| 2019-05-15 11:41:51 | GAS 1ST REVISION REVIEW**DENIED** PLEASE CLOUD ALL |
| | CHANGES THIS REVISION PERTAINS TOO. FBC 107.3.5 |
| | |
| | 1) NO INCREASE OF VALVE PROVIDE. WITH THE LARGE AMOUNT |
| | OF ADDED GAS APPLIANCES AND THE RECONFIGURATION OF THE |
| | COTTAGE WITH COMPLETED KITCHEN YOU MUST PROVIDE THE |
| | INCREASE VALUE. THE GENERATOR SHALL NOT BE PART OF THIS |
| | AS IT WILL BE ASSET ON IT STAND ALONG PERMIT. WPB AMED |
| | 109.3 |
| | |
| | 2) THE REVISED TAKAGI TANKLESS HEATER (E.F80%) SHOWN IS |
| | A COMMERCIAL UNIT THAT DOES NOT MEET THE FEDERAL MIN |
| | EFFICIENCY REQUIRED OF .82%. ANY CHANGING OF THE WATER |
| | HEATER FROM THE APPROVED MODEL EFFICIENCY WILL REQUIRED |
| | A NEW R405-2017 ENERGY FORM BE COMPLETED AND SUBMITTED. |
| | 10 FCR 429, 10 FCR 430.22 (D) |
| | |
| | 3) SUBMIT MANUFACTURER?S SPECIFICATION SHEETS / |
| | INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY |
| | COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND 2017 |
| | FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED |
| | AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS |
| | APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF |
| | INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1. |
| | |
| | 4) SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL |
| | PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE |
| | CORRUGATED STAINLESS STEEL TUBING (IF APPLICABLE) FOR |
| | EACH PIPE SIZE. WPB AMENDMENTS TO FBC SEC.107.2.1. YOU |
| | CALL OUT ALL EXTERIOR PIPING TO BE P.E BUT P.E IS NOT |
| | APPROVED FOR USE ABOVE GROUND. FBC 107.2.1 |
| | |
| | 5) SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2017 |
| | FBC-FUEL GAS CODE SEC.304.1,2017 FBC-RES. SEC. G 2407.1 |
| | AND G2439.4 (CLOTHES DRYERS). |
| | |
| | 6) SUBMIT COMBUSTION AIR CALCULATIONS FOR THE ADDED GAS |
| | APPLIANCES BOTH RANGE/ COOK TOPS. WHERE COMBUSTION AIR |
| | IS PROVIDED BY THE BUILDING?S MECHANICAL VENTILATION |
| | SYSTEM, THE SYSTEM SHALL PROVIDE THE SPECIFIED |
| | COMBUSTION AIR RATE IN ADDITION TO THE REQUIRED |
| | VENTILATION AIR. 2017 FBCR G2407.9.3. |
| | |
| | 7) PROVIDE CORRECT SIZING TABLES FOR ENTIRE SYSTEM AND |
| | ALL MATERIALS AND PRESSURES BEING USED.FBC RES G2413.3 |
| | |
| | 8) SUBMIT TWO COPIES OF A HOUSE PLAN SHOWING THE |
| | LOCATION OF THE TANKLESS WATER HEATER AND THE LOCATION |
| | AND DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN |
| | RELATION TO THE WATER HEATER. THE LOCATION OF THE WATER |
| | HEATER SHALL COMPLY WITH THE MANUFACTURER'S |
| | INSTALLATION INSTRUCTIONS. THE HOUSE PLAN CAN BE HAND |
| | DRAWN. WPB AMEND. TO FBC SEC. 107.2.1. |
| | |
| | 9) SHOW THE DISTANCE FROM THE 2 PSI REGULATOR TO THE |
| | APPLIANCE. COMPLY WITH 2017 FBC-FUEL GAS SEC. 402.4.1 |
| | OR 2017 FBC-RES. SEC. G2413.4.1, G2413.4.2 FOR THE |
| | PROPER PIPE SIZE AND BTU LOAD. |
| | |
| | 10) SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE |
| | PRESSURE REGULATORS. REGULATORS INSTALLED ON THE |
| | EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR |
| | INSTALLATION. 2017 FBC-RES. SEC. G2421.1 |
| | |
| | |
| | TIM HUNT |
| | PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR |
| | BUILDING DIVISION |
| | CITY OF WEST PALM BEACH |
| | 401 CLEMATIS STREET, 1ST FLOOR |
| | WEST PALM BEACH, FL 33401 |
| | 561-248-2703 |
| | [email protected] |
| | [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |