| Plan Review Stops For Permit 19050525 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2019-08-12 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2019-08-12 |
Time |
17:27 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2019-08-12 |
Time |
17:27 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2019-07-10 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2019-07-10 |
Time |
07:07 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2019-07-10 |
Time |
06:54 |
Sent To |
|
|
| Notes |
| 2019-07-10 07:17:45 | ***CORRECTIONS*** | | | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6673 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | 3RD BUILDING REVIEW DENIED: | | | | | | FBC A 202.4 PLEASE COMPLY WITH THE REQUIREMENTS OF THE | | | ACCESSIBILITY CODE SECTION 202.4, 202.4.1, AND 202.4.2 | | | REGARDING THE DRINKING FOUNTAIN AREA AS NOTED IN THE | | | PLUMBING REVIEW COMMENTS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2019-06-27 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2019-06-27 |
Time |
08:15 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2019-06-27 |
Time |
08:14 |
Sent To |
|
|
| Notes |
| 2019-06-27 10:10:49 | ***CORRECTIONS*** | | | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6673 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | 2ND BUILDING REVIEW DENIED: | | | | | | 1. A SEPERATE PERMIT IS REQUIRED FOR THE 9TH FLOOR. | | | APPROVED WITH PROVISO. CONTRACTOR TO APPLY; APPLICATION | | | IN PROGRESS. | | | | | | 2. REVISE PLAN TO SHOW HOW THE ELEVATOR LOBBY SHOWN | | | COMPLIES WITH FBC B 3006.3. | | | APPROVED WITH PROVISO. ADJUST WALL ADJACENT TO LOBBY | | | DOOR TO COMPLY WITH ACCESSIBILE MANEUVERABILITY(WALL | | | NEEDS TO HAVE AN 18" HORIZONTAL MEASUREMENT). | | | | | | 3. PAGE A0.03 THE COMMON PATH OF TRAVEL IS NOT CLEAR. | | | PROVIDE INFORMATION ON HOW THE COMMON PATH OF TRAVEL IS | | | AT 68'. | | | FAIL. | | | | | | 4. APPROVED | | | | | | 5. APPROVED | | | | | | 6. APPROVED | | | | | | 7. APPROVED |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2019-06-05 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2019-06-05 |
Time |
09:15 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2019-06-05 |
Time |
08:39 |
Sent To |
|
|
| Notes |
| 2019-06-05 09:15:51 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | 1. A SEPARATE PERMIT IS REQUIRED FOR THE 9TH FLOOR. | | | CONTACT ME AFTER ALL REVIEWS HAVE PASSED TO COORDINATE. | | | | | | 2. REVISE PLAN TO SHOW HOW THE "ELEVATOR LOBBY" SHOWN | | | COMPLIES WITH FBC B 3006.3. IF THE ELEVATORS ARE | | | PRESSURIZED, PLEASE ADVISE VIA EMAIL PRIOR TO | | | RESUBMITTING. | | | | | | 3. A0.03, COMMON PATH OF TRAVEL NOT CLEAR. OCCUPANCY | | | ANALYSIS STATES THAT THIS IS 68', BUT IT APPEARS THAT | | | IT IS 140'. SEE FBC CHAPTER 2, DEFINITION OF COMMON | | | PATH. | | | | | | 4. A0.03, ROOM 806, TAC WORKSTATION ADA, REVISE PLAN TO | | | SHOW COMPLIANCE, FBC A 904. NO DIMENSIONS FOR THE | | | ACCESSIBLE ROUTE INTO AND OUT OF THE SPACE WERE | | | PROVIDED; PROVIDE DIMENSIONS AND DETAIL FOR THE SERVICE | | | COUNTER. | | | | | | 5. REVISE PLAN TO CLARIFY AREAS WHICH WOULD BE REQUIRED | | | TO COMPLY WITH FBC A 808 (A0.03 SHOWS A "GRAND JURY"). | | | | | | 6. A0.02 ROOM 806 SHOWS "SELF HELP" STATIONS. PROVIDE A | | | DETAIL, FBC A 904. | | | | | | 7. SEE FIRE COMMENTS REGARDING MECHANICAL ROOM RATING; | | | CHECK ALL. | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2019-06-05 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2019-06-05 |
Time |
09:55 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2019-06-05 |
Time |
09:55 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2019-06-20 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2019-06-20 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2019-06-20 |
Time |
13:17 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2019-05-20 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2019-05-20 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2019-05-20 |
Time |
14:56 |
Sent To |
|
|
| Notes |
| 2019-05-20 15:24:29 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | 1) SHEET A 1.11 - THERE IS A DOUBLE DOOR INDICATED AT | | | THE MECHANICAL ROOM WITHIN A RATED WALL; HOWEVER, THERE | | | IS NO INDICATION ON THE DOOR SCHEDULE THAT THESE DOORS | | | HAVE FIRE RATING OR SELFCLOSING. | | | | | | PLEASE REVIEW AND COORECT OR JUSTIFY. | | | | | | | | | | | | 2) SHEET A 1.12 - THERE IS A DOUBLE DOOR INDICATED AT | | | THE MECHANICAL ROOM WITHIN A RATED WALL; HOWEVER, THERE | | | IS NO INDICATION ON THE DOOR SCHEDULE THAT THESE DOORS | | | HAVE FIRE RATING OR SELFCLOSING. | | | | | | PLEASE REVIEW AND COORECT OR JUSTIFY. | | | | | | | | | | | | 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | | | | 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2019-08-14 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2019-08-14 |
Time |
11:30 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2019-07-30 |
Time |
16:14 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2019-07-10 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2019-07-10 |
Time |
07:18 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2019-07-01 |
Time |
14:03 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2019-06-27 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2019-06-27 |
Time |
16:00 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2019-06-19 |
Time |
13:11 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2019-06-05 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2019-06-05 |
Time |
11:58 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2019-05-10 |
Time |
10:48 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2019-06-27 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2019-06-27 |
Time |
14:40 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2019-06-27 |
Time |
13:25 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2019-06-05 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2019-06-05 |
Time |
10:54 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2019-06-05 |
Time |
10:54 |
Sent To |
|
|
| Notes |
| 2019-06-05 11:02:17 | 1ST REVIEW FBC-2017 MECHANICAL | | | PERMIT #19050525 | | | 6/5/19 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | | 2017 | | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | | 2017 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SEPARATE PLANS AND PERMIT APPLICATION ARE REQUIRED | | | FOR THE WORK ON THE 9TH FLOOR. PLEASE AMEND THE WORK | | | DESCRIPTION ON THE PERMIT APPLICATION AND SEPARATE THE | | | PLANS OUT ACCORDINGLY- SECTION 107.2.1 WPB. | | | | | | 2) PLEASE PROVIDE A DETAILED ESTIMATE FOR THE WORK ON | | | THE 8TH FLOOR- SECTION 109.3 WPB. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2019-08-14 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2019-08-14 |
Time |
10:33 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2019-08-13 |
Time |
09:58 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2019-07-09 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2019-07-09 |
Time |
11:54 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2019-07-09 |
Time |
11:54 |
Sent To |
|
|
| Notes |
| 2019-07-09 11:56:53 | 3RD REVIEW: | | | 2017 FLORIDA BUILDING CODE 6TH EDITION | | | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH | | | EDITION | | | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH | | | EDITION | | | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH | | | EDITION | | | | | | PLUMBING COMMENTS: | | | | | | 1) THE PLUMBING PAGES CLEARLY SHOW NEW SANITARY AND | | | WATER PIPING TO THE WATER FOUNTAIN LOCATION. PLEASE | | | PROVIDE EXITING DEMO PLAN. I LOOKED INTO OUR RECORDS | | | FOR THAT BUILDING AND COULD NOT FIND ANY SHOWING A | | | WATER FOUNTAIN IN THAT LOCATION. AFTER DISCUSSING IT | | | WITH THE BUILDING OFFICIAL WE FEEL THAT THIS DOES NOT | | | FALL UNDER THE EXCEPTION AS BEING TECHNICALLY | | | INFEASIBLE. | | | | | | 2) ROBERT BROWN ASK IF THIS WORK WAS COMPLYING WITH FBC | | | ACC 202.4, 202.4.1, 202.4.2 PLEASE PROVIDE A COST BREAK | | | DOWN TO SHOW THAT A MIN OF 20% OF THE TOTAL COST OF THE | | | JOB IS BEING USED TO PROVIDE 1.AN ACCESSIBLE PATH OF | | | TRAVEL TO THE ALTERED AREA, 2. ACCESSIBLE REST ROOMS, | | | TELEPHONES, AND DRINKING FOUNTAINS SERVING THE ALTERED | | | AREA IN THAT ORDER. PER FBC ACC 202.4.1 | | | | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2019-06-27 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2019-06-27 |
Time |
10:51 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2019-06-26 |
Time |
12:14 |
Sent To |
|
|
| Notes |
| 2019-06-27 11:36:22 | 1ST REVIEW: | | | 2017 FLORIDA BUILDING CODE 6TH EDITION | | | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH | | | EDITION | | | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH | | | EDITION | | | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH | | | EDITION | | | | | | PLUMBING COMMENTS: PREVIOUS COMMENTS. | | | | | | 1. TWO WATER FOUNTAINS ARE REQUIRED THEY SHALL COMPLY | | | WITH FBC PL [BE] 410.3 PROVIDE HIGH AND LOW DRINKING | | | FOUNTAINS. WHERE DRINKING FOUNTAINS ARE REQUIRED, NOT | | | FEWER THEN TWO DRINKING FOUNTAINS SHALL BE PROVIDED. | | | ONE DRINKING FOUNTAIN SHALL COMPLY WITH THE | | | REQUIREMENTS FOR PEOPLE WHO USE A WHEELCHAIR AND ONE | | | DRINKING FOUNTAIN SHALL COMPLY WITH THE REQUIREMENTS | | | FOR STANDING PERSONS. | | | FBC ACC 211.2 MINIMUM NUMBER.NO FEWER THAN TWO DRINKING | | | FOUNTAINS SHALL BE PROVIDED. ONE DRINKING FOUNTAIN | | | SHALL COMPLY WITH 602.1 THEOUGH 602.6 AND ONE DRINKING | | | FOUNTAIN SHALL COMPLY WITH 602.7. | | | 602.4 SPOUT HEIGHT. SPOUT OUTLETS SHALL BE 36 INCHES | | | MAXIMUM ABOVE THE FINISH FLOOR OR GROUND | | | 602.7 DRINKING FOUNTAINS FOR STANDING PERSONS. SPOUT | | | OUTLETS OF DRINKING FOUNTAINS FOR STANDING PERSONS | | | SHALL BE 38 INCHES MINIMUM AND 43 INCHES MAXIMUM ABOVE | | | THE FINISH FLOOR OR GROUND. | | | | | | IN THE RESPONSE LETTER THE ARCHITECT IS CLAIMING THE | | | EXCEPTION #2 FBC ACC 202.3 A SIGNED AND SEALED LETTER | | | ON THE ARCHITECTS LETTER HEAD EXPLAINING HOW IT MEETS | | | THE EXCEPTION SHALL BE SUBMITTED AND SHALL BE APPROVED | | | BY THE BUILDING OFFICIAL ROBERT BROWN BEFORE PERMIT CAN | | | BE APPROVED. | | | | | | NEW COMMENTS: | | | | | | 1. SHT A0.05 PLEASE REMOVE DETAILS FOR THE PLUMBING | | | FIXTURES THA ARE NOT IN THE SCOPE OF WORK. PER WPB | | | AMEND TO FBC 107.2.1 | | | | | | 2. SHT. A0.05 THE DETAIL FOR THE WATER FOUNTAIN SHOWS A | | | PARALLEL CLEAR FLOOR SPACE THR CODE REQUIRES A FRONTAL | | | APPROACH PLEASE CLARIFY. FBC ACC 602.2 | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | | | 2019-06-26 12:14:26 | GPJ TO DO REVIEW. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2019-06-05 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2019-06-05 |
Time |
11:48 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2019-06-05 |
Time |
11:11 |
Sent To |
|
|
| Notes |
| 2019-06-05 11:57:01 | 1ST REVIEW: | | | 2017 FLORIDA BUILDING CODE 6TH EDITION | | | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH | | | EDITION | | | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH | | | EDITION | | | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH | | | EDITION | | | | | | PLUMBING COMMENTS: | | | | | | 1. TWO WATER FOUNTAINS ARE REQUIRED THEY SHALL COMPLY | | | WITH FBC PL [BE] 410.3 PROVIDE HIGH AND LOW DRINKING | | | FOUNTAINS. WHERE DRINKING FOUNTAINS ARE REQUIRED, NOT | | | FEWER THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED. | | | ONE DRINKING FOUNTAIN SHALL COMPLY WITH THE | | | REQUIREMENTS FOR PEOPLE WHO USE A WHEELCHAIR AND ONE | | | DRINKING FOUNTAIN SHALL COMPLY WITH THE REQUIREMENTS | | | FOR STANDING PERSONS. | | | FBC ACC 211.2 MINIMUM NUMBER.NO FEWER THAN TWO DRINKING | | | FOUNTAINS SHALL BE PROVIDED. ONE DRINKING FOUNTAIN | | | SHALL COMPLY WITH 602.1 THROUGH 602.6 AND ONE DRINKING | | | FOUNTAIN SHALL COMPLY WITH 602.7. | | | 602.4 SPOUT HEIGHT. SPOUT OUTLETS SHALL BE 36 INCHES | | | MAXIMUM ABOVE THE FINISH FLOOR OR GROUND | | | 602.7 DRINKING FOUNTAINS FOR STANDING PERSONS. SPOUT | | | OUTLETS OF DRINKING FOUNTAINS FOR STANDING PERSONS | | | SHALL BE 38 INCHES MINIMUM AND 43 INCHES MAXIMUM ABOVE | | | THE FINISH FLOOR OR GROUND. | | | | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
4 |
Status |
P |
Date |
2019-08-12 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2019-08-12 |
Time |
07:36 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2019-08-12 |
Time |
07:35 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
F |
Date |
2019-07-09 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2019-07-09 |
Time |
11:50 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2019-07-09 |
Time |
11:50 |
Sent To |
|
|
| Notes |
| 2019-07-09 11:55:13 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | 1. FAC61G15-23.004, ENGINEERS CANNOT SELF CERTIFY OR | | | SELF SIGN; A 3RD PARTY DIGITAL SIGNATURE IS REQUIRED. | | | MEP PLANS WHICH CHANGE DUE TO CODE RELATED COMMENTS | | | REQUIRE A 3RD PARTY DIGITAL SIGNATURE TO BE REVIEWED IN | | | THE NEXT REVIEW CYCLE. | | | | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
P |
Date |
2019-06-27 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2019-06-27 |
Time |
15:57 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2019-06-27 |
Time |
15:57 |
Sent To |
|
|
| Notes |
| 2019-06-27 15:59:14 | THE ENGINEER OF RECORD, BRADLEY BROWN IS ADVISED TO | | | ASSURE COMPLIANCE WITH FAC 61G15-23.005 PROCEDURES FOR | | | ELECTRONICALLY SIGNING AND SEALING ELECTRONICALLY | | | TRANSMITTED PLANS, |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2019-06-05 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2019-06-05 |
Time |
09:19 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2019-06-05 |
Time |
09:16 |
Sent To |
|
|
| Notes |
| 2019-06-05 09:19:55 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | 1. ARCHITECT SHEETS LACK A SEAL, FS481 (SIGNATURE OK). | | | | | | 2. PAGES SIGNED BY BRADLEY BROWN, PE LACK A SEAL, | | | FAC61G15-23.004 (CAN MODIFY DIGITAL SIGNATURE TO STATE | | | "SIGNED AND SEALED" OR CAN INCLUDE A SEAL IMAGE). | | | ENGINEER'S PAGES REQUIRE ADDITIONAL LANGUAGE, SEE | | | FAC61G15-23.004 REGARDING DIGITALLY SIGNED PLANS. (MEP | | | SIGNATURES OK, BUT NEED TO MODIFY PAGES AS DESCRIBED). | | | | | | | | | | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
N |
Date |
2019-05-17 |
|
|
Cont ID |
|
| Sent By |
aaponte |
Date |
2019-05-17 |
Time |
16:30 |
Rev Time |
0.00 |
| Received By |
aaponte |
Date |
2019-05-17 |
Time |
16:30 |
Sent To |
|
|
| Notes |
| 2019-05-17 16:31:00 | INTERIOR OFFICE IMPROVEMENT |
|
|