Plan Review Details - Permit 19050525
Plan Review Stops For Permit 19050525
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2019-08-12 Cont ID  
Sent By pvalenti Date 2019-08-12 Time 17:27 Rev Time 0.00
Received By pvalenti Date 2019-08-12 Time 17:27 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2019-07-10 Cont ID  
Sent By pvalenti Date 2019-07-10 Time 07:07 Rev Time 0.00
Received By pvalenti Date 2019-07-10 Time 06:54 Sent To  
Notes
2019-07-10 07:17:45***CORRECTIONS***
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 3RD BUILDING REVIEW DENIED:
  
 FBC A 202.4 PLEASE COMPLY WITH THE REQUIREMENTS OF THE
 ACCESSIBILITY CODE SECTION 202.4, 202.4.1, AND 202.4.2
 REGARDING THE DRINKING FOUNTAIN AREA AS NOTED IN THE
 PLUMBING REVIEW COMMENTS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-06-27 Cont ID  
Sent By pvalenti Date 2019-06-27 Time 08:15 Rev Time 0.00
Received By pvalenti Date 2019-06-27 Time 08:14 Sent To  
Notes
2019-06-27 10:10:49***CORRECTIONS***
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 2ND BUILDING REVIEW DENIED:
  
 1. A SEPERATE PERMIT IS REQUIRED FOR THE 9TH FLOOR.
 APPROVED WITH PROVISO. CONTRACTOR TO APPLY; APPLICATION
 IN PROGRESS.
  
 2. REVISE PLAN TO SHOW HOW THE ELEVATOR LOBBY SHOWN
 COMPLIES WITH FBC B 3006.3.
 APPROVED WITH PROVISO. ADJUST WALL ADJACENT TO LOBBY
 DOOR TO COMPLY WITH ACCESSIBILE MANEUVERABILITY(WALL
 NEEDS TO HAVE AN 18" HORIZONTAL MEASUREMENT).
  
 3. PAGE A0.03 THE COMMON PATH OF TRAVEL IS NOT CLEAR.
 PROVIDE INFORMATION ON HOW THE COMMON PATH OF TRAVEL IS
 AT 68'.
 FAIL.
  
 4. APPROVED
  
 5. APPROVED
  
 6. APPROVED
  
 7. APPROVED

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-06-05 Cont ID  
Sent By shill Date 2019-06-05 Time 09:15 Rev Time 0.00
Received By shill Date 2019-06-05 Time 08:39 Sent To  
Notes
2019-06-05 09:15:51****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. A SEPARATE PERMIT IS REQUIRED FOR THE 9TH FLOOR.
 CONTACT ME AFTER ALL REVIEWS HAVE PASSED TO COORDINATE.
  
 2. REVISE PLAN TO SHOW HOW THE "ELEVATOR LOBBY" SHOWN
 COMPLIES WITH FBC B 3006.3. IF THE ELEVATORS ARE
 PRESSURIZED, PLEASE ADVISE VIA EMAIL PRIOR TO
 RESUBMITTING.
  
 3. A0.03, COMMON PATH OF TRAVEL NOT CLEAR. OCCUPANCY
 ANALYSIS STATES THAT THIS IS 68', BUT IT APPEARS THAT
 IT IS 140'. SEE FBC CHAPTER 2, DEFINITION OF COMMON
 PATH.
  
 4. A0.03, ROOM 806, TAC WORKSTATION ADA, REVISE PLAN TO
 SHOW COMPLIANCE, FBC A 904. NO DIMENSIONS FOR THE
 ACCESSIBLE ROUTE INTO AND OUT OF THE SPACE WERE
 PROVIDED; PROVIDE DIMENSIONS AND DETAIL FOR THE SERVICE
 COUNTER.
  
 5. REVISE PLAN TO CLARIFY AREAS WHICH WOULD BE REQUIRED
 TO COMPLY WITH FBC A 808 (A0.03 SHOWS A "GRAND JURY").
  
 6. A0.02 ROOM 806 SHOWS "SELF HELP" STATIONS. PROVIDE A
 DETAIL, FBC A 904.
  
 7. SEE FIRE COMMENTS REGARDING MECHANICAL ROOM RATING;
 CHECK ALL.
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2019-06-05 Cont ID  
Sent By jpearson Date 2019-06-05 Time 09:55 Rev Time 0.00
Received By jpearson Date 2019-06-05 Time 09:55 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-06-20 Cont ID  
Sent By pleduc Date 2019-06-20 Time   Rev Time 0.00
Received By pleduc Date 2019-06-20 Time 13:17 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2019-05-20 Cont ID  
Sent By pleduc Date 2019-05-20 Time   Rev Time 0.00
Received By pleduc Date 2019-05-20 Time 14:56 Sent To  
Notes
2019-05-20 15:24:29THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET A 1.11 - THERE IS A DOUBLE DOOR INDICATED AT
 THE MECHANICAL ROOM WITHIN A RATED WALL; HOWEVER, THERE
 IS NO INDICATION ON THE DOOR SCHEDULE THAT THESE DOORS
 HAVE FIRE RATING OR SELFCLOSING.
  
 PLEASE REVIEW AND COORECT OR JUSTIFY.
  
  
  
 2) SHEET A 1.12 - THERE IS A DOUBLE DOOR INDICATED AT
 THE MECHANICAL ROOM WITHIN A RATED WALL; HOWEVER, THERE
 IS NO INDICATION ON THE DOOR SCHEDULE THAT THESE DOORS
 HAVE FIRE RATING OR SELFCLOSING.
  
 PLEASE REVIEW AND COORECT OR JUSTIFY.
  
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2019-08-14 Cont ID  
Sent By lmarchan Date 2019-08-14 Time 11:30 Rev Time 0.00
Received By lmarchan Date 2019-07-30 Time 16:14 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-07-10 Cont ID  
Sent By pvalenti Date 2019-07-10 Time 07:18 Rev Time 0.00
Received By pvalenti Date 2019-07-01 Time 14:03 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-06-27 Cont ID  
Sent By skennedy Date 2019-06-27 Time 16:00 Rev Time 0.00
Received By skennedy Date 2019-06-19 Time 13:11 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-06-05 Cont ID  
Sent By gjohnson Date 2019-06-05 Time 11:58 Rev Time 0.00
Received By gjohnson Date 2019-05-10 Time 10:48 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2019-06-27 Cont ID  
Sent By ccole Date 2019-06-27 Time 14:40 Rev Time 0.00
Received By ccole Date 2019-06-27 Time 13:25 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-06-05 Cont ID  
Sent By ccole Date 2019-06-05 Time 10:54 Rev Time 0.00
Received By ccole Date 2019-06-05 Time 10:54 Sent To  
Notes
2019-06-05 11:02:171ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19050525
 6/5/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SEPARATE PLANS AND PERMIT APPLICATION ARE REQUIRED
 FOR THE WORK ON THE 9TH FLOOR. PLEASE AMEND THE WORK
 DESCRIPTION ON THE PERMIT APPLICATION AND SEPARATE THE
 PLANS OUT ACCORDINGLY- SECTION 107.2.1 WPB.
  
 2) PLEASE PROVIDE A DETAILED ESTIMATE FOR THE WORK ON
 THE 8TH FLOOR- SECTION 109.3 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2019-08-14 Cont ID  
Sent By tklarge Date 2019-08-14 Time 10:33 Rev Time 0.00
Received By tklarge Date 2019-08-13 Time 09:58 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2019-07-09 Cont ID  
Sent By gjohnson Date 2019-07-09 Time 11:54 Rev Time 0.00
Received By gjohnson Date 2019-07-09 Time 11:54 Sent To  
Notes
2019-07-09 11:56:533RD REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1) THE PLUMBING PAGES CLEARLY SHOW NEW SANITARY AND
 WATER PIPING TO THE WATER FOUNTAIN LOCATION. PLEASE
 PROVIDE EXITING DEMO PLAN. I LOOKED INTO OUR RECORDS
 FOR THAT BUILDING AND COULD NOT FIND ANY SHOWING A
 WATER FOUNTAIN IN THAT LOCATION. AFTER DISCUSSING IT
 WITH THE BUILDING OFFICIAL WE FEEL THAT THIS DOES NOT
 FALL UNDER THE EXCEPTION AS BEING TECHNICALLY
 INFEASIBLE.
  
 2) ROBERT BROWN ASK IF THIS WORK WAS COMPLYING WITH FBC
 ACC 202.4, 202.4.1, 202.4.2 PLEASE PROVIDE A COST BREAK
 DOWN TO SHOW THAT A MIN OF 20% OF THE TOTAL COST OF THE
 JOB IS BEING USED TO PROVIDE 1.AN ACCESSIBLE PATH OF
 TRAVEL TO THE ALTERED AREA, 2. ACCESSIBLE REST ROOMS,
 TELEPHONES, AND DRINKING FOUNTAINS SERVING THE ALTERED
 AREA IN THAT ORDER. PER FBC ACC 202.4.1
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2019-06-27 Cont ID  
Sent By gjohnson Date 2019-06-27 Time 10:51 Rev Time 0.00
Received By gjohnson Date 2019-06-26 Time 12:14 Sent To  
Notes
2019-06-27 11:36:221ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS: PREVIOUS COMMENTS.
  
 1. TWO WATER FOUNTAINS ARE REQUIRED THEY SHALL COMPLY
 WITH FBC PL [BE] 410.3 PROVIDE HIGH AND LOW DRINKING
 FOUNTAINS. WHERE DRINKING FOUNTAINS ARE REQUIRED, NOT
 FEWER THEN TWO DRINKING FOUNTAINS SHALL BE PROVIDED.
 ONE DRINKING FOUNTAIN SHALL COMPLY WITH THE
 REQUIREMENTS FOR PEOPLE WHO USE A WHEELCHAIR AND ONE
 DRINKING FOUNTAIN SHALL COMPLY WITH THE REQUIREMENTS
 FOR STANDING PERSONS.
 FBC ACC 211.2 MINIMUM NUMBER.NO FEWER THAN TWO DRINKING
 FOUNTAINS SHALL BE PROVIDED. ONE DRINKING FOUNTAIN
 SHALL COMPLY WITH 602.1 THEOUGH 602.6 AND ONE DRINKING
 FOUNTAIN SHALL COMPLY WITH 602.7.
 602.4 SPOUT HEIGHT. SPOUT OUTLETS SHALL BE 36 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND
 602.7 DRINKING FOUNTAINS FOR STANDING PERSONS. SPOUT
 OUTLETS OF DRINKING FOUNTAINS FOR STANDING PERSONS
 SHALL BE 38 INCHES MINIMUM AND 43 INCHES MAXIMUM ABOVE
 THE FINISH FLOOR OR GROUND.
  
 IN THE RESPONSE LETTER THE ARCHITECT IS CLAIMING THE
 EXCEPTION #2 FBC ACC 202.3 A SIGNED AND SEALED LETTER
 ON THE ARCHITECTS LETTER HEAD EXPLAINING HOW IT MEETS
 THE EXCEPTION SHALL BE SUBMITTED AND SHALL BE APPROVED
 BY THE BUILDING OFFICIAL ROBERT BROWN BEFORE PERMIT CAN
 BE APPROVED.
  
 NEW COMMENTS:
  
 1. SHT A0.05 PLEASE REMOVE DETAILS FOR THE PLUMBING
 FIXTURES THA ARE NOT IN THE SCOPE OF WORK. PER WPB
 AMEND TO FBC 107.2.1
  
 2. SHT. A0.05 THE DETAIL FOR THE WATER FOUNTAIN SHOWS A
 PARALLEL CLEAR FLOOR SPACE THR CODE REQUIRES A FRONTAL
 APPROACH PLEASE CLARIFY. FBC ACC 602.2
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
2019-06-26 12:14:26GPJ TO DO REVIEW.

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-06-05 Cont ID  
Sent By gjohnson Date 2019-06-05 Time 11:48 Rev Time 0.00
Received By gjohnson Date 2019-06-05 Time 11:11 Sent To  
Notes
2019-06-05 11:57:011ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. TWO WATER FOUNTAINS ARE REQUIRED THEY SHALL COMPLY
 WITH FBC PL [BE] 410.3 PROVIDE HIGH AND LOW DRINKING
 FOUNTAINS. WHERE DRINKING FOUNTAINS ARE REQUIRED, NOT
 FEWER THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED.
 ONE DRINKING FOUNTAIN SHALL COMPLY WITH THE
 REQUIREMENTS FOR PEOPLE WHO USE A WHEELCHAIR AND ONE
 DRINKING FOUNTAIN SHALL COMPLY WITH THE REQUIREMENTS
 FOR STANDING PERSONS.
 FBC ACC 211.2 MINIMUM NUMBER.NO FEWER THAN TWO DRINKING
 FOUNTAINS SHALL BE PROVIDED. ONE DRINKING FOUNTAIN
 SHALL COMPLY WITH 602.1 THROUGH 602.6 AND ONE DRINKING
 FOUNTAIN SHALL COMPLY WITH 602.7.
 602.4 SPOUT HEIGHT. SPOUT OUTLETS SHALL BE 36 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND
 602.7 DRINKING FOUNTAINS FOR STANDING PERSONS. SPOUT
 OUTLETS OF DRINKING FOUNTAINS FOR STANDING PERSONS
 SHALL BE 38 INCHES MINIMUM AND 43 INCHES MAXIMUM ABOVE
 THE FINISH FLOOR OR GROUND.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2019-08-12 Cont ID  
Sent By shill Date 2019-08-12 Time 07:36 Rev Time 0.00
Received By shill Date 2019-08-12 Time 07:35 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2019-07-09 Cont ID  
Sent By shill Date 2019-07-09 Time 11:50 Rev Time 0.00
Received By shill Date 2019-07-09 Time 11:50 Sent To  
Notes
2019-07-09 11:55:13****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. FAC61G15-23.004, ENGINEERS CANNOT SELF CERTIFY OR
 SELF SIGN; A 3RD PARTY DIGITAL SIGNATURE IS REQUIRED.
 MEP PLANS WHICH CHANGE DUE TO CODE RELATED COMMENTS
 REQUIRE A 3RD PARTY DIGITAL SIGNATURE TO BE REVIEWED IN
 THE NEXT REVIEW CYCLE.
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2019-06-27 Cont ID  
Sent By skennedy Date 2019-06-27 Time 15:57 Rev Time 0.00
Received By skennedy Date 2019-06-27 Time 15:57 Sent To  
Notes
2019-06-27 15:59:14THE ENGINEER OF RECORD, BRADLEY BROWN IS ADVISED TO
 ASSURE COMPLIANCE WITH FAC 61G15-23.005 PROCEDURES FOR
 ELECTRONICALLY SIGNING AND SEALING ELECTRONICALLY
 TRANSMITTED PLANS,

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2019-06-05 Cont ID  
Sent By shill Date 2019-06-05 Time 09:19 Rev Time 0.00
Received By shill Date 2019-06-05 Time 09:16 Sent To  
Notes
2019-06-05 09:19:55****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. ARCHITECT SHEETS LACK A SEAL, FS481 (SIGNATURE OK).
  
 2. PAGES SIGNED BY BRADLEY BROWN, PE LACK A SEAL,
 FAC61G15-23.004 (CAN MODIFY DIGITAL SIGNATURE TO STATE
 "SIGNED AND SEALED" OR CAN INCLUDE A SEAL IMAGE).
 ENGINEER'S PAGES REQUIRE ADDITIONAL LANGUAGE, SEE
 FAC61G15-23.004 REGARDING DIGITALLY SIGNED PLANS. (MEP
 SIGNATURES OK, BUT NEED TO MODIFY PAGES AS DESCRIBED).
  
  
  
  

Review Stop Z ZONING
Rev No 1 Status N Date 2019-05-17 Cont ID  
Sent By aaponte Date 2019-05-17 Time 16:30 Rev Time 0.00
Received By aaponte Date 2019-05-17 Time 16:30 Sent To  
Notes
2019-05-17 16:31:00INTERIOR OFFICE IMPROVEMENT