Plan Review Details - Permit 19050596
Plan Review Stops For Permit 19050596
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-07-23 Cont ID  
Sent By jbrooks Date 2019-07-23 Time 08:34 Rev Time 0.00
Received By jbrooks Date 2019-07-23 Time 08:34 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-05-28 Cont ID  
Sent By jduprey Date 2019-05-28 Time 09:11 Rev Time 0.00
Received By jduprey Date 2019-05-28 Time 09:11 Sent To E
Notes
2019-05-28 09:25:52BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 JOSEAN A. DUPREY E.I., PX, BN
 BUILDING PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6716
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. THE DRAWING SHEETS S001 AND S101 WERE PROVIDED WITH
 A COPY OF THE ENGINEER'S SIGNATURE. PLEASE PROVIDE THIS
 DRAWINGS SHEETS WITH THE ORIGINAL ENGINEER'S SIGNATURE.
  
 CHAPTER 61G15-23.003(1), F.A.C., THE LICENSEE SHALL
 SIGN BY HAND AN ORIGINAL OF THE LICENSEE?S SIGNATURE ON
 EACH PAGE REQUIRED TO BE SEALED. A SCANNED, FACSIMILE,
 DIGITALLY CREATED OR COPIED IMAGE OF THE LICENSEE?S
 SIGNATURE SHALL NOT BE USED.
  
 2. THE STRUCTURAL CALCULATIONS DOCUMENT WAS PROVIDED
 WITH AN ORIGINAL SIGNATURE BUT ONLY ON THE COVER PAGE
 AND NO INDEX SHEET WAS PROVIDED, PLEASE PROVIDE INDEX
 SHEET ACCORDINGLY WITH RULE 61G15?23.00 .
  
 61G15?23.001 SIGNATURE, DATE AND SEAL SHALL BE AFFIXED.
 (B) ENGINEERING SPECIFICATIONS AND CALCULATIONS. AN
 INDEX SHEET SHALL BE USED AND SHALL BE SIGNED, DATED
 AND SEALED BY EACH PROFESSIONAL ENGINEER WHO IS IN
 RESPONSIBLE CHARGE OF ANY PORTION OF THE ENGINEERING
 SPECIFICATIONS OR CALCULATIONS.
 1. THE INDEX SHEET MUST BE SIGNED, DATED AND SEALED BY
 THOSE PROFESSIONAL ENGINEERS IN RESPONSIBLE CHARGE OF
 THE PRODUCTION AND PREPARATION OF EACH SECTION OF THE
 ENGINEERING SPECIFICATIONS OR CALCULATIONS, WITH
 SUFFICIENT INFORMATION ON THE INDEX SHEET SO THAT THE
 USER WILL BE AWARE OF EACH PORTION OF THE
 SPECIFICATIONS OR CALCULATIONS FOR WHICH EACH
 PROFESSIONAL ENGINEER IS RESPONSIBLE.
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-07-22 Cont ID  
Sent By fgiaquin Date 2019-07-22 Time 06:07 Rev Time 0.00
Received By fgiaquin Date 2019-07-22 Time 05:50 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-06-05 Cont ID  
Sent By fgiaquin Date 2019-06-05 Time 06:42 Rev Time 0.00
Received By fgiaquin Date 2019-06-05 Time 06:34 Sent To I
Notes
2019-06-05 06:42:35ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED AND
 SEALED BY A LICENSED DESIGN PROFESSIONAL OR SIGNED BY
 THE ELECTRICAL CONTRACTOR QUALIFIER. PROVIDE CLEAR
 LOCATION AND DIAGRAMS OF EACH SIGN. FS 471.003(2)(H);
 471.025; WPB FBC 107.2.1, 107.3.5
  
 INFORMATIONAL NOTE: PROVIDE NOTE ON PLANS INDICATING
 SIGNS WILL BE CONTROLLED BY A ASTROMICAL TIMECLOCK PER
 EXTERIOR LIGHTING CONTROLS REQUIREMENTS OF THE FBC EC
 405.2.4
  
 DISCONNECT REQUIREMENTS FOR EACH SIGN MUST CONFORM TO
 NEC 600.6A1.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-07-23 Cont ID  
Sent By jbrooks Date 2019-07-23 Time 08:35 Rev Time 0.00
Received By jbrooks Date 2019-07-02 Time 14:43 Sent To  
Notes
2019-07-12 13:12:39TO LMARCHAN
2019-07-03 14:43:29RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-06-05 Cont ID  
Sent By fgiaquin Date 2019-06-05 Time 06:42 Rev Time 0.00
Received By fgiaquin Date 2019-05-10 Time 11:30 Sent To  
Notes
2019-05-23 13:55:44TO L MARCHAN
2019-05-13 11:30:28ROUTED TO ZONING INBOX

Review Stop Z ZONING
Rev No 2 Status P Date 2019-07-12 Cont ID  
Sent By aaponte Date 2019-07-12 Time 13:12 Rev Time 0.00
Received By aaponte Date 2019-07-12 Time 13:12 Sent To E
Notes
2019-07-12 13:12:23IDENTITY SIGN FOR RESIDENTIAL BUILDING

Review Stop Z ZONING
Rev No 1 Status F Date 2019-05-23 Cont ID  
Sent By aaponte Date 2019-05-23 Time 13:50 Rev Time 0.00
Received By aaponte Date 2019-05-23 Time 13:50 Sent To B
Notes
2019-05-23 13:55:211. PLEASE CLEARLY INDICATE IN THE ELEVATION THE
 LOCATION OF THE CANOPY SIGN. IS THE CANOPY SIGN AT THE
 RESIDENTIAL ENTRANCE LOCATED AT OLIVE AVENUE AND 2ND
 STREET? IF SO, BOTH SIGNS WOULD BE CONSIDERED THE
 IDENTITY SIGNS FOR THE RESIDENTIAL BUILDING AND NO
 ADDITIONAL SIGN WOULD BE PERMITTED EXCEPT THE SIGNS FOR
 THE GROUND FLOOR COMMERCIAL TENANTS.
 FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA
 APONTE AT 561-822-1439.