Plan Review Details - Permit 19050455
Plan Review Stops For Permit 19050455
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-07-12 Cont ID  
Sent By cthroop Date 2019-07-12 Time 09:08 Rev Time 0.00
Received By cthroop Date 2019-07-12 Time 09:08 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-06-03 Cont ID  
Sent By rmcdouga Date 2019-06-03 Time 13:36 Rev Time 0.00
Received By shill Date 2019-06-03 Time 13:36 Sent To  
Notes
2019-06-03 13:38:21****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. FS481, HAVE THE ARCHITECT REVISE ALL PLAN PAGES
 AFFECTED BY THE PROPOSED CHANGE (FOR EXAMPLE, A1.04).
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-07-11 Cont ID  
Sent By jleahy Date 2019-07-11 Time 13:50 Rev Time 0.00
Received By jleahy Date 2019-07-11 Time 13:50 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-05-28 Cont ID  
Sent By jleahy Date 2019-05-28 Time 10:09 Rev Time 0.00
Received By jleahy Date 2019-05-28 Time 10:09 Sent To  
Notes
2019-05-28 10:36:30FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) 200 AMPERE TRANSFER SWITCH FEEDING 2 PANELS ONE 60A
 AND ONE 100A ? OVERCURRENT DEVICE TO LARGE FOR THE
 WIRE.
 E3602.1AMPACITY OF UNGROUNDED CONDUCTORS.
 UNGROUNDED SERVICE CONDUCTORS SHALL HAVE AN AMPACITY OF
 NOT LESS THAN THE LOAD SERVED. 200A BREAKER FEEDING 60
 AND 100 AMPERE LOADS.
  
 2) FEEDERS AND SERVICE MIXED IN SAME ENCLOURE (GUTTER)
 E3601.4OTHER CONDUCTORS IN RACEWAY OR CABLE.
 CONDUCTORS OTHER THAN SERVICE CONDUCTORS SHALL NOT BE
 INSTALLED IN THE SAME SERVICE RACEWAY OR SERVICE CABLE.
 (230.7)
  
 3) COTTAGE DOES NOT SHOW GROUNDING PER 250.32
 E3607.3BUILDINGS OR STRUCTURES SUPPLIED BY FEEDER(S) OR
 BRANCH CIRCUIT(S).
 BUILDINGS OR STRUCTURES SUPPLIED BY FEEDER(S) OR BRANCH
 CIRCUIT(S) SHALL HAVE A GROUNDING ELECTRODE OR
 GROUNDING ELECTRODE SYSTEM INSTALLED IN ACCORDANCE WITH
 SECTION E3608. THE GROUNDING ELECTRODE CONDUCTOR(S)
 SHALL BE CONNECTED IN A MANNER SPECIFIED IN SECTION
 E3607.3.1 OR, FOR EXISTING PREMISES WIRING SYSTEMS
 ONLY, SECTION E3607.3.2. WHERE THERE IS NO EXISTING
 GROUNDING ELECTRODE, THE GROUNDING ELECTRODE(S)
 REQUIRED IN SECTION E3608 SHALL BE INSTALLED.
 [250.32(A)]

Review Stop G GAS REVIEW
Rev No 2 Status N Date 2019-07-12 Cont ID  
Sent By cthroop Date 2019-07-12 Time 09:05 Rev Time 0.00
Received By cthroop Date 2019-07-12 Time 09:04 Sent To  
Notes
2019-07-12 09:05:32NO GAS WORK. CT

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2019-05-15 Cont ID  
Sent By gjohnson Date 2019-05-15 Time 11:37 Rev Time 0.00
Received By thunt Date 2019-05-15 Time 09:54 Sent To  
Notes
2019-05-15 11:41:51GAS 1ST REVISION REVIEW**DENIED** PLEASE CLOUD ALL
 CHANGES THIS REVISION PERTAINS TOO. FBC 107.3.5
  
 1) NO INCREASE OF VALVE PROVIDE. WITH THE LARGE AMOUNT
 OF ADDED GAS APPLIANCES AND THE RECONFIGURATION OF THE
 COTTAGE WITH COMPLETED KITCHEN YOU MUST PROVIDE THE
 INCREASE VALUE. THE GENERATOR SHALL NOT BE PART OF THIS
 AS IT WILL BE ASSET ON IT STAND ALONG PERMIT. WPB AMED
 109.3
  
 2) THE REVISED TAKAGI TANKLESS HEATER (E.F80%) SHOWN IS
 A COMMERCIAL UNIT THAT DOES NOT MEET THE FEDERAL MIN
 EFFICIENCY REQUIRED OF .82%. ANY CHANGING OF THE WATER
 HEATER FROM THE APPROVED MODEL EFFICIENCY WILL REQUIRED
 A NEW R405-2017 ENERGY FORM BE COMPLETED AND SUBMITTED.
 10 FCR 429, 10 FCR 430.22 (D)
  
 3) SUBMIT MANUFACTURER?S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND 2017
 FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED
 AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS
 APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF
 INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1.
  
 4) SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE
 CORRUGATED STAINLESS STEEL TUBING (IF APPLICABLE) FOR
 EACH PIPE SIZE. WPB AMENDMENTS TO FBC SEC.107.2.1. YOU
 CALL OUT ALL EXTERIOR PIPING TO BE P.E BUT P.E IS NOT
 APPROVED FOR USE ABOVE GROUND. FBC 107.2.1
  
 5) SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2017
 FBC-FUEL GAS CODE SEC.304.1,2017 FBC-RES. SEC. G 2407.1
 AND G2439.4 (CLOTHES DRYERS).
  
 6) SUBMIT COMBUSTION AIR CALCULATIONS FOR THE ADDED GAS
 APPLIANCES BOTH RANGE/ COOK TOPS. WHERE COMBUSTION AIR
 IS PROVIDED BY THE BUILDING?S MECHANICAL VENTILATION
 SYSTEM, THE SYSTEM SHALL PROVIDE THE SPECIFIED
 COMBUSTION AIR RATE IN ADDITION TO THE REQUIRED
 VENTILATION AIR. 2017 FBCR G2407.9.3.
  
 7) PROVIDE CORRECT SIZING TABLES FOR ENTIRE SYSTEM AND
 ALL MATERIALS AND PRESSURES BEING USED.FBC RES G2413.3
  
 8) SUBMIT TWO COPIES OF A HOUSE PLAN SHOWING THE
 LOCATION OF THE TANKLESS WATER HEATER AND THE LOCATION
 AND DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN
 RELATION TO THE WATER HEATER. THE LOCATION OF THE WATER
 HEATER SHALL COMPLY WITH THE MANUFACTURER'S
 INSTALLATION INSTRUCTIONS. THE HOUSE PLAN CAN BE HAND
 DRAWN. WPB AMEND. TO FBC SEC. 107.2.1.
  
 9) SHOW THE DISTANCE FROM THE 2 PSI REGULATOR TO THE
 APPLIANCE. COMPLY WITH 2017 FBC-FUEL GAS SEC. 402.4.1
 OR 2017 FBC-RES. SEC. G2413.4.1, G2413.4.2 FOR THE
 PROPER PIPE SIZE AND BTU LOAD.
  
 10) SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE
 PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION. 2017 FBC-RES. SEC. G2421.1
  
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR
 BUILDING DIVISION
 CITY OF WEST PALM BEACH
 401 CLEMATIS STREET, 1ST FLOOR
 WEST PALM BEACH, FL 33401
 561-248-2703
 [email protected]
 [email protected]
  
  
  
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-07-12 Cont ID  
Sent By cthroop Date 2019-07-12 Time 09:06 Rev Time 0.00
Received By cthroop Date 2019-07-12 Time 09:03 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-07-11 Cont ID  
Sent By jleahy Date 2019-07-11 Time 13:50 Rev Time 0.00
Received By jleahy Date 2019-07-05 Time 15:24 Sent To  
Notes
2019-07-08 15:24:51REVISION ROUTED TO JLEAHY

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-06-04 Cont ID  
Sent By cpuell Date 2019-06-04 Time 17:03 Rev Time 0.00
Received By cpuell Date 2019-05-08 Time 12:49 Sent To  
Notes
2019-05-09 12:50:15R19

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2019-07-12 Cont ID  
Sent By cthroop Date 2019-07-12 Time 09:04 Rev Time 0.00
Received By cthroop Date 2019-07-12 Time 09:04 Sent To  
Notes
2019-07-12 09:05:05NO MECH. WORK. CT

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-05-28 Cont ID  
Sent By hmoser Date 2019-05-28 Time 09:53 Rev Time 0.00
Received By hmoser Date 2019-05-28 Time 09:53 Sent To  
Notes
2019-05-28 09:54:23NO AIR CONDITIONING REVISIONS SUBMITTED HM.

Review Stop P PLUMBING
Rev No 2 Status N Date 2019-07-12 Cont ID  
Sent By cthroop Date 2019-07-12 Time 09:05 Rev Time 0.00
Received By cthroop Date 2019-07-12 Time 09:04 Sent To  
Notes
2019-07-12 09:06:00NO PLUMBING WORK. CT

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-05-15 Cont ID  
Sent By gjohnson Date 2019-05-15 Time 11:13 Rev Time 0.00
Received By thunt Date 2019-05-15 Time 09:54 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2019-06-04 Cont ID  
Sent By fmittner Date 2019-06-04 Time 15:16 Rev Time 0.00
Received By fmittner Date 2019-06-04 Time 15:16 Sent To  
Notes
2019-06-04 15:16:44LOT IS LARGE ENOUGH IN SF14 ZONING DISTRICT TO ALLOW
 FOR ACCESSORY UNIT
2019-05-15 09:53:47ZONING STOP ADDED AS APPROVED PLAN DID NOT HAVE A
 COMPLETE KITCHEN IN THE COTTAGE AND THIS REVISION NOW
 SHOWS A COMPLETE KITCHEN WITH GAS COOK TOP. THUNT