAL IMPROVEMENT, THE STRUCTURE IS TO BE |
| | BROUGHT INTO COMPLIANCE (BFE 6.0' + 2.0?) NAVD88 FOR |
| | THE LOWEST FINISHED FLOOR, & ALL MECHANICAL EQUIPMENT). |
| | APPLICANT MAY PROVIDE DOCUMENTATION FOR VALUATION OTHER |
| | THAN PROPERTY APPRAISER; PLEASE SEE FEMA TECHNICAL |
| | BULLETIN 758, SECTION 4.5: |
| | HTTPS://WWW.FEMA.GOV/MEDIA-LIBRARY-DATA/20130726-1734-2 |
| | 5045-2915/P_758_COMPLETE_R3.PDF |
| | |
| | 2) THE PROPOSED VALUE OF $45,000.00 DOLLARS SEAMS LOW |
| | FOR THE SCOPE OF WORK SHOWN FOR THE 2ND FLOOR LEVEL. |
| | 108.3* BUILDING PERMIT VALUATION. |
| | IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE |
| | CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE, |
| | ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS |
| | APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE |
| | PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES, |
| | VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL |
| | REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND |
| | SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE |
| | STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR |
| | FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR |
| | BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING |
| | COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. |
| | VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED |
| | DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES |
| | (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS |
| | FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE |
| | CONGRESS. |
| | |
| | THIS MAIN BUILDING PERMIT WILL INCLUDE THE FEES FOR THE |
| | MECHANICAL, ELECTRICAL, PLUMBING & ROOFING PERMITS. |
| | WHEN THE GENERAL CONTRACTOR COMES IN FOR A BUILDING |
| | PERMIT WITH THE SIGNED PERMIT APPLICATION FORM BY THE |
| | QUALIFIER AND OWNER AND BRINGS IN THE LISTED |
| | SUB-PERMITS M-E-P & ROOFING PERMITS SIGNED BY THE |
| | QUALIFIER OF EACH COMPANY, THEIR INSURANCES AND |
| | LICENSURE UP TO DATE, THE M-E-P AND ROOFING PERMITS ARE |
| | FREE OF CHARGE. IF THE M-E-P & ROOFING PERMITS COME IN |
| | LATER THERE WILL BE AN $80.00 ADMINISTRATIVE FEE FOR |
| | EACH PERMIT. |
| | |
| | ALL OTHER PERMITS FIRE SPRINKLER, FIRE ALARM, RACK |
| | STORAGE, EXHAUST HOODS, ANSUL SYSTEMS OR ALTERNATIVE |
| | AUTOMATIC FIRE-EXTINGUISHING SYSTEMS, WALK IN COOLERS & |
| | FREEZERS, ALL LOW VOLTAGE PERMITS, GENERATORS & FUEL |
| | TANKS, GAS PERMIT, POOL, JACUZZI AND ASSOCIATED |
| | SUB-PERMITS, AWNING, SCREEN ENCLOSURES, CANOPY, FENCE, |
| | LANDSCAPE, IRRIGATION, AUGER CAST PILE AND OR |
| | FOUNDATION OR STRUCTURE ONLY PERMIT WILL BE SEPARATE |
| | REVIEWS AND ASSOCIATED FEES WITH EACH PERMIT. |
| | PLEASE PROVIDE AN ITEMIZED LIST AND SUBTRACT THESE LINE |
| | ITEMS AND THEIR VALUE FROM THE OVERALL BUILDING VALUE |
| | STATED ON THE PERMIT APPLICATION FOR THIS PROJECT. THE |
| | REMAINING BALANCE WILL BE AFFECTIVELY THE VALUE OF THE |
| | BUILDING YOU WILL BE PAYING FOR THIS PERMIT. THE |
| | BUILDING DEPARTMENT DOES NOT WANT TO COLLECT TWICE FOR |
| | THE VALUE OF THESE SUB-PERMITS NOT COVERED UNDER THE |
| | PRIME OR MASTER PERMIT. |
| | |
| | 3) THE TITLE BLOCK IS CONFUSING AS TO THE LOCATION OF |
| | WORK TO BE ACCOMPLISHED UNDER THIS PERMIT. AT 1ST |
| | GLANCE THE COVERSHEET, A.01 IT WOULD APPEAR ALL WORK ON |
| | ALL 8 ARCHITECTURAL SHEETS WOULD BE ON THE 3RD FLOOR. |
| | ON SHEETS A.02-A0.4 THESE SHEETS STILL SAY SALES OFFICE |
| | 3RD FLOOR AS WELL AS 2ND FLOOR PLAN. (4) SETS OF PLANS |
| | WERE BROUGHT IN MAKING IT MORE CONFUSING ALL PLANS |
| | LABELED THE SAME WAY FOR THE 2 PERMITS THE 2ND FLOOR & |
| | 3RD FLOOR. PLEASE CORRECT THE TITLE BLOCK FOR THE COVER |
| | SHEET TO INCLUDE THE 2ND FLOOR AND AS TO WHERE THE WORK |
| | IS GOING TO BE COMPLETED FOR THE 2ND FLOOR FOR SHEETS |
| | A.02-A0.4, NO REFERENCE TO THE 3RD FLOOR PLEASE. |
| | 2017 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION 107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE OF |
| | SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND |
| | EXTENT OF THE WORK PROPOSED. |
| | |
| | 4) SHEET A.02 & A.03 LIFE SAFETY SHEET: |
| | 4A) EXISTING DOORWAY INTO THE COPY ROOM DOES NOT HAVE |
| | THE 18 INCHES MANEUVERING CLEARANCE ON THE LATCH SIDE |
| | OF THE DOORWAY. |
| | |
| | 2017 FBC-ACCESS. CODE 404.2.4 MANEUVERING CLEARANCES. |
| | DOORS. MINIMUM MANEUVERING CLEARANCES AT DOORS AND |
| | GATES SHALL COMPLY WITH 404.2.4. MANEUVERING CLEARANCES |
| | SHALL EXTEND THE FULL WIDTH OF THE DOORWAY AND THE |
| | REQUIRED LATCH SIDE FOR SIDE CLEARANCE. |
| | ACCESS CODE 404.2.4.1 SWINGING DOORS AND GATES. |
| | SWINGING DOORS AND GATES SHALL HAVE MANEUVERING |
| | CLEARANCES COMPLYING WITH TABLE 404.2.4.1. |
| | |
| | 4B) THE 2ND ISSUE WITH THE EXISTING DOORWAY INTO THE |
| | COPY ROOM AND THE LOCATION OF THE COLUMN, THE DOORWAY |
| | LOCATION CREATES A RECESSED DOORWAY AND NO MANEUVERING |
| | CLEARANCE PER ACCESSIBILITY CODE SECTION 404.2.4.3 AND |
| | FIGURE 404.2.4.3. |
| | |
| | 4C) NEW DOORWAY INTO THE CONFERENCE ROOM HAS THE SAME 2 |
| | ISSUES AS THE COPY ROOM DOOR IN LOCATION TO THE COLUMN. |
| | 2017 FBC-ACCESS. CODE 404.2.4 MANEUVERING CLEARANCES. |
| | DOORS. MINIMUM MANEUVERING CLEARANCES AT DOORS AND |
| | GATES SHALL COMPLY WITH 404.2.4. MANEUVERING CLEARANCES |
| | SHALL EXTEND THE FULL WIDTH OF THE DOORWAY AND THE |
| | REQUIRED LATCH SIDE FOR SIDE CLEARANCE. |
| | ACCESS CODE 404.2.4.1 SWINGING DOORS AND GATES. |
| | SWINGING DOORS AND GATES SHALL HAVE MANEUVERING |
| | CLEARANCES COMPLYING WITH TABLE 404.2.4.1. |
| | ACCESSIBILITY CODE SECTION 404.2.4.3 AND FIGURE |
| | 404.2.4.3. THE CONFERENCE ROOM DOOR IN LOCATION TO THE |
| | COLUMN CREATES A RECESSED DOORWAY. |
| | |
| | 4D) THE NEW OFFICE # 2 HAS FURNITURE IN THE REQUIRED |
| | CLEAR MANEUVERING SPACE LATCH SIDE OF THE DOORWAY. |
| | ACCESS CODE 404.2.4.1 SWINGING DOORS AND GATES. |
| | SWINGING DOORS AND GATES SHALL HAVE MANEUVERING |
| | CLEARANCES COMPLYING WITH TABLE 404.2.4.1. |
| | DISCREPANCY IN PLANS SHEET A.02 VERSES SHEETS P.01 & |
| | P.02. SHEET A.02 INDICATES IN THE A.02 SHEET A MOP SINK |
| | IN THE ACCESSIBLE BATHROOM/ RESTROOM, WHEREAS P1 & P2 |
| | CALL THIS FIXTURE OUT AS P-5 AN ADA PREFABRICATED |
| | SHOWER ENCLOSURE BY OTHERS. DISCREPANCY IN PLANS, |
| | ADDITIONAL INFORMATION IS REQUIRED. 107.2.1.2. |
| | 4E)(1) THE DETAIL OF THE BREAK ROOM CABINETS AND SINK |
| | DOES NOT INDICATE THE HEIGHT OF THE BASE CABINETS NOR |
| | THE HEIGHT OF THE RIM OF THE SINK IN THE BASE CABINETS. |
| | PLEASE SHOW COMPLIANCE WITH 2017 ACCESSIBILITY CODE |
| | SECTION 606.3 HEIGHT. SINKS SHALL BE INSTALLED WITH THE |
| | FRONT OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 |
| | INCHES MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. |
| | |
| | 4E)(2) PLEASE ALSO SHOW COMPLIANCE WITH THE 2017 |
| | FBC-ACCESS. CODE SECTION 606.2. A CLEAR FLOOR SPACE |
| | COMPLYING WITH 305, POSITIONED FOR A FORWARD APPROACH, |
| | AND KNEE AND TOE CLEARANCE COMPLYING WITH 306 SHALL BE |
| | PROVIDED. |
| | |
| | 4F) THE BREAK ROOM SHOWS 4 CHAIRS AND SHELF BUT NO |
| | HEIGHT IS GIVEN FOR THE HEIGHT OF THE TABLE TOP/ SHELF. |
| | THE LIFE SAFETY SHEET DOES NOT SHOW COMPLIANCE WITH THE |
| | 2014 FBC-ACCESSIBILITY CODE; 226.1 WHERE DINING |
| | SURFACES ARE PROVIDED FOR THE CONSUMPTION OF FOOD OR |
| | DRINK, AT LEAST 5 PERCENT OF THE SEATING SPACES AND |
| | STANDING SPACES AT THE DINING SURFACES SHALL COMPLY |
| | WITH 902. |
| | 902.1 .DINING SURFACES AND WORK SURFACES SHALL COMPLY |
| | WITH 902.2 AND 902.3. ADVISORY 902.1. DINING SURFACES |
| | INCLUDE, BUT ARE NOT LIMITED TO, BARS, TABLES, LUNCH |
| | COUNTERS, AND BOOTHS. |
| | |
| | 4G) NEITHER A.02 OR A.03 GIVE A SECTION THROUGH THE |
| | CONFERENCE ROOM GLASS WALL OR DOORWAY. PLEASE SHOW |
| | COMPLIANCE WITH THE 2017 FBC-B SECTIONS: |
| | 2406.4 HAZARDOUS LOCATIONS. THE LOCATIONS SPECIFIED IN |
| | SECTIONS 2406.4.1 THROUGH 2406.4.7 SHALL BE CONSIDERED |
| | SPECIFIC HAZARDOUS LOCATIONS REQUIRING SAFETY GLAZING |
| | MATERIALS. |
| | |
| | 2406.4.2 GLAZING ADJACENT TO DOORS. GLAZING IN AN |
| | INDIVIDUAL FIXED OR OPERABLE PANEL ADJACENT TO A DOOR |
| | WHERE THE NEAREST VERTICAL EDGE OF THE GLAZING IS |
| | WITHIN A 24-INCH (610 MM) ARC OF EITHER VERTICAL EDGE |
| | OF THE DOOR IN A CLOSED POSITION AND WHERE THE BOTTOM |
| | EXPOSED EDGE OF THE GLAZING IS LESS THAN 60 INCHES |
| | (1524 MM) ABOVE THE WALKING SURFACE SHALL BE CONSIDERED |
| | A HAZARDOUS LOCATION. |
| | |
| | 2406.4.1 GLAZING IN DOORS. GLAZING IN ALL FIXED AND |
| | OPERABLE PANELS OF SWINGING, SLIDING AND BIFOLD DOORS |
| | SHALL BE CONSIDERED A HAZARDOUS LOCATION. |
| | |
| | |
| | 5) ACCESSIBLE RESTROOM/ BATHROOM DETAILS ARE FOUND ON |
| | SHEET A.08 3RD FLOOR PERMIT. |
| | |
| | 6) PLEASE PROVIDE A LETTER EITHER FROM THE CONTRACTOR |
| | OR DESIGNER OF RECORD ON THEIR LETTERHEAD WHERE UP TO |
| | 20 % OF THE CONTRACT VALUE IS GOING TO BE SPENT IN |
| | ACCESSIBLE UPGRADES TO THE PROJECT. IF ALL EXISTING |
| | CONDITIONS ARE COMPLETED (COMPLIED) BEFORE |
| | DISPROPORTIONATION COST IS MET A LETTER IS NOT |
| | REQUIRED. SHOW COMPLIANCE WITH THE: |
| | |
| | 2017 FBC-ACCESSIBILITY CODE SECTION 202.4.1 |
| | DISPROPORTIONATE COST.ALTERATIONS MADE TO PROVIDE AN |
| | ACCESSIBLE PATH OF TRAVEL TO THE ALTERED AREA WILL BE |
| | DEEMED DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN |
| | THE COST EXCEEDS 20% OF THE COST OF THE ALTERATION TO |
| | THE PRIMARY FUNCTION AREA. COSTS THAT MAY BE COUNTED AS |
| | EXPENDITURES REQUIRED TO PROVIDE AN ACCESSIBLE PATH OF |
| | TRAVEL MAY INCLUDE: (I) COSTS ASSOCIATED WITH PROVIDING |
| | AN ACCESSIBLE ENTRANCE AND AN ACCESSIBLE ROUTE TO THE |
| | ALTERED AREA; (II) COSTS ASSOCIATED WITH MAKING |
| | RESTROOMS ACCESSIBLE, SUCH AS INSTALLING GRAB BARS, |
| | ENLARGING TOILET STALLS, INSULATING PIPES, OR |
| | INSTALLING ACCESSIBLE FAUCET CONTROLS; (III) COSTS |
| | ASSOCIATED WITH PROVIDING ACCESSIBLE TELEPHONES, SUCH |
| | AS RELOCATING THE TELEPHONE TO AN ACCESSIBLE HEIGHT, |
| | INSTALLING AMPLIFICATION DEVICES, OR INSTALLING A TEXT |
| | TELEPHONE (TTY); (IV) COSTS ASSOCIATED WITH RELOCATING |
| | AN INACCESSIBLE DRINKING FOUNTAIN. |
| | |
| | |
| | 7A) NEW MECHANICAL UNITS ARE BEING ADDED AS INDICATED |
| | IN THE MECHANICAL SHEETS, PLEASE SHOW WHERE THE |
| | LOCATION WILL BE? IF ROOFTOP SHOW COMPLIANCE WITH: 2017 |
| | FBC-B 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA |
| | DEPARTMENT OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE |
| | 61G20-3.005, RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY |
| | OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE |
| | PRODUCT APPROVALS: (31)(G) PRE-ENGINEERED A/C STANDS. |
| | |
| | 7B) W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE |
| | PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03 |
| | SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE |
| | ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING |
| | ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC.. |
| | |
| | 7C) FOR ROOF TOP A/C STAND PRODUCT APPROVAL. THE |
| | PRODUCT APPROVAL IS TO BE REVIEWED BY THE DESIGNER OF |
| | RECORD. PLEASE IDENTIFY THE FOLLOWING REQUIREMENTS |
| | CALCULATING THE AREA (SIDE VIEW) OF THE ROOF TOP |
| | COMPRESSORS, CONFIGURATION ON STAND, THE MEAN ROOF |
| | HEIGHT OF THE STAND AND COMPRESSORS, WEIGHT, CIRCLED |
| | THE DESIGN PARAMETERS IN THE TABLES, ANCHORS AND UPLIFT |
| | VERSES MOMENT FOR THE UNIT TO THE STAND AND THE STAND |
| | TO THE ROOF. THE PRODUCT APPROVAL IS TO BE REVIEWED BY |
| | THE DESIGNER OF RECORD, APPROVED BEFORE SUBMISSION TO |
| | THE BUILDING DEPARTMENT. 107.2.1.2 ADDITIONAL |
| | INFORMATION IS REQUIRED. |
| | |
| | 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE |
| | THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED |
| | DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE |
| | MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS |
| | AND INFORMATION LACKING UNDER THE PRIOR REVIEW. |
| | |
| | JAMES A. WITMER BN, PX, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| 2019-05-16 15:12:53 | 1) SHT.A.03 - DETAIL #2 - THE HEIGHT OF THE BREAK ROOM |
| | SINK ON THE 2ND AND 3RD FLOOR SHALL BE 34 INCHES MAX. |
| | 2017 FBC-ACCESS. SEC.606.3. |
| | 2) CLEAR FLOOR SPACE SHALL BE PROVIDED AT THE BREAK |
| | ROOM SINKS COMPLYING WITH 2017 FBC-ACCESS.SEC. 606.2. |
| | 3) SHT. A.02 REFERS TO DETAIL 6 ON SHT. A.05 FOR ADA |
| | BATH DETAIL.THERE IS NO SUCH DETAIL ON SHT. A.05. THE |
| | DETAIL IS ON SHT. A.08. REVISE THE NOTE. |
| | 4) |
| | |
| | REVIEW IS INCOMPLETE. |
| | |