Plan Review Details - Permit 19050491
Plan Review Stops For Permit 19050491
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-06-06 Cont ID  
Sent By rmcdouga Date 2019-06-06 Time 11:01 Rev Time 0.00
Received By rmcdouga Date 2019-06-06 Time 11:01 Sent To I
Notes
2019-06-06 11:01:32BUILDING PROVISO
 ALL MECHANICAL EQUIPMENT AND DUCT WORK INSTALLED ON THE
 EXTERIOR OF THE BUILDING SHALL BE ANCHORED AND SECURED
 SUCH THAT IT IS CAPABLE OF RESISTING WINDLOADS OF 170
 MPH EXPOSURE C. SUBMIT PRODUCT APPROVALS AND/OR
 ENGINEERED DOCUMENTS FOR REVIEW PRIOR TO INSTALLATION.
 FBC 107.3.4.2 & 1609.1

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2019-05-14 Cont ID  
Sent By rmcdouga Date 2019-05-14 Time 08:31 Rev Time 0.00
Received By rmcdouga Date 2019-05-14 Time 07:24 Sent To M
Notes
2019-05-14 08:31:08BUILDING PROVISO
 ALL MECHANICAL EQUIPMENT AND DUCT WORK INSTALLED ON THE
 EXTERIOR OF THE BUILDING SHALL BE ANCHORED AND SECURED
 SUCH THAT IT IS CAPABLE OF RESISTING WINDLOADS OF 170
 MPH EXPOSURE C. SUBMIT PRODUCT APPROVALS AND/OR
 ENGINEERED DOCUMENTS FOR REVIEW PRIOR TO INSTALLATION.
 FBC 107.3.4.2 & 1609.1

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2019-05-13 Cont ID  
Sent By jpearson Date 2019-05-13 Time 10:23 Rev Time 0.00
Received By jpearson Date 2019-05-13 Time 10:23 Sent To B
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-06-06 Cont ID  
Sent By rmcdouga Date 2019-06-06 Time 11:01 Rev Time 0.00
Received By rmcdouga Date 2019-05-31 Time 14:27 Sent To  
Notes
2019-06-03 14:27:44RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2019-05-20 Time   Rev Time 0.00
Received By lmarchan Date 2019-05-09 Time 13:34 Sent To  
Notes
2019-05-09 13:34:59REVISION ROUTED TO JPEARSON

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2019-06-06 Cont ID  
Sent By ccole Date 2019-06-06 Time 10:13 Rev Time 0.00
Received By ccole Date 2019-06-06 Time 10:13 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-05-20 Cont ID  
Sent By ccole Date 2019-05-20 Time 10:50 Rev Time 0.00
Received By ccole Date 2019-05-20 Time 10:14 Sent To I
Notes
2019-05-20 11:17:261ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19050491
 5/20/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M1: THE ORIGINAL KITCHEN HOOD PLANS SUBMITTED
 UNDER PERMIT #19011174 MUST BE REVISED TO SHOW THE
 CHANGES TO THE GREASE EXHAUST DUCT RUN AND NEW KEF
 LOCATION, HOWEVER PLEASE NOTE THE PROPOSED NEW PLANS
 ARE DEFICIENT- SEE COMMENTS BELOW.
  
 2) M1: PROVIDE EITHER A FIRE-RATED SHAFT FOR THE GREASE
 EXHAUST DUCT PENETRATING THE FIRE-RATED CEILING OR A
 FIRE WRAP ENCLOSURE- SEE SECTIONS 506.3.11, 506.3.11.1,
 506.3.11.2, AND 506.3.11.3 FBC M
  
 3) M1: THE GREASE DUCT SHALL EITHER SLOPE TO THE HOOD
 OR TO A GREASE RESERVOIR IN ACCORDANCE WITH SECTION
 506.3.7 FBC M. NO RESERVOIR IS SHOWN ON THE PLAN.
  
 4) M1: THE GREASE EXHAUST TERMINATION SHALL BE 10'
 ABOVE GRADE- SECTION 506.3.13.3 FBC M
  
 5) WIND LOAD ENGINEERING IS REQUIRED FOR INSTALLATION
 OF THE GREASE EXHAUST FAN AND CURB- SECTION 301.15 FBC
 M.
  
 6) SHEET ID-3.0 INDICATES A CHASE DOWN THE SIDE OF THE
 BUILDING TO ENCLOSE THE EXHAUST DUCT HOWEVER NO
 CONSTRUCTION DETAILS HAVE BEEN PROVIDED- SECTION
 107.2.1 WPB, AND SECTION 506.3.11.1 FBC M. PLEASE NOTE
 THAT ACCESS TO CLEANOUTS SHALL BE PROVIDED IN
 ACCORDANCE WITH SECTION 506.3.8 FBC M.
  
 7) ID-3.0: THERE IS A NOTE REFERENCING A SOUTHWEST
 ELEVATION DETAIL, HOWEVER THE ELEVATION HAS NOT BEEN
 PROVIDED- SECTION 107.2.1 WPB
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  