Plan Review Details - Permit 19050386
Plan Review Stops For Permit 19050386
Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2019-10-19 Cont ID  
Sent By cthroop Date 2019-10-19 Time 12:49 Rev Time 0.00
Received By cthroop Date 2019-10-15 Time 16:08 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2019-10-04 Cont ID  
Sent By cthroop Date 2019-10-04 Time 16:38 Rev Time 0.00
Received By cthroop Date 2019-10-04 Time 12:47 Sent To  
Notes
2019-10-04 16:40:30ADDRESS: 110 FLAGLER LANE PERMIT # 19050386
 TYPE: BLD-RES NEW SFR
  
 BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 5TH REVIEW - DISREGARD PREVIOUS 4TH REVIEW LOCKED OUT
 OF COMMUNITY PLUS
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. SHOW LOCATION OF FLOOD VENTS ON FOUNDATION PLAN AND
 RE-SUBMIT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2019-09-14 Cont ID  
Sent By cthroop Date 2019-09-14 Time 11:01 Rev Time 0.00
Received By cthroop Date 2019-09-14 Time 11:01 Sent To  
Notes
2019-09-14 11:13:37ADDRESS: 110 FLAGLER LANE PERMIT # 19050386
 TYPE: BLD-RES NEW SFR
  
 BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 4TH REVIEW - DISREGARD PREVIOUS 4TH REVIEW LOCKED OUT
 OF COMMUNITY PLUS
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 THOSE ITEMS THAT HAVE BEEN ADDRESSED FROM 1ST REVIEW
 HAVE BEEN NOTED CORRECTED.
  
 THOSE ITEMS THAT HAVE NOT BEEN ADDRESSED FROM 1ST
 REVIEW (NOT ADDRESSED) IN PARANTHESIS.
  
 ANY NEW ITEM WILL BE LISTED AT THE END OF COMMENTS.
  
 1. CORRECTED
  
 2. CORRECTED
  
 3. ELEVATION CERTIFICATES ARE REQUIRED. SEE COMMENTS
 UNDER NFIP REVIEW. (INCOMPLETE)
  
 4. PROVIDE PRODUCT APPROVALS FOR ALL WINDOWS AND
 EXTERIOR DOORS. (NOT ADDRESSED - LIST PRODUCT APPROVALS
 ON WINDOW AND DOOR SCHEDULE OR DESIGNER SHALL REVIEW
 AND APPROVE EACH PRODUCT APPROVAL OR PRODUCT APPROVALS
 MAY BE DEFERRED BY PLACING STATEMENT ON PLAN "PRODUCT
 APPROVALS ARE DEFERRED")
 FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE WINDOW AND DOOR SUBMITTALS.
 OPTION:
 107.3.4.1 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS
 SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON
 THE CONSTRUCTION DOCUMENTS FOR REVIEW BY THE BUILDING
 OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 5. PROVIDE SOILS REPORT. (TWO ENGINEER'S SIGNED SOILS
 REPORT, NEITHER SIGNATURE AND SEAL IS VALID. PROVIDE
 HARD COPY OF SOILS REPORT WITH ORIGINAL SIGNATURES AND
 SEALS AT TIME OF PERMIT PICK-UP)
  
 6. PALM BEACH COUNTY IMPACT FEES (CLOSED - SEE IMPACT
 FEE REVIEW)
  
 7. PROVIDE AN ACCURATELEY COMPLETED ENERGY SUBMITTAL.
 (NOT ADDRESSED) (SUBMITTAL SHALL BE SIGNED BY PREPERARE
 AND OWNER/AGENT)
 FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405
 (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE
 SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE
 COMPLIANCE BY SECTION 405.
  
 8. PROVIDE FLOOD VENTS IN GARAGE WALLS. (NOT ADDRESSED)
 (PRODUCT APPROVALS PROVIDED FOR TWO DIFFERENT SMART
 VENTS, NO VENTS LOCATED ON FOUNDATION PLAN. PRODUCT
 APPROVALS SHALL BE REVIEWEED AND APPROVED BY DESIGNER)
 1612.5 FLOOD HAZARD DOCUMENTATION.
 THE FOLLOWING DOCUMENTATION SHALL BE PREPARED AND
 SEALED BY A REGISTERED DESIGN PROFESSIONAL AND
 SUBMITTED TO THE BUILDING OFFICIAL:
  
 1. FOR CONSTRUCTION IN FLOOD HAZARD AREAS OTHER THAN
 COASTAL HIGH HAZARD AREAS:
 1.1. THE ELEVATION OF THE LOWEST FLOOR, INCLUDING
 BASEMENT, AS REQUIRED BY THE FOUNDATION INSPECTION AND
 THE FINAL INSPECTION IN SECTION 110.3.
 1.2. FOR FULLY ENCLOSED AREAS BELOW THE DESIGN FLOOD
 ELEVATION WHERE PROVISIONS TO ALLOW FOR THE AUTOMATIC
 ENTRY AND EXIT OF FLOODWATERS DO NOT MEET THE MINIMUM
 REQUIREMENTS IN SECTION 2.6.2.1 OF ASCE 24,
 CONSTRUCTION DOCUMENTS SHALL INCLUDE A STATEMENT THAT
 THE DESIGN WILL PROVIDE FOR EQUALIZATION OF HYDROSTATIC
 FLOOD FORCES IN ACCORDANCE WITH SECTION 2.6.2.2 OF ASCE
 24.
  
 ADVISORY:
  
 4X FEES
  
 F.S. 553.80 (2) (B)
 (B)?WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS?
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2019-09-14 Cont ID  
Sent By cthroop Date 2019-09-14 Time 09:11 Rev Time 0.00
Received By cthroop Date 2019-09-14 Time 08:06 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2019-09-07 Cont ID  
Sent By cthroop Date 2019-09-07 Time 08:38 Rev Time 0.00
Received By cthroop Date 2019-09-05 Time 09:23 Sent To  
Notes
2019-09-07 08:45:10ADDRESS: 110 FLAGLER LANE PERMIT # 19050386
 TYPE: BLD-RES NEW SFR
  
 BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 3RD REVIEW
  
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 THOSE ITEMS THAT HAVE BEEN ADDRESSED FROM 1ST REVIEW
 HAVE BEEN NOTED CORRECTED.
  
 THOSE ITEMS THAT HAVE NOT BEEN ADDRESSED FROM 1ST
 REVIEW (NOT ADDRESSED) IN PARANTHESIS.
  
 ANY NEW ITEM WILL BE LISTED AT THE END OF COMMENTS.
  
 1. PROVIDE SITE DRAINAGE PLAN. CORRECTED
  
 2. PROVIDE A CURRENT SURVEY. (SURVEYORS SIG. & SEAL ARE
 NOT DIGITAL. PROVIDE HARD COPY WITH WET SEAL)
  
 3. ELEVATION CERTIFICATES ARE REQUIRED. SEE COMMENTS
 UNDER NFIP REVIEW. (INCOMPLETE) (EC UNSUCESSFULLY
 UPLOADED, NO INFORMATION AVAILABLE)
  
 4. PROVIDE PRODUCT APPROVALS FOR ALL WINDOWS AND
 EXTERIOR DOORS. (NOT ADDRESSED - PROVIDE PRODUCT
 APPROVALS LISTED ON PRODUCT APPROVAL SCHEDULE)
 (MULTIPLE PRODUCT APPROVALS UNSUCESSFULLY UPLOADED, NO
 INFO AVAILABLE)
  
 FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE WINDOW AND DOOR SUBMITTALS.
 OPTION:
 107.3.4.1 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS
 SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON
 THE CONSTRUCTION DOCUMENTS FOR REVIEW BY THE BUILDING
 OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 5. PROVIDE SOILS REPORT. (ENGINEER'S SIG. & SEAL ARE
 NOT DIGITAL. PROVIDE HARD COPY WITH WET SEAL)
  
 6. PALM BEACH COUNTY IMPACT FEES ARE REQUIRED. (OPEN)
 (COMPLETE AND UPLOAD IMPACT FEE QUESTIONAIRE)
  
 7. PROVIDE AN ACCURATELEY COMPLETED ENERGY SUBMITTAL.
 (NOT ADDRESSED) (ENERGY SUBMITTAL UNSUCESSFULLY
 UPLOADED, NO INFORMATION AVAILBLE)
 FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405
 (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE
 SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE
 COMPLIANCE BY SECTION 405.
  
 8. PROVIDE FLOOD VENTS IN GARAGE WALLS. (NOT ADDRESSED)
 (PRODUCT APPROVALS FOR VENTS UNSECUSSFULLY UPLOADED, NO
 INFORMATION AVAILABLE)
 1612.5 FLOOD HAZARD DOCUMENTATION.
 THE FOLLOWING DOCUMENTATION SHALL BE PREPARED AND
 SEALED BY A REGISTERED DESIGN PROFESSIONAL AND
 SUBMITTED TO THE BUILDING OFFICIAL:
  
 1. FOR CONSTRUCTION IN FLOOD HAZARD AREAS OTHER THAN
 COASTAL HIGH HAZARD AREAS:
 1.1. THE ELEVATION OF THE LOWEST FLOOR, INCLUDING
 BASEMENT, AS REQUIRED BY THE FOUNDATION INSPECTION AND
 THE FINAL INSPECTION IN SECTION 110.3.
 1.2. FOR FULLY ENCLOSED AREAS BELOW THE DESIGN FLOOD
 ELEVATION WHERE PROVISIONS TO ALLOW FOR THE AUTOMATIC
 ENTRY AND EXIT OF FLOODWATERS DO NOT MEET THE MINIMUM
 REQUIREMENTS IN SECTION 2.6.2.1 OF ASCE 24,
 CONSTRUCTION DOCUMENTS SHALL INCLUDE A STATEMENT THAT
 THE DESIGN WILL PROVIDE FOR EQUALIZATION OF HYDROSTATIC
 FLOOD FORCES IN ACCORDANCE WITH SECTION 2.6.2.2 OF ASCE
 24.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-08-05 Cont ID  
Sent By cthroop Date 2019-08-05 Time 13:29 Rev Time 0.00
Received By cthroop Date 2019-08-02 Time 16:10 Sent To  
Notes
2019-08-05 13:38:25ADDRESS: 110 FLAGLER LANE PERMIT # 19050386
 TYPE: BLD-RES NEW SFR
  
 BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 2ND REVIEW
  
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 THOSE ITEMS THAT HAVE BEEN ADDRESSED FROM 1ST REVIEW
 HAVE BEEN NOTED CORRECTED.
  
 THOSE ITEMS THAT HAVE NOT BEEN ADDRESSED FROM 1ST
 REVIEW (NOT ADDRESSED) IN PARANTHESIS.
  
 ANY NEW ITEM WILL BE LISTED AT THE END OF COMMENTS.
  
 1. PROVIDE SITE DRAINAGE PLAN. CORRECTED
  
 2. PROVIDE A CURRENT SURVEY. (SURVEYORS SIG. & SEAL ARE
 NOT DIGITAL. PROVIDE HARD COPY WITH WET SEAL)
  
 3. ELEVATION CERTIFICATES ARE REQUIRED. SEE COMMENTS
 UNDER NFIP REVIEW. (INCOMPLETE)
  
 4. PROVIDE PRODUCT APPROVALS FOR ALL WINDOWS AND
 EXTERIOR DOORS. (NOT ADDRESSED - PROVIDE PRODUCT
 APPROVALS LISTED ON PRODUCT APPROVAL SCHEDULE)
 FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE WINDOW AND DOOR SUBMITTALS.
 OPTION:
 107.3.4.1 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS
 SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON
 THE CONSTRUCTION DOCUMENTS FOR REVIEW BY THE BUILDING
 OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 5. PROVIDE SOILS REPORT. (ENGINEER'S SIG. & SEAL ARE
 NOT DIGITAL. PROVIDE HARD COPY WITH WET SEAL)
  
 6. PALM BEACH COUNTY IMPACT FEES ARE REQUIRED. (OPEN)
  
 7. PROVIDE AN ACCURATELEY COMPLETED ENERGY SUBMITTAL.
 (NOT ADDRESSED)
 FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405
 (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE
 SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE
 COMPLIANCE BY SECTION 405.
  
 8. PROVIDE FLOOD VENTS IN GARAGE WALLS. (NOT ADDRESSED)
 1612.5 FLOOD HAZARD DOCUMENTATION.
 THE FOLLOWING DOCUMENTATION SHALL BE PREPARED AND
 SEALED BY A REGISTERED DESIGN PROFESSIONAL AND
 SUBMITTED TO THE BUILDING OFFICIAL:
  
 1. FOR CONSTRUCTION IN FLOOD HAZARD AREAS OTHER THAN
 COASTAL HIGH HAZARD AREAS:
 1.1. THE ELEVATION OF THE LOWEST FLOOR, INCLUDING
 BASEMENT, AS REQUIRED BY THE FOUNDATION INSPECTION AND
 THE FINAL INSPECTION IN SECTION 110.3.
 1.2. FOR FULLY ENCLOSED AREAS BELOW THE DESIGN FLOOD
 ELEVATION WHERE PROVISIONS TO ALLOW FOR THE AUTOMATIC
 ENTRY AND EXIT OF FLOODWATERS DO NOT MEET THE MINIMUM
 REQUIREMENTS IN SECTION 2.6.2.1 OF ASCE 24,
 CONSTRUCTION DOCUMENTS SHALL INCLUDE A STATEMENT THAT
 THE DESIGN WILL PROVIDE FOR EQUALIZATION OF HYDROSTATIC
 FLOOD FORCES IN ACCORDANCE WITH SECTION 2.6.2.2 OF ASCE
 24.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-06-05 Cont ID  
Sent By cthroop Date 2019-06-05 Time 14:09 Rev Time 0.00
Received By cthroop Date 2019-05-30 Time 13:43 Sent To  
Notes
2019-06-05 14:57:15ADDRESS: 110 FLAGLER LANE PERMIT # 19050386
 TYPE: BLD-RES NEW SFR
  
 BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC M = FLORIDA BUILDING CODE MECHANICAL 2017 6TH
 EDITION
 FBC P = FLORIDA BUILDING CODE PLUMBING 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 1. PROVIDE SITE DRAINAGE PLAN.
 FBC R401.3 SITE DRAINAGE
 PROVIDE TWO SETS OF A SITE DRAINAGE PLAN SHOWING
 COMPLIANCE WITH FBC R401.3 DRAINAGE.
 SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER
 CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION THAT
 DOES NOT CREATE A HAZARD.
 LOTS SHALL BE GRADED TO DRAIN SURFACE WATER AWAY FROM
 FOUNDATION WALLS. THE GRADE SHALL FALL A MINIMUM OF 6
 INCHES WITHIN THE FIRST 10 FEET.
 EXCEPTION: WHERE LOT LINES, WALLS, SLOPES OR OTHER
 PHYSICAL BARRIERS PROHIBIT 6 INCHES OF FALL WITHIN 10
 FEET, DRAINS OR SWALES SHALL BE CONSTRUCTED TO ENSURE
 DRAINAGE AWAY FROM THE STRUCTURE.
 IMPERVIOUS SURFACES WITHIN 10 FEET OF THE BUILDING
 FOUNDATION SHALL BE SLOPED A MINIMUM OF
 2 PERCENT AWAY FROM THE BUILDING.
  
 FBC R 401.3 (DRAINAGE)
 FBC 107.2.5 (SITE PLAN)
 FBC 110.9 (IMPACT OF CONSTRUCTION)
  
 2. PROVIDE A CURRENT SURVEY.
 107.2.5 SITE PLAN. THE CONSTRUCTION DOCUMENTS SUBMITTED
 WITH THE APPLICATION FOR PERMIT SHALL BE ACCOMPANIED BY
 A SITE PLAN SHOWING TO SCALE THE SIZE AND LOCATION OF
 NEW CONSTRUCTION AND EXISTING STRUCTURES ON THE SITE,
 DISTANCES FROM LOT LINES, THE ESTABLISHED STREET GRADES
 AND THE PROPOSED FINISHED GRADES, DEPICTING THE
 PROPOSED LOT DRAINAGE AND, AS APPLICABLE, FLOOD HAZARD
 AREAS, FLOODWAYS, AND DESIGN FLOOD ELEVATIONS; AND IT
 SHALL BE DRAWN IN ACCORDANCE WITH AN ACCURATE AND
 INCLUDED ON A BOUNDARY LINE SURVEY.
  
 3. ELEVATION CERTIFICATES ARE REQUIRED. SEE COMMENTS
 UNDER NFIP REVIEW.
  
 4. PROVIDE PRODUCT APPROVALS FOR ALL WINDOWS AND
 EXTERIOR DOORS.
 FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE WINDOW AND DOOR SUBMITTALS.
  
 5. PROVIDE SOILS REPORT.
 BASED ON THE OFFICIAL ZONING MAP REFERRED TO IN SECTION
 53-2 OF CHAPTER 53 OF THE CITY CODE OF WEST PALM BEACH,
 FLORIDA, 1962, ADOPTED JUNE 15, 1964, YOUR PROPERTY,
 LOCATED AT 110 FLAGLER LANE, W.P.B., FL, IS LOCATED IN
 AN AREA OF QUESTIONABLE SOILS AND REQUIRES
 INVESTIGATION BY A GEOTECHNICAL ENGINEER WITH ITS
 SUBSEQUENT SOILS REPORT AND DENSITY TESTING.
 THIS ONLY RELIEVES YOU FROM THE STATUTORY REQUIREMENTS
 OF THE FLORIDA BUILDING CODE. THERE MAY BE OTHER
 ENTITIES, SUCH AS YOUR DESIGN PROFESSIONAL OR YOUR
 LENDING INSTITUTION THAT MAY REQUIRE THE ABOVE
 MENTIONED INVESTIGATION.
  
 6. PALM BEACH COUNTY IMPACT FEES ARE REQUIRED.
  
 7. PROVIDE AN ACCURATELEY COMPLETED ENERGY SUBMITTAL.
 FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405
 (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE
 SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE
 COMPLIANCE BY SECTION 405.
  
 R401.3 ENERGY PERFORMANCE LEVEL (EPL) DISPLAY CARD
 (MANDATORY).
  
 8. PROVIDE FLOOD VENTS IN GARAGE WALLS.
 1612.5 FLOOD HAZARD DOCUMENTATION.
 THE FOLLOWING DOCUMENTATION SHALL BE PREPARED AND
 SEALED BY A REGISTERED DESIGN PROFESSIONAL AND
 SUBMITTED TO THE BUILDING OFFICIAL:
  
 1. FOR CONSTRUCTION IN FLOOD HAZARD AREAS OTHER THAN
 COASTAL HIGH HAZARD AREAS:
 1.1. THE ELEVATION OF THE LOWEST FLOOR, INCLUDING
 BASEMENT, AS REQUIRED BY THE FOUNDATION INSPECTION AND
 THE FINAL INSPECTION IN SECTION 110.3.
 1.2. FOR FULLY ENCLOSED AREAS BELOW THE DESIGN FLOOD
 ELEVATION WHERE PROVISIONS TO ALLOW FOR THE AUTOMATIC
 ENTRY AND EXIT OF FLOODWATERS DO NOT MEET THE MINIMUM
 REQUIREMENTS IN SECTION 2.6.2.1 OF ASCE 24,
 CONSTRUCTION DOCUMENTS SHALL INCLUDE A STATEMENT THAT
 THE DESIGN WILL PROVIDE FOR EQUALIZATION OF HYDROSTATIC
 FLOOD FORCES IN ACCORDANCE WITH SECTION 2.6.2.2 OF ASCE
 24.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2019-09-06 Cont ID  
Sent By jpearson Date 2019-09-06 Time 10:32 Rev Time 0.00
Received By jpearson Date 2019-09-06 Time 10:32 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-08-05 Cont ID  
Sent By cthroop Date 2019-08-05 Time 14:44 Rev Time 0.00
Received By cthroop Date 2019-08-02 Time 16:10 Sent To  
Notes
2019-08-05 15:25:46ADDRESS: 110 FLAGLER LANE PERMIT # 19050386
 TYPE: BLD-RES NEW SFR
  
 ELECTRICAL PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 2ND REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 THOSE ITEMS THAT HAVE BEEN ADDRESSED FROM 1ST REVIEW
 HAVE BEEN NOTED CORRECTED.
  
 THOSE ITEMS THAT HAVE NOT BEEN ADDRESSED FROM 1ST
 REVIEW (NOT ADDRESSED) IN PARANTHESIS.
  
 ANY NEW ITEM WILL BE LISTED AT THE END OF COMMENTS.
  
  
 1. AIC RATING OF SERVICE DISCONNECT AND PANEL (PER
 PROVISO ON PLAN)
 FBC R E3606.3AVAILABLE SHORT-CIRCUIT CURRENT.
  
 2. PROVIDE LOAD CALCULATIONS BASED ON FBC R TABLE
 3602.2. CORRECTED
  
 3. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT
 SERVICE. SHOW ON PLAN. NEC 250.94; FBC RE E3609.3 (SEE
 NOTE ON PLAN)
  
 4. EMERGENCY GENERATOR AND TRANSFER SWITCH WILL BE BY
 SEPERATE PERMIT. N/A
  
 5. REMOVE #4 GROUNDING CONDUTOR BETWEEN METER AND
 DISCONNECT. CORRECTED
  
 6. NOTE A ON ELECTRICAL NOTES REFERENCING ARC-FAULT
 PROTECTION SHALL INCLUDE KITCHENS. CORRECTED
  
 7. . PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF
 THE LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES
 SHALL BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT
 OF THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE.
 FBC EC R404.1. CORRECTED
  
 8. PROVIDE GFCI PROTECTION FOR DISHWASHERS. NEC
 210.8(D); FBC RE E3902.10. CORRECTED
  
 9. SEVERAL AREAS DO NOT COMPLY WITH THE WALL SPACING
 REQUIREMENTS FOR OUTLETS. RECEPTACLES SHALL BE
 INSTALLED SO THAT NO POINT MEASURED HORIZONTALLY ALONG
 THE FLOOR LINE OF ANY WALL SPACE IS MORE THAN 6 FEET
 FROM A RECEPTACLE OUTLET. PROVIDE CORRECTION. NEC
 210.52; FBC RE E3901.2.1. CORRECTED
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-06-06 Cont ID  
Sent By cthroop Date 2019-06-06 Time 13:23 Rev Time 0.00
Received By cthroop Date 2019-05-30 Time 13:46 Sent To  
Notes
2019-06-06 13:42:56ADDRESS: 110 FLAGLER LANE PERMIT # 19050386
 TYPE: BLD-RES NEW SFR
  
 ELECTRICAL PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC M = FLORIDA BUILDING CODE MECHANICAL 2017 6TH
 EDITION
 FBC P = FLORIDA BUILDING CODE PLUMBING 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 1. AIC RATING OF SERVICE DISCONNECT AND PANEL
 FBC R E3606.3AVAILABLE SHORT-CIRCUIT CURRENT.
 SERVICE EQUIPMENT SHALL BE SUITABLE FOR THE MAXIMUM
 FAULT CURRENT AVAILABLE AT ITS SUPPLY TERMINALS, BUT
 NOT LESS THAN 10,000 AMPERES. (110.9)
  
 PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10; FBC RE E3404.2 & FBC RE E3606.3
  
 2. PROVIDE LOAD CALCULATIONS BASED ON FBC R TABLE
 3602.2.
 PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL LOADS.
 NEC 220; FBC RE E3602.2.
 2A. REMOVE CALCULATION FOR CONVIENCE LIGHTING.
 2B. GENERAL LIGHTING LOAD WILL BE CALCULATED BY
 MULTIPLYING THE SQUARE FOOTAGE BY 3 VA.
 2C. HVAC DOES NOT REQUIRE A DF OF 1.25.
  
 3. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT
 SERVICE. SHOW ON PLAN. NEC 250.94; FBC RE E3609.3
  
 4. EMERGENCY GENERATOR AND TRANSFER SWITCH WILL BE BY
 SEPERATE PERMIT.
  
 5. REMOVE #4 GROUNDING CONDUTOR BETWEEN METER AND
 DISCONNECT.
 THE # 4 EQUIPMENT GROUNDING CONDUCTOR SHOULD NOT BE
 INCLUDED IN THE CONDUIT FROM FPL TO THE METER OR IN THE
 CONDUIT FROM THE METER TO THE MAIN DISCONNECT SWITCH.
 PROVIDE CORRECTION. NEC 250.6; FBC RE E3610.4.
  
 6. NOTE A ON ELECTRICAL NOTES REFERENCING ARC-FAULT
 PROTECTION SHALL INCLUDE KITCHENS.
 BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15-
 AND 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY
 ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES,
 DENS, BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS,
 HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS
 SHALL BE AFCI PROTECTED. PROVIDE COMPLIANCE. NEC
 210.12; FBC RE E3902.16.
  
 7. . PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF
 THE LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES
 SHALL BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT
 OF THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE.
 FBC EC R404.1.
  
 8. PROVIDE GFCI PROTECTION FOR DISHWASHERS. NEC
 210.8(D); FBC RE E3902.10.
  
 9. SEVERAL AREAS DO NOT COMPLY WITH THE WALL SPACING
 REQUIREMENTS FOR OUTLETS. RECEPTACLES SHALL BE
 INSTALLED SO THAT NO POINT MEASURED HORIZONTALLY ALONG
 THE FLOOR LINE OF ANY WALL SPACE IS MORE THAN 6 FEET
 FROM A RECEPTACLE OUTLET. PROVIDE CORRECTION. NEC
 210.52; FBC RE E3901.2.1.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  
  
  

Review Stop ENG ENGINEERING CSD
Rev No 4 Status N Date 2019-10-07 Cont ID  
Sent By rrossano Date 2019-10-07 Time   Rev Time 0.00
Received By   Date 2019-10-07 Time   Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 3 Status F Date 2019-09-16 Cont ID  
Sent By rrossano Date 2019-09-16 Time   Rev Time 0.00
Received By rrossano Date 2019-09-16 Time   Sent To  
Notes
2019-09-16 11:22:58PLEASE ADDRESS BUILDING COMMENTS.

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2019-09-10 Cont ID  
Sent By lmarchan Date 2019-09-10 Time 11:20 Rev Time 0.00
Received By lmarchan Date 2019-09-10 Time 11:20 Sent To  
Notes
2019-09-10 11:20:42ADD NEW STOP FOR NEXT REVIEW CYCLE

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2019-08-26 Cont ID  
Sent By Mgonzale Date 2019-08-26 Time   Rev Time 1.00
Received By mgonzale Date 2019-08-26 Time   Sent To I
Notes
2019-08-26 13:06:26ADDRESS PLANNING COMMENTS / NO FURTHER ENGINEERING
 COMMENTS:
  
  
  
  
  
  
  
  
2019-08-21 10:04:54*ADDED AT THE REQUEST OF THE APPLICANT*

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2019-09-07 Cont ID  
Sent By cthroop Date 2019-09-07 Time 08:36 Rev Time 0.00
Received By cthroop Date 2019-09-05 Time 09:23 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2019-08-05 Cont ID  
Sent By cthroop Date 2019-08-05 Time 15:50 Rev Time 0.00
Received By cthroop Date 2019-08-02 Time 16:10 Sent To  
Notes
2019-08-05 15:55:32ADDRESS: 110 FLAGLER LANE PERMIT # 19050386
 TYPE: BLD-RES NEW SFR
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 GAS PLAN REVIEW
  
 2ND REVIEW:
  
 RESULTS: DENIED
  
 GAS COMMENTS:
  
 1. SUBMIT TWO COPIES OF AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS THE LENGTH OF ALL CUT SECTIONS OF PIPE
 PER 2017 FBC-FUEL GAS, SECS. 402.4.1, 402.4.2. OR 2017
 FBC-R SEC. G2413.4.1, G2413.4.2.
  
 2. SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE
 CORRUGATED STAINLESS STEEL TUBING
  
 (IF APPLICABLE) FOR EACH PIPE SIZE. WPB AMENDMENTS TO
 FBC SEC.107.2.1.
  
 3. TYPE OF GAS (LP OR NATURAL).WPB AMEND. TO FBC SEC.
 107.2.1.
  
 4. LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL
 BTU LOAD ON THE SYSTEM. REFER TO THE 2017 FBC-FUEL GAS
 SECS.401.8, 402.2, AND TABLES 402.4 (1) THRU 402.4 (37)
 OR 2017 FBC-RES. SEC. G2413.3, G2413.4 AND TABLES
 G2413.4 (1 ) THROUGH G2413.4 (21).
  
 5. SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS
 METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND / OR SYSTEM PER THE 2017
 FBC-FUEL GAS SEC.402.4.1, 402.4.2, OR 2017 FBC-RES.
 SEC. G 2413.4.1, G2413.4.2.
  
 6. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2017
 FBC-FUEL GAS CODE SEC.304.1, 614.6 (CLOTHES DRYERS) OR
 2017 FBC-RES. SEC.G 2407.1 AND G2439.4 (CLOTHES
 DRYERS).
  
 7. INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM
 ON THE PLAN PER 2017 FBC-FUEL GAS SEC.402.1, 402.4.3
 THRU 402.6 OR 2017 FBC RES. SEC. G2413.2, G2413.4.3.
  
 8. SUBMIT TWO COPIES OF A DETAIL SHOWING THE TYPE OF
 VENT, LOCATION, SIZE, TERMINATION POINT, HEIGHT ABOVE
 THE ROOF AND ANCHORING DETAILS OF THE GAS VENT(S) PER
 2017 FBC-FUEL GAS SECS. 502 THRU 505 OR 2017 FBC-RES.
 SEC.G2426 THROUGH G2439.
  
 9. SUBMIT TWO COPIES OF THE MANUFACTURER?S
 SPECIFICATION SHEETS / INSTALLATION MANUAL FOR ALL GAS
 EQUIPMENT AND REGULATORS TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND FBC-2017 FUEL GAS CODE
 SEC. 402.2, AND 301.3 OR 2017 FBC-RES. SEC. G2404.3.
 GAS APPLIANCES SHALL BE LISTED AND LABELED. THE
 INSTALLATION MANUALS FOR ALL GAS APPLIANCES / EQUIPMENT
 SHALL BE ONSITE AT THE TIME OF INSPECTION. FGC
 SEC.305.1, FBC-RES. SEC.G2408.1.
  
 17) SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES
 USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE
 PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM
 THE GAS CODE OR OTHER STANDARD THAT WERE USED IN THE
 DESIGN OF THIS GAS SYSTEM. REFER TO THE 2017 FBC-FUEL
 GAS SECS. 401.4, 401.8, 402.3, AND TABLES 402.4 (1)
 THRU 402.4 (37) OR 2017 FBC-RES. SEC. G2413.3, G2412.8,
 G2413.1, G2413.2, & G2413.3.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2019-05-22 Cont ID  
Sent By gjohnson Date 2019-05-22 Time 15:24 Rev Time 0.00
Received By gjohnson Date 2019-05-22 Time 15:24 Sent To  
Notes
2019-05-22 15:28:041ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. SUBMIT TWO COPIES OF AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS THE LENGTH OF ALL CUT SECTIONS OF PIPE
 PER 2017 FBC-FUEL GAS, SECS. 402.4.1, 402.4.2. OR 2017
 FBC-R SEC. G2413.4.1, G2413.4.2.
  
 2. SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE
 CORRUGATED STAINLESS STEEL TUBING
  
 (IF APPLICABLE) FOR EACH PIPE SIZE. WPB AMENDMENTS TO
 FBC SEC.107.2.1.
  
 3. TYPE OF GAS (LP OR NATURAL).WPB AMEND. TO FBC SEC.
 107.2.1.
  
 4. LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL
 BTU LOAD ON THE SYSTEM. REFER TO THE 2017 FBC-FUEL GAS
 SECS.401.8, 402.2, AND TABLES 402.4 (1) THRU 402.4 (37)
 OR 2017 FBC-RES. SEC. G2413.3, G2413.4 AND TABLES
 G2413.4 (1 ) THROUGH G2413.4 (21).
  
 5. SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS
 METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND / OR SYSTEM PER THE 2017
 FBC-FUEL GAS SEC.402.4.1, 402.4.2, OR 2017 FBC-RES.
 SEC. G 2413.4.1, G2413.4.2.
  
 6. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2017
 FBC-FUEL GAS CODE SEC.304.1, 614.6 (CLOTHES DRYERS) OR
 2017 FBC-RES. SEC.G 2407.1 AND G2439.4 (CLOTHES
 DRYERS).
  
 7. INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM
 ON THE PLAN PER 2017 FBC-FUEL GAS SEC.402.1, 402.4.3
 THRU 402.6 OR 2017 FBC RES. SEC. G2413.2, G2413.4.3.
  
 8. SUBMIT TWO COPIES OF A DETAIL SHOWING THE TYPE OF
 VENT, LOCATION, SIZE, TERMINATION POINT, HEIGHT ABOVE
 THE ROOF AND ANCHORING DETAILS OF THE GAS VENT(S) PER
 2017 FBC-FUEL GAS SECS. 502 THRU 505 OR 2017 FBC-RES.
 SEC.G2426 THROUGH G2439.
  
 9. SUBMIT TWO COPIES OF THE MANUFACTURER?S
 SPECIFICATION SHEETS / INSTALLATION MANUAL FOR ALL GAS
 EQUIPMENT AND REGULATORS TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND FBC-2017 FUEL GAS CODE
 SEC. 402.2, AND 301.3 OR 2017 FBC-RES. SEC. G2404.3.
 GAS APPLIANCES SHALL BE LISTED AND LABELED. THE
 INSTALLATION MANUALS FOR ALL GAS APPLIANCES / EQUIPMENT
 SHALL BE ONSITE AT THE TIME OF INSPECTION. FGC
 SEC.305.1, FBC-RES. SEC.G2408.1.
  
 17) SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES
 USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE
 PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM
 THE GAS CODE OR OTHER STANDARD THAT WERE USED IN THE
 DESIGN OF THIS GAS SYSTEM. REFER TO THE 2017 FBC-FUEL
 GAS SECS. 401.4, 401.8, 402.3, AND TABLES 402.4 (1)
 THRU 402.4 (37) OR 2017 FBC-RES. SEC. G2413.3, G2412.8,
 G2413.1, G2413.2, & G2413.3.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2019-10-22 Cont ID  
Sent By lmarchan Date 2019-10-22 Time 09:17 Rev Time 0.00
Received By lmarchan Date 2019-10-15 Time 07:43 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2019-10-07 Cont ID  
Sent By cpuell Date 2019-10-07 Time 15:01 Rev Time 0.00
Received By cpuell Date 2019-10-01 Time 07:38 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2019-09-16 Cont ID  
Sent By shill Date 2019-09-16 Time 13:34 Rev Time 0.00
Received By shill Date 2019-09-12 Time 11:14 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-09-10 Cont ID  
Sent By rmcdouga Date 2019-09-10 Time 11:28 Rev Time 0.00
Received By rmcdouga Date 2019-08-21 Time 12:21 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-08-05 Cont ID  
Sent By cthroop Date 2019-08-05 Time 16:00 Rev Time 0.00
Received By cthroop Date 2019-07-25 Time 10:20 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-06-06 Cont ID  
Sent By cthroop Date 2019-06-06 Time 13:43 Rev Time 0.00
Received By cthroop Date 2019-05-16 Time 13:25 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2019-10-22 Cont ID  
Sent By lmarchan Date 2019-10-22 Time 09:16 Rev Time 0.00
Received By lmarchan Date 2019-10-15 Time 07:44 Sent To  
Notes
2019-10-22 09:16:30RECEIPT - 2019-1023-21 - $141.30 - PAID
2019-10-15 07:44:3410/15/19 EMAILED IMPACT FEE OFFICE. LEM

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2019-06-04 Cont ID  
Sent By cthroop Date 2019-06-04 Time 16:55 Rev Time 0.00
Received By cthroop Date 2019-05-30 Time 13:46 Sent To  
Notes
2019-06-04 16:56:04IMPACT FEES - DIGITAL SUBMITTALS
  
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected] .
  

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2019-10-04 Cont ID  
Sent By cthroop Date 2019-10-04 Time 14:44 Rev Time 0.00
Received By cthroop Date 2019-10-04 Time 12:47 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2019-09-14 Cont ID  
Sent By cthroop Date 2019-09-14 Time 11:15 Rev Time 0.00
Received By cthroop Date 2019-09-14 Time 08:07 Sent To  
Notes
2019-09-14 11:35:39ADDRESS: 110 FLAGLER LANE PERMIT # 19050386
 TYPE: BLD-RES NEW SFR
  
 MECHANICAL PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 4TH REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 THOSE ITEMS THAT HAVE BEEN ADDRESSED FROM 1ST REVIEW
 HAVE BEEN NOTED CORRECTED.
  
 THOSE ITEMS THAT HAVE NOT BEEN ADDRESSED FROM 1ST
 REVIEW (NOT ADDRESSED) IN PARANTHESIS.
  
 ANY NEW ITEM WILL BE LISTED AT THE END OF COMMENTS.
  
 1. PROVIDE AN ACCURATELEY COMPLETED ENERGY SUBMITTAL.
 (NOT ADDRESSED) (ENERGY SUBMITTAL SHALL BE SIGNED BY
 PREPERARER AND OWNER/AGENT)
 FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405
 (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE
 SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE
 COMPLIANCE BY SECTION 405.
  
 2. EXTERIOR MECHANICAL EQUIPMENT SHALL BE INSTALLED AT
 OR ABOVE THE DESIGN FLOOD ELEVATION. (DFE) (NOT
 ADDRESSED - ELEVATION OF EQUIPMENT ON ELEVATION
 CERTIFICATE IS BELOW DESIGN FLOOD ELEVATION) (ELEVATION
 CERTIFICATE)
  
 3. CONDENSER SHALL BE INSTALLED AT OR ABOVE THE DESIGN
 FLOOD ELEVATION (DFE). (SECTION C2E SHOWS ELEVATION OF
 MECHANICAL EQUIPMENT AT 9.0 FEET NAVD. DFE IS 9.4 FEET
 NAVD)
 FBC R M1401.5 AND FBC R 322.1.6
 M1401.5 FLOOD HAZARD.
 IN FLOOD HAZARD AREAS AS ESTABLISHED BY TABLE
 R301.2(1), HEATING AND COOLING EQUIPMENT AND APPLIANCES
 SHALL BE LOCATED OR INSTALLED IN ACCORDANCE WITH
 SECTION R322.1.6.
 R322.1.6 PROTECTION OF MECHANICAL, PLUMBING AND
 ELECTRICAL SYSTEMS.
  
 4. PROVIDE MANUFACTURERS SPECIFICATIONS FOR EXHAUST
 HOOD. PROVIDE EXHAUST RATE IN CUBIC FEET PER MINUTE.
 (NOT ADDRESSED) (NOT PROVIDED)
 G2408.1 (305.1)GENERAL. FBC SEC. 107.2.1.
 EQUIPMENT AND APPLIANCES SHALL BE INSTALLED AS REQUIRED
 BY THE TERMS OF THEIR APPROVAL, IN ACCORDANCE WITH THE
 CONDITIONS OF LISTING, THE MANUFACTURER?S INSTRUCTIONS
 AND THIS CODE.
  
 5. PROVIDE MAKE UP AIR CALCULATIONS. (NOT ADDRESSED)
 (NOT PROVIDED) (NOTE ON PLAN PAGE M-1 STATES MAKE UP
 AIR DETAIL IS LOCATED ON BUILDING SECTION E-E. NO
 DETAIL PROVIDED)
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 M1503.4 MAKEUP AIR REQUIRED.
 EXHAUST HOOD SYSTEMS CAPABLE OF EXHAUSTING IN EXCESS OF
 400 CUBIC FEET PER MINUTE (0.19 M3/S) SHALL BE
 MECHANICALLY OR NATURALLY PROVIDED WITH MAKEUP AIR AT A
 RATE APPROXIMATELY EQUAL TO THE EXHAUST AIR RATE. SUCH
 MAKEUP AIR SYSTEMS SHALL BE EQUIPPED WITH NOT LESS THAN
 ONE DAMPER. EACH DAMPER SHALL BE A GRAVITY DAMPER OR AN
 ELECTRICALLY OPERATED DAMPER THAT AUTOMATICALLY OPENS
 WHEN THE EXHAUST SYSTEM OPERATES. DAMPERS SHALL BE
 ACCESSIBLE FOR INSPECTION, SERVICE, REPAIR AND
 REPLACEMENT WITHOUT REMOVING PERMANENT CONSTRUCTION OR
 ANY OTHER DUCTS NOT CONNECTED TO THE DAMPER BEING
 INSPECTED, SERVICED, REPAIRED OR REPLACED.
 EXCEPTION: IN A SINGLE-FAMILY DWELLING, MAKE-UP AIR IS
 NOT REQUIRED FOR RANGE HOOD EXHAUST SYSTEMS CAPABLE OF
 EXHAUSTING:
 1. (A)FOUR HUNDRED CUBIC FEET PER MINUTE OR LESS; OR
 2. (B)MORE THAN 400 CUBIC FEET PER MINUTE BUT NO MORE
 THAN 800 CUBIC FEET PER MINUTE IF THERE ARE NO GRAVITY
 VENT APPLIANCES WITHIN THE CONDITIONED LIVING SPACE OF
 THE STRUCTURE.
  
 6. CORRECTED
  
 7. PROVIDE MANUFACTURERS INSTALLATION INSTRUCTIONS FOR
 FIREPLACE. (NOT ADDRESSED) (NOT PROVIDED)
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 8. PROVIDE PRODUCT APPROVAL OR ENGINEERED DESIGN FOR CU
 TIE DOWN. (NOT ADDRESSED)
  
 9. CORRECTED
  
 NEW COMMENTS:
  
 10. PROVIDE SHOP DRAWINGS FOR KITCHEN EXHAUST HOOD.
 (NOT PROVIDED)
  
 11. PROVIDE MAKE UP AIR CALCULATIONS FOR KITCHEN
 EXHAUST HOOD. (NOT PROVIDED)
  
 12. NOTE ON PLAN PAGE M-1 STATES OWNER MAY SUBSTITUTE
 EQUIPMENT. ANY CHANGES FROM APPORVED PLANS WILL REQUIRE
 A REVISION.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2019-09-07 Cont ID  
Sent By cthroop Date 2019-09-07 Time 08:46 Rev Time 0.00
Received By cthroop Date 2019-09-05 Time 09:22 Sent To  
Notes
2019-09-07 08:50:22ADDRESS: 110 FLAGLER LANE PERMIT # 19050386
 TYPE: BLD-RES NEW SFR
  
 MECHANICAL PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 2ND REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 THOSE ITEMS THAT HAVE BEEN ADDRESSED FROM 1ST REVIEW
 HAVE BEEN NOTED CORRECTED.
  
 THOSE ITEMS THAT HAVE NOT BEEN ADDRESSED FROM 1ST
 REVIEW (NOT ADDRESSED) IN PARANTHESIS.
  
 ANY NEW ITEM WILL BE LISTED AT THE END OF COMMENTS.
  
 1. PROVIDE AN ACCURATELEY COMPLETED ENERGY SUBMITTAL.
 (NOT ADDRESSED) (ELEVATION CERTIFICATE UNSUCESSFULLY
 UPLOADED, NO INFORMATION AVAILABLE)
 FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405
 (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE
 SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE
 COMPLIANCE BY SECTION 405.
  
 2. EXTERIOR MECHANICAL EQUIPMENT SHALL BE INSTALLED AT
 OR ABOVE THE DESIGN FLOOD ELEVATION. (DFE) (NOT
 ADDRESSED - ELEVATION OF EQUIPMENT ON ELEVATION
 CERTIFICATE IS BELOW DESIGN FLOOD ELEVATION) (ELEVATION
 CERTIFICATE UNSUCESSFULLY UPLOADED, NO INFORMATION
 AVAILABLE)
  
 3. CONDENSER SHALL BE INSTALLED AT OR ABOVE THE DESIGN
 FLOOD ELEVATION (DFE). (ELEVATION CERTIFICATE
 UNSUCESSFULLY UPLOADED, NO INFORMATION AVAILABLE)
 FBC R M1401.5 AND FBC R 322.1.6
 M1401.5 FLOOD HAZARD.
 IN FLOOD HAZARD AREAS AS ESTABLISHED BY TABLE
 R301.2(1), HEATING AND COOLING EQUIPMENT AND APPLIANCES
 SHALL BE LOCATED OR INSTALLED IN ACCORDANCE WITH
 SECTION R322.1.6.
 R322.1.6 PROTECTION OF MECHANICAL, PLUMBING AND
 ELECTRICAL SYSTEMS.
  
 4. PROVIDE MANUFACTURERS SPECIFICATIONS FOR EXHAUST
 HOOD. PROVIDE EXHAUST RATE IN CUBIC FEET PER MINUTE.
 (NOT ADDRESSED) (NOT PROVIDED)
 G2408.1 (305.1)GENERAL. FBC SEC. 107.2.1.
 EQUIPMENT AND APPLIANCES SHALL BE INSTALLED AS REQUIRED
 BY THE TERMS OF THEIR APPROVAL, IN ACCORDANCE WITH THE
 CONDITIONS OF LISTING, THE MANUFACTURER?S INSTRUCTIONS
 AND THIS CODE.
  
 5. PROVIDE MAKE UP AIR CALCULATIONS. (NOT ADDRESSED)
 (NOT PROVIDED)
 M1503.4 MAKEUP AIR REQUIRED.
 EXHAUST HOOD SYSTEMS CAPABLE OF EXHAUSTING IN EXCESS OF
 400 CUBIC FEET PER MINUTE (0.19 M3/S) SHALL BE
 MECHANICALLY OR NATURALLY PROVIDED WITH MAKEUP AIR AT A
 RATE APPROXIMATELY EQUAL TO THE EXHAUST AIR RATE. SUCH
 MAKEUP AIR SYSTEMS SHALL BE EQUIPPED WITH NOT LESS THAN
 ONE DAMPER. EACH DAMPER SHALL BE A GRAVITY DAMPER OR AN
 ELECTRICALLY OPERATED DAMPER THAT AUTOMATICALLY OPENS
 WHEN THE EXHAUST SYSTEM OPERATES. DAMPERS SHALL BE
 ACCESSIBLE FOR INSPECTION, SERVICE, REPAIR AND
 REPLACEMENT WITHOUT REMOVING PERMANENT CONSTRUCTION OR
 ANY OTHER DUCTS NOT CONNECTED TO THE DAMPER BEING
 INSPECTED, SERVICED, REPAIRED OR REPLACED.
 EXCEPTION: IN A SINGLE-FAMILY DWELLING, MAKE-UP AIR IS
 NOT REQUIRED FOR RANGE HOOD EXHAUST SYSTEMS CAPABLE OF
 EXHAUSTING:
 1. (A)FOUR HUNDRED CUBIC FEET PER MINUTE OR LESS; OR
 2. (B)MORE THAN 400 CUBIC FEET PER MINUTE BUT NO MORE
 THAN 800 CUBIC FEET PER MINUTE IF THERE ARE NO GRAVITY
 VENT APPLIANCES WITHIN THE CONDITIONED LIVING SPACE OF
 THE STRUCTURE.
  
 6. NOTE ON PLAN PAGE M-1 REFERENCES DETAIL D/S-4 FOR
 SECTION VIEW OF MSU#1 & FCU#1. THERE IS NO DETAIL ON
 PAGE S-4. PLEASE CLARIFY. CORRECTED
  
 7. PROVIDE MANUFACTURERS INSTALLATION INSTRUCTIONS FOR
 FIREPLACE. (NOT ADDRESSED) (NOT PROVIDED)
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 8. PROVIDE PRODUCT APPROVAL OR ENGINEERED DESIGN FOR CU
 TIE DOWN. (NOT ADDRESSED) (NOT PROVIDED)
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 9. PROVIDE CFM RATING FOR BATHROOM EXHAUST FANS.
 CORRECTED
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 NEW COMMENTS:
  
 10. PROVIDE SHOP DRAWINGS FOR KITCHEN EXHAUST HOOD.
 (NOT PROVIDED)
  
 11. PROVIDE MAKE UP AIR CALCULATIONS FOR KITCHEN
 EXHAUST HOOD. (NOT PROVIDED)
  
 12. NOTE ON PLAN PAGE M-1 STATES OWNER MAY SUBSTITUTE
 EQUIPMENT. ANY CHANGES FROM APPORVED PLANS WILL REQUIRE
 A REVISION.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2019-08-05 Cont ID  
Sent By cthroop Date 2019-08-05 Time 14:01 Rev Time 0.00
Received By cthroop Date 2019-08-02 Time 16:10 Sent To  
Notes
2019-08-05 14:23:40ADDRESS: 110 FLAGLER LANE PERMIT # 19050386
 TYPE: BLD-RES NEW SFR
  
 MECHANICAL PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 2ND REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 THOSE ITEMS THAT HAVE BEEN ADDRESSED FROM 1ST REVIEW
 HAVE BEEN NOTED CORRECTED.
  
 THOSE ITEMS THAT HAVE NOT BEEN ADDRESSED FROM 1ST
 REVIEW (NOT ADDRESSED) IN PARANTHESIS.
  
 ANY NEW ITEM WILL BE LISTED AT THE END OF COMMENTS.
  
 1. PROVIDE AN ACCURATELEY COMPLETED ENERGY SUBMITTAL.
 (NOT ADDRESSED)
 FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405
 (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE
 SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE
 COMPLIANCE BY SECTION 405.
  
 2. EXTERIOR MECHANICAL EQUIPMENT SHALL BE INSTALLED AT
 OR ABOVE THE DESIGN FLOOD ELEVATION. (DFE) (NOT
 ADDRESSED - ELEVATION OF EQUIPMENT ON ELEVATION
 CERTIFICATE IS BELOW DESIGN FLOOD ELEVATION)
  
 3. CONDENSER SHALL BE INSTALLED AT OR ABOVE THE DESIGN
 FLOOD ELEVATION (DFE).
 FBC R M1401.5 AND FBC R 322.1.6
 M1401.5 FLOOD HAZARD.
 IN FLOOD HAZARD AREAS AS ESTABLISHED BY TABLE
 R301.2(1), HEATING AND COOLING EQUIPMENT AND APPLIANCES
 SHALL BE LOCATED OR INSTALLED IN ACCORDANCE WITH
 SECTION R322.1.6.
 R322.1.6 PROTECTION OF MECHANICAL, PLUMBING AND
 ELECTRICAL SYSTEMS.
  
 4. PROVIDE MANUFACTURERS SPECIFICATIONS FOR EXHAUST
 HOOD. PROVIDE EXHAUST RATE IN CUBIC FEET PER MINUTE.
 (NOT ADDRESSED)
 G2408.1 (305.1)GENERAL. FBC SEC. 107.2.1.
 EQUIPMENT AND APPLIANCES SHALL BE INSTALLED AS REQUIRED
 BY THE TERMS OF THEIR APPROVAL, IN ACCORDANCE WITH THE
 CONDITIONS OF LISTING, THE MANUFACTURER?S INSTRUCTIONS
 AND THIS CODE.
  
 5. PROVIDE MAKE UP AIR CALCULATIONS. (NOT ADDRESSED)
 M1503.4 MAKEUP AIR REQUIRED.
 EXHAUST HOOD SYSTEMS CAPABLE OF EXHAUSTING IN EXCESS OF
 400 CUBIC FEET PER MINUTE (0.19 M3/S) SHALL BE
 MECHANICALLY OR NATURALLY PROVIDED WITH MAKEUP AIR AT A
 RATE APPROXIMATELY EQUAL TO THE EXHAUST AIR RATE. SUCH
 MAKEUP AIR SYSTEMS SHALL BE EQUIPPED WITH NOT LESS THAN
 ONE DAMPER. EACH DAMPER SHALL BE A GRAVITY DAMPER OR AN
 ELECTRICALLY OPERATED DAMPER THAT AUTOMATICALLY OPENS
 WHEN THE EXHAUST SYSTEM OPERATES. DAMPERS SHALL BE
 ACCESSIBLE FOR INSPECTION, SERVICE, REPAIR AND
 REPLACEMENT WITHOUT REMOVING PERMANENT CONSTRUCTION OR
 ANY OTHER DUCTS NOT CONNECTED TO THE DAMPER BEING
 INSPECTED, SERVICED, REPAIRED OR REPLACED.
 EXCEPTION: IN A SINGLE-FAMILY DWELLING, MAKE-UP AIR IS
 NOT REQUIRED FOR RANGE HOOD EXHAUST SYSTEMS CAPABLE OF
 EXHAUSTING:
 1. (A)FOUR HUNDRED CUBIC FEET PER MINUTE OR LESS; OR
 2. (B)MORE THAN 400 CUBIC FEET PER MINUTE BUT NO MORE
 THAN 800 CUBIC FEET PER MINUTE IF THERE ARE NO GRAVITY
 VENT APPLIANCES WITHIN THE CONDITIONED LIVING SPACE OF
 THE STRUCTURE.
  
 6. NOTE ON PLAN PAGE M-1 REFERENCES DETAIL D/S-4 FOR
 SECTION VIEW OF MSU#1 & FCU#1. THERE IS NO DETAIL ON
 PAGE S-4. PLEASE CLARIFY. CORRECTED
  
 7. PROVIDE MANUFACTURERS INSTALLATION INSTRUCTIONS FOR
 FIREPLACE. (NOT ADDRESSED)
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 8. PROVIDE PRODUCT APPROVAL OR ENGINEERED DESIGN FOR CU
 TIE DOWN. (NOT ADDRESSED)
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 9. PROVIDE CFM RATING FOR BATHROOM EXHAUST FANS.
 CORRECTED
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 NEW COMMENTS:
  
 10. PROVIDE SHOP DRAWINGS FOR KITCHEN EXHAUST HOOD.
  
 11. PROVIDE MAKE UP AIR CALCULATIONS FOR KITCHEN
 EXHAUST HOOD.
  
 12. NOTE ON PLAN PAGE M-1 STATES OWNER MAY SUBSTITUTE
 EQUIPMENT. ANY CHANGES FROM APPORVED PLANS WILL REQUIRE
 A REVISION.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-06-06 Cont ID  
Sent By cthroop Date 2019-06-06 Time 09:51 Rev Time 0.00
Received By cthroop Date 2019-05-30 Time 13:46 Sent To  
Notes
2019-06-06 10:11:41ADDRESS: 110 FLAGLER LANE PERMIT # 19050386
 TYPE: BLD-RES NEW SFR
  
 MECHANICAL PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC M = FLORIDA BUILDING CODE MECHANICAL 2017 6TH
 EDITION
 FBC P = FLORIDA BUILDING CODE PLUMBING 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 1. PROVIDE AN ACCURATELEY COMPLETED ENERGY SUBMITTAL.
 FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405
 (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE
 SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE
 COMPLIANCE BY SECTION 405.
  
 R401.3 ENERGY PERFORMANCE LEVEL (EPL) DISPLAY CARD
 (MANDATORY). SIGNED BY BUILDER.
  
 2. EXTERIOR MECHANICAL EQUIPMENT SHALL BE INSTALLED AT
 OR ABOVE THE DESIGN FLOOD ELEVATION. (DFE)
 CONDENSER SHALL BE INSTALLED AT OR ABOVE THE DESIGN
 FLOOD ELEVATION (DFE).
 FBC R M1401.5 AND FBC R 322.1.6
 M1401.5 FLOOD HAZARD.
 IN FLOOD HAZARD AREAS AS ESTABLISHED BY TABLE
 R301.2(1), HEATING AND COOLING EQUIPMENT AND APPLIANCES
 SHALL BE LOCATED OR INSTALLED IN ACCORDANCE WITH
 SECTION R322.1.6.
 R322.1.6 PROTECTION OF MECHANICAL, PLUMBING AND
 ELECTRICAL SYSTEMS.
  
 4. PROVIDE MANUFACTURERS SPECIFICATIONS FOR EXHAUST
 HOOD. PROVIDE EXHAUST RATE IN CUBIC FEET PER MINUTE.
 G2408.1 (305.1)GENERAL. FBC SEC. 107.2.1.
 EQUIPMENT AND APPLIANCES SHALL BE INSTALLED AS REQUIRED
 BY THE TERMS OF THEIR APPROVAL, IN ACCORDANCE WITH THE
 CONDITIONS OF LISTING, THE MANUFACTURER?S INSTRUCTIONS
 AND THIS CODE.
  
 5. PROVIDE MAKE UP AIR CALCULATIONS.
 M1503.4 MAKEUP AIR REQUIRED.
 EXHAUST HOOD SYSTEMS CAPABLE OF EXHAUSTING IN EXCESS OF
 400 CUBIC FEET PER MINUTE (0.19 M3/S) SHALL BE
 MECHANICALLY OR NATURALLY PROVIDED WITH MAKEUP AIR AT A
 RATE APPROXIMATELY EQUAL TO THE EXHAUST AIR RATE. SUCH
 MAKEUP AIR SYSTEMS SHALL BE EQUIPPED WITH NOT LESS THAN
 ONE DAMPER. EACH DAMPER SHALL BE A GRAVITY DAMPER OR AN
 ELECTRICALLY OPERATED DAMPER THAT AUTOMATICALLY OPENS
 WHEN THE EXHAUST SYSTEM OPERATES. DAMPERS SHALL BE
 ACCESSIBLE FOR INSPECTION, SERVICE, REPAIR AND
 REPLACEMENT WITHOUT REMOVING PERMANENT CONSTRUCTION OR
 ANY OTHER DUCTS NOT CONNECTED TO THE DAMPER BEING
 INSPECTED, SERVICED, REPAIRED OR REPLACED.
 EXCEPTION: IN A SINGLE-FAMILY DWELLING, MAKE-UP AIR IS
 NOT REQUIRED FOR RANGE HOOD EXHAUST SYSTEMS CAPABLE OF
 EXHAUSTING:
 1. (A)FOUR HUNDRED CUBIC FEET PER MINUTE OR LESS; OR
 2. (B)MORE THAN 400 CUBIC FEET PER MINUTE BUT NO MORE
 THAN 800 CUBIC FEET PER MINUTE IF THERE ARE NO GRAVITY
 VENT APPLIANCES WITHIN THE CONDITIONED LIVING SPACE OF
 THE STRUCTURE.
  
 6. NOTE ON PLAN PAGE M-1 REFERENCES DETAIL D/S-4 FOR
 SECTION VIEW OF MSU#1 & FCU#1. THERE IS NO DETAIL ON
 PAGE S-4. PLEASE CLARIFY.
  
 7. PROVIDE MANUFACTURERS INSTALLATION INSTRUCTIONS FOR
 FIREPLACE.
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 8. PROVIDE PRODUCT APPROVAL OR ENGINEERED DESIGN FOR CU
 TIE DOWN.
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 9. PROVIDE CFM RATING FOR BATHROOM EXHAUST FANS.
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  
  
  

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 6 Status P Date 2019-10-19 Cont ID  
Sent By cthroop Date 2019-10-19 Time 12:40 Rev Time 0.00
Received By cthroop Date 2019-10-15 Time 16:08 Sent To  
Notes
2020-09-21 11:07:52STRUCTURE IS LOCATED IN A SPECIAL FLOOD HAZARD AREA
 (SFHA) AE WITH A BASE FLOOD ELEVATION OF 7.0 FEET NAVD.
 CONSTRUCTION DRAWING EC WITH DESIGN FLOOD ELEVATION OF
 9.4 FEET NAVD REVIEWED AND APPROVED. CT

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 5 Status F Date 2019-10-04 Cont ID  
Sent By cthroop Date 2019-10-04 Time 16:29 Rev Time 0.00
Received By cthroop Date 2019-10-04 Time 12:47 Sent To  
Notes
2019-10-04 16:37:35NFIP PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 5TH REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
  
  
 1. PROPOSED STRUCTURE IS LOCATED IN A SPECIAL FLOOD
 HAZARD AREA WITH A DESIGNATION OF AE WITH A BASE FLOOD
 ELEVATION (BFE) OF 7.0 FEET NAVD.
 THE CITY OF WEST PALM BEACH REQUIRES A FREEBOARD OF 2.0
 FEET. IF VERTICAL DATUM IS TAKEN FROM A FIRM THEN 0.4
 FEET SHALL BE ADDED AS A ROUNDING FACTOR. ALTHOUGH THIS
 INFORMATION IS GENERALLY CORRECT, FURTHER RESEARCH IS
 REQUIRED TO DETERMINE THE BASE FLOOD ELEVATION OF A
 PARTICULAR PARCEL. MORE ACCURATE INFORMATION COMES FROM
 THE FLOOD INSURANCE STUDY AND CAN PROVIDE MORE PRECISE
 DATUM. PLEASE USE THE FOLLOWING LINK TO ACCESS MY
 GEONAV TO OBTAIN MORE ACCURATE ELEVATION DATUM.
 HTTP://MAPS.CO.PALM-BEACH.FL.US/CWGIS/MYGEONAV.HTML?
 BASED ON SECTION B10, THE SOURCE OF THE BFE DATA IS A
 FIRM. DESIGN FLOOD ELEVATION (DFE) SHALL BE AT OR ABOVE
 9.4 FEET NAVD. (NO ACTION REQUIRED)
  
 2. (CORRECTED)
  
 3. AS SHOWN ON THE PROPOSED PLANS THIS STRUCTURE HAS AN
 ATTACHED GARAGE. COMPLETE SECTION A9. (SPECIFICALLY,
 CORRECT SECTIONS A9 (B), A9 (C) & A9 (D)).
  
 4. (CORRECTED)
  
 5. (CORRECTED)
  
 6. (CORRECTED)
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 4 Status F Date 2019-09-14 Cont ID  
Sent By cthroop Date 2019-09-14 Time 12:47 Rev Time 0.00
Received By cthroop Date 2019-09-14 Time 08:07 Sent To  
Notes
2019-09-14 13:08:53NFIP PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 4TH REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
  
  
 1. PROPOSED STRUCTURE IS LOCATED IN A SPECIAL FLOOD
 HAZARD AREA WITH A DESIGNATION OF AE WITH A BASE FLOOD
 ELEVATION (BFE) OF 7.0 FEET NAVD.
 THE CITY OF WEST PALM BEACH REQUIRES A FREEBOARD OF 2.0
 FEET. IF VERTICAL DATUM IS TAKEN FROM A FIRM THEN 0.4
 FEET SHALL BE ADDED AS A ROUNDING FACTOR. ALTHOUGH THIS
 INFORMATION IS GENERALLY CORRECT, FURTHER RESEARCH IS
 REQUIRED TO DETERMINE THE BASE FLOOD ELEVATION OF A
 PARTICULAR PARCEL. MORE ACCURATE INFORMATION COMES FROM
 THE FLOOD INSURANCE STUDY AND CAN PROVIDE MORE PRECISE
 DATUM. PLEASE USE THE FOLLOWING LINK TO ACCESS MY
 GEONAV TO OBTAIN MORE ACCURATE ELEVATION DATUM.
 HTTP://MAPS.CO.PALM-BEACH.FL.US/CWGIS/MYGEONAV.HTML?
 DESIGN FLOOD ELEVATION (DFE) SHALL BE AT OR ABOVE 9.4
 FEET NAVD.
  
 2. (CORRECTED)
  
 3. AS SHOWN ON THE PROPOSED PLANS THIS STRUCTURE HAS AN
 ATTACHED GARAGE. COMPLETE SECTION A9. INCLUDE PROPOSED
 FLOOD OPENINGS.
  
 4.PER SECTION C2 ELEVATION OF MACHINERY SHALL BE AT OR
 ABOVE THE DESIGN FLOOD ELEVATION OF 9.4 FEET NAVD.
 (DESCRIBE TYPE OF EQUIPMENT IN COMMENTS SECTION)
  
 5. SURVEYORS SIGNATURE AND SEAL REQUIRED ON ELEVATION
 CERTIFICATE. YOU MAY PROVIDE A PAPER COPY WITH WET SEAL
 AND SIGNATURE AT TIME OF PERMIT.
  
 6. PER SECTION A6 PHOTOGRAPHS ARE NOT REQUIRED UNTIL
 FINAL ELEVATION CERTIFICATE. THEY ARE REQUIRED TO SHOW
 THE BUILDING FOUNDATION, FLOOD VENTS AND ELEVATED
 MECHANICAL EQUIPMENT.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 3 Status F Date 2019-09-07 Cont ID  
Sent By cthroop Date 2019-09-07 Time 08:50 Rev Time 0.00
Received By cthroop Date 2019-09-05 Time 09:23 Sent To  
Notes
2019-09-07 08:53:00NFIP PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 3RD REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 ELEVATION CERTIFICATE UNSUCESSFULLY UPLOADED, NO
 INFORMATION AVAILABLE
  
 1. PROPOSED STRUCTURE IS LOCATED IN A SPECIAL FLOOD
 HAZARD AREA WITH A DESIGNATION OF AE WITH A BASE FLOOD
 ELEVATION (BFE) OF 7.0 FEET NAVD.
 THE CITY OF WEST PALM BEACH REQUIRES A FREEBOARD OF 2.0
 FEET. DESIGN FLOOD ELEVATION (DFE) SHALL BE AT OR ABOVE
 9.0 FEET NAVD.
  
 2. SECTION B9 OF THE SUBMITTED ELEVATION CERTIFICATE
 STATES THE BFE AS 5.0 FEET NAVD. PLEASE CORRECT. TO 7.0
 FEET NAVD.
  
 3. AS STATED IN SECTION C2, THIS STRUCTURE HAS AN
 ATTACHED GARAGE. COMPLETE SECTION A9. INCLUDE PROPOSED
 FLOOD OPENINGS.
 SECTION C2(A) SHOWS TOP OF BOTTOM FLOOR AS 9.0 FEET.
 SITE PLAN, DRAINAGE PLAN AND FIRST FLOOR PLAN SHOW TOP
 OF FLOOR AS 9.4 FEET. PLEASE CLARIFY.
  
 4. ELEVATION OF MACHINERY SHALL BE AT OR ABOVE THE
 DESIGN FLOOD ELEVATION OF 9.0 NAVD. CORRECT SECTION C2
 (E).
  
 5. SURVEYORS SIGNATURE AND SEAL ON ELEVATION
 CERTIFICATE ARE NOT DIGITAL. YOU MAY PROVIDE A PAPER
 COPY WITH WET SEAL AND SIGNATURE.
  
 6. THE SURVEY SUBMITTED BY BOB BUGGEE, INC. STATES THE
 FLOOD ZONE AS AE WITH AN ELEVATION OF 6.0 FEET. THIS
 INFORMATION IS TAKEN FROM THE FLOOD INSURANCE RATE MAP
 # 12099C0581F DATED 10/5/2017. ALTHOUGH THIS
 INFORMATION IS GENERALLY CORRECT, FURTHER RESEARCH IS
 REQUIRED TO DETERMINE THE BASE FLOOD ELEVATION OF A
 PARTICULAR PARCEL. MORE ACCURATE INFORMATION COMES FROM
 THE FLOOD INSURANCE STUDY AND CAN PROVIDE MORE PRECISE
 DATUM. PLEASE USE THE FOLLOWING LINK TO ACCESS MY
 GEONAV TO OBTAIN MORE ACCURATE ELEVATION DATUM.
 HTTP://MAPS.CO.PALM-BEACH.FL.US/CWGIS/MYGEONAV.HTML?
 FEEL FREE TO CONTACT ME FOR ASSITANCE IN USING THIS
 SITE.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 2 Status F Date 2019-08-05 Cont ID  
Sent By cthroop Date 2019-08-05 Time 11:07 Rev Time 0.00
Received By cthroop Date 2019-08-02 Time 16:10 Sent To  
Notes
2019-08-05 11:22:50NFIP PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 2ND REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROPOSED STRUCTURE IS LOCATED IN A SPECIAL FLOOD
 HAZARD AREA WITH A DESIGNATION OF AE WITH A BASE FLOOD
 ELEVATION (BFE) OF 7.0 FEET NAVD.
 THE CITY OF WEST PALM BEACH REQUIRES A FREEBOARD OF 2.0
 FEET. DESIGN FLOOD ELEVATION (DFE) SHALL BE AT OR ABOVE
 9.0 FEET NAVD.
  
 2. SECTION B9 OF THE SUBMITTED ELEVATION CERTIFICATE
 STATES THE BFE AS 5.0 FEET NAVD. PLEASE CORRECT. TO 7.0
 FEET NAVD.
  
 3. AS STATED IN SECTION C2, THIS STRUCTURE HAS AN
 ATTACHED GARAGE. COMPLETE SECTION A9. INCLUDE PROPOSED
 FLOOD OPENINGS.
 SECTION C2(A) SHOWS TOP OF BOTTOM FLOOR AS 9.0 FEET.
 SITE PLAN, DRAINAGE PLAN AND FIRST FLOOR PLAN SHOW TOP
 OF FLOOR AS 9.4 FEET. PLEASE CLARIFY.
  
 4. ELEVATION OF MACHINERY SHALL BE AT OR ABOVE THE
 DESIGN FLOOD ELEVATION OF 9.0 NAVD. CORRECT SECTION C2
 (E).
  
 5. SURVEYORS SIGNATURE AND SEAL ON ELEVATION
 CERTIFICATE ARE NOT DIGITAL. YOU MAY PROVIDE A PAPER
 COPY WITH WET SEAL AND SIGNATURE.
  
 6. THE SURVEY SUBMITTED BY BOB BUGGEE, INC. STATES THE
 FLOOD ZONE AS AE WITH AN ELEVATION OF 6.0 FEET. THIS
 INFORMATION IS TAKEN FROM THE FLOOD INSURANCE RATE MAP
 # 12099C0581F DATED 10/5/2017. ALTHOUGH THIS
 INFORMATION IS GENERALLY CORRECT, FURTHER RESEARCH IS
 REQUIRED TO DETERMINE THE BASE FLOOD ELEVATION OF A
 PARTICULAR PARCEL. MORE ACCURATE INFORMATION COMES FROM
 THE FLOOD INSURANCE STUDY AND CAN PROVIDE MORE PRECISE
 DATUM. PLEASE USE THE FOLLOWING LINK TO ACCESS MY
 GEONAV TO OBTAIN MORE ACCURATE ELEVATION DATUM.
 HTTP://MAPS.CO.PALM-BEACH.FL.US/CWGIS/MYGEONAV.HTML?
 FEEL FREE TO CONTACT ME FOR ASSITANCE IN USING THIS
 SITE.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 1 Status F Date 2019-06-05 Cont ID  
Sent By cthroop Date 2019-06-05 Time 08:22 Rev Time 0.00
Received By cthroop Date 2019-05-30 Time 13:46 Sent To  
Notes
2019-06-05 08:35:42ADDRESS: 110 FLAGLER LANE PERMIT # 19050386
 TYPE: BLD-RES NEW SFR
  
 BUILDING PLAN REVIEW - NFIP
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC M = FLORIDA BUILDING CODE MECHANICAL 2017 6TH
 EDITION
 FBC P = FLORIDA BUILDING CODE PLUMBING 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 NFIP REVIEW
 CITY OF WEST PALM BEACH ORDINANCE NO. 4658-16
 AS OF OCTOBER 5, 2017, THE FEDERAL EMERGENCY MANAGEMENT
 AGENCY (FEMA) ESTABLISHED A NEW FLOOD INSURANCE RATE
 MAP (FIRM) UTILIZING THE RECENTLY COMPLETED FLOOD
 HAZARD DETERMINATION (FHD) FOR THE CITY OF WEST PALM
 BEACH, FL.
 ALL NEW BASE FLOOD ELEVATIONS (BFE) SHALL BE BASED ON
 NAVD88 DATUM. ON AUGUST 23, 2017, THE CITY OF WEST PALM
 BEACH, BY ORDINANCE, NO. 4658-16, ESTABLISHED A TWO
 FOOT FREEBOARD ABOVE THE (BFE).
  
 1. THIS STRUCTURE IS LOCATED IN A SPECIAL FLOOD HAZARD
 AREA. DESIGNATED FLOOD ZONE IS AE WITH A BASE FLOOD
 ELEVATION OF 7.0 FEET NAVD88. THE FOLLOWING CONDITIONS
 SHALL APPLY.
  
 NFIP
  
 1. BASED ON THE SUBMITTED SURVEY, THIS LOT AND PROPOSED
 IMPROVEMENTS ARE LOCATED IN AN AE FLOOD ZONE WITH A
 BASE FLOOD ELEVATION (BFE) OF 7.0 FEET NAVD.
 2. AS OF OCTOBER 5, 2017, THE FEDERAL EMERGENCY
 MANAGEMENT AGENCY (FEMA) ESTABLISHED A NEW FLOOD
 INSURANCE RATE MAP (FIRM) UTILIZING THE RECENTLY
 COMPLETED FLOOD HAZARD DETERMINATION (FHD) FOR THE CITY
 OF WEST PALM BEACH, FL.
 3. ALL NEW BASE FLOOD ELEVATIONS (BFE) SHALL BE BASED
 ON NAVD88 DATUM. ON AUGUST 23, 2017, THE CITY OF WEST
 PALM BEACH, BY ORDINANCE, ESTABLISHED A TWO FOOT
 FREEBOARD ABOVE THE (BFE).
 4. YOU MAY SUBMIT A SURVEY SHOWING ALL EXISTING AND
 PROPOSED ELEVATIONS BASED ON NAVD88 DATUM PLUS TWO FEET
 OF FREEBOARD OR THE ENGINEER OF RECORD (EOR) MAY ADD A
 STATEMENT TO THE STRUCTURAL PLAN THAT THE DESIGN FLOOD
 ELEVATION (DFE) WILL BE 9.4 FEET NAVD88 BASED ON THE
 (BFE) OF 7.00 FEET FOR FLOOD ZONE AE PLUS A CORRECTION
 FACTOR OF .4 FEET PLUS TWO FEET OF FREEBOARD.
  
 2. ELEVATION CERTIFACES ARE REQUIRED AS FOLLOWS:
  
 A CONSTRUCTION DRAWING ELEVATION CERTIFICATE IS
 REQUIRED AT TIME OF PERMIT APPLICATION.
 NOTE: ALL EQUIPMENT SERVICING THE BUILDINGS ON THIS
 SITE ARE REQUIRED TO BE AT OR ABOVE 9 FEET 4 INCHES
 NAVD.
  
 AN UNDER CONSTRUCTION (FORMBOARD) SURVEY WITH FINISHED
 FLOOR ELEVATION IS REQUIRED.
  
 A FINISHED CONSTRUCTION ELEVATION CERTIFICATE IS
 REQUIRED AND SHALL BE SUBMITTED FOR REVIEW AND APPROVAL
 PRIOR TO THE ISSUANCE OF THE CERTIFICATE OF OCCUPANCY.
 THIS EC MAY BE SUBMITTED FOR REVIEW PRIOR TO BUILDING
 FINAL.
  
  

Review Stop P PLUMBING
Rev No 5 Status P Date 2019-10-04 Cont ID  
Sent By cthroop Date 2019-10-04 Time 13:39 Rev Time 0.00
Received By cthroop Date 2019-10-03 Time 16:58 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status F Date 2019-09-14 Cont ID  
Sent By cthroop Date 2019-09-14 Time 12:07 Rev Time 0.00
Received By cthroop Date 2019-09-14 Time 08:07 Sent To  
Notes
2019-09-14 12:08:35ADDRESS: 110 FLAGLER LANE PERMIT # 19050386
 TYPE: BLD-RES NEW SFR
  
 PLUMBING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 4TH REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 SIGNATURE AND SEAL ON PLAN IS INVALID.
  
 1. DIGITAL SIGNATURES/SEALS ARE NOT IN ACCORDANCE WITH
 FS 471, FS 481 AS NOTED. NEW SHEETS SUBMITTED IN THE
 NEXT REVIEW CYCLE REQUIRE REVIEW.
  
 2. UPLOAD VIA THE PROJECTDOX PORTAL WITH DIGITAL
 SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE
 THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT.
  
  
  

Review Stop P PLUMBING
Rev No 3 Status F Date 2019-09-07 Cont ID  
Sent By cthroop Date 2019-09-07 Time 08:53 Rev Time 0.00
Received By cthroop Date 2019-09-05 Time 09:22 Sent To  
Notes
2019-09-07 08:55:59ADDRESS: 110 FLAGLER LANE PERMIT # 19050386
 TYPE: BLD-RES NEW SFR
  
 BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 3RD REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 SIGNATURE AND SEAL ON PLAN IS INVALID.
  
 1. DIGITAL SIGNATURES/SEALS ARE NOT IN ACCORDANCE WITH
 FS 471, FS 481 AS NOTED. NEW SHEETS SUBMITTED IN THE
 NEXT REVIEW CYCLE REQUIRE REVIEW.
  
 2. UPLOAD VIA THE PROJECTDOX PORTAL WITH DIGITAL
 SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE
 THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT.
  
  
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-08-05 Cont ID  
Sent By cthroop Date 2019-08-05 Time 15:47 Rev Time 0.00
Received By cthroop Date 2019-08-02 Time 16:10 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2019-05-22 Cont ID  
Sent By gjohnson Date 2019-05-22 Time 15:24 Rev Time 0.00
Received By gjohnson Date 2019-05-22 Time 12:38 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 5 Status P Date 2019-10-04 Cont ID  
Sent By cthroop Date 2019-10-04 Time 14:44 Rev Time 0.00
Received By cthroop Date 2019-10-04 Time 13:29 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 4 Status F Date 2019-09-14 Cont ID  
Sent By cthroop Date 2019-09-14 Time 11:37 Rev Time 0.00
Received By cthroop Date 2019-09-14 Time 08:07 Sent To  
Notes
2019-09-14 11:40:45ADDRESS: 110 FLAGLER LANE PERMIT # 19050386
 TYPE: BLD-RES NEW SFR
  
 BUILDING PLAN REVIEW - ROOFING
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 4TH REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 COMMENTS FROM 1ST REVIEW HAVE BEEN ADDRESSED
  
 1. ROOFING SUB-PERMIT REQUIRED. (CORRECTED)
  
 2. PROVIDE PRODUCT APPROVALS FOR NEW ROOFING SYSTEM
 COMPONENTS. (CORRECTED)
  
 NEW ITEM
  
 3. PRODUCT APPROVALS SHALL BE REVIEWD AND APPROVED BY
 DESIGNER
 FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE ROOFING SUBMITTALS.
  
  

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status F Date 2019-09-07 Cont ID  
Sent By cthroop Date 2019-09-07 Time 08:56 Rev Time 0.00
Received By cthroop Date 2019-09-05 Time 09:22 Sent To  
Notes
2019-09-07 08:58:00ADDRESS: 110 FLAGLER LANE PERMIT # 19050386
 TYPE: BLD-RES NEW SFR
  
 BUILDING PLAN REVIEW - ROOFING
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 3RD REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 COMMENTS FROM 1ST REVIEW HAVE NOT BEEN ADDRESSED
  
 1. ROOFING SUB-PERMIT REQUIRED. (SUB PERMIT
 UNSUCESSFULLY UPLOADED)
  
 2. PROVIDE PRODUCT APPROVALS FOR NEW ROOFING SYSTEM
 COMPONENTS. (PRODUCT APPROVALS UNSUCESSFULLY UPLOADED)
 FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE ROOFING SUBMITTALS.
  
  
  
  

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2019-08-05 Cont ID  
Sent By cthroop Date 2019-08-05 Time 15:58 Rev Time 0.00
Received By cthroop Date 2019-08-02 Time 16:10 Sent To  
Notes
2019-08-05 16:00:22ADDRESS: 110 FLAGLER LANE PERMIT # 19050386
 TYPE: BLD-RES NEW SFR
  
 BUILDING PLAN REVIEW - ROOFING
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 2ND REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 COMMENTS FROM 1ST REVIEW HAVE NOT BEEN ADDRESSED
  
 1. ROOFING SUB-PERMIT REQUIRED.
  
 2. PROVIDE PRODUCT APPROVALS FOR NEW ROOFING SYSTEM
 COMPONENTS.
 FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE ROOFING SUBMITTALS.
  
  
  
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2019-06-05 Cont ID  
Sent By cthroop Date 2019-06-05 Time 08:37 Rev Time 0.00
Received By cthroop Date 2019-05-30 Time 13:46 Sent To  
Notes
2019-06-05 09:18:22ADDRESS: 110 FLAGLER LANE PERMIT # 19050386
 TYPE: BLD-RES NEW SFR
  
 BUILDING PLAN REVIEW - ROOFING
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC M = FLORIDA BUILDING CODE MECHANICAL 2017 6TH
 EDITION
 FBC P = FLORIDA BUILDING CODE PLUMBING 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 1. ROOFING SUB-PERMIT REQUIRED.
  
 2. PROVIDE PRODUCT APPROVALS FOR NEW ROOFING SYSTEM
 COMPONENTS.
 FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE ROOFING SUBMITTALS.
  
  
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 6 Status P Date 2019-10-19 Cont ID  
Sent By cthroop Date 2019-10-19 Time 12:49 Rev Time 0.00
Received By cthroop Date 2019-10-15 Time 16:08 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status P Date 2019-10-04 Cont ID  
Sent By cthroop Date 2019-10-04 Time 16:40 Rev Time 0.00
Received By cthroop Date 2019-10-04 Time 12:47 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status F Date 2019-09-14 Cont ID  
Sent By cthroop Date 2019-09-14 Time 12:03 Rev Time 0.00
Received By cthroop Date 2019-09-14 Time 08:07 Sent To  
Notes
2019-09-14 12:03:50BUILDING PLAN REVIEW - DIGITAL SIGNATURE REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 4TH REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 DIGITAL REVIEW
  
 1. DIGITAL SIGNATURES/SEALS ARE NOT IN ACCORDANCE WITH
 FS 471, FS 481 AS NOTED. NEW SHEETS SUBMITTED IN THE
 NEXT REVIEW CYCLE REQUIRE REVIEW.
  
 2. UPLOAD VIA THE PROJECTDOX PORTAL WITH DIGITAL
 SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE
 THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT.
  
 3. FLORIDA PROFESSIONAL ENGINEERS MAY NOT SELF CERTIFY
 DIGITAL SIGATURES AND SEALS PER FS 668.003.
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2019-09-07 Cont ID  
Sent By cthroop Date 2019-09-07 Time 08:58 Rev Time 0.00
Received By cthroop Date 2019-09-05 Time 09:23 Sent To  
Notes
2019-09-07 09:00:02BUILDING PLAN REVIEW - DIGITAL SIGNATURE REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 3RD REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 (MULTIPLE PLAN PAGES UNSUCESSFULLY UPLOADED)
  
 DIGITAL REVIEW
  
 1. DIGITAL SIGNATURES/SEALS ARE NOT IN ACCORDANCE WITH
 FS 471, FS 481 AS NOTED. NEW SHEETS SUBMITTED IN THE
 NEXT REVIEW CYCLE REQUIRE REVIEW.
  
 2. UPLOAD VIA THE PROJECTDOX PORTAL WITH DIGITAL
 SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE
 THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT.
  
 3. FLORIDA PROFESSIONAL ENGINEERS MAY NOT SELF CERTIFY
 DIGITAL SIGATURES AND SEALS PER FS 668.003.
  
  
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2019-08-05 Cont ID  
Sent By cthroop Date 2019-08-05 Time 09:43 Rev Time 0.00
Received By cthroop Date 2019-08-02 Time 16:10 Sent To  
Notes
2019-08-05 09:45:17BUILDING PLAN REVIEW - DIGITAL SIGNATURE REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 DIGITAL REVIEW
  
 1. DIGITAL SIGNATURES/SEALS ARE NOT IN ACCORDANCE WITH
 FS 471, FS 481 AS NOTED. NEW SHEETS SUBMITTED IN THE
 NEXT REVIEW CYCLE REQUIRE REVIEW.
  
 2. UPLOAD VIA THE PROJECTDOX PORTAL WITH DIGITAL
 SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE
 THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT.
  
 3. FLORIDA PROFESSIONAL ENGINEERS MAY NOT SELF CERTIFY
 DIGITAL SIGATURES AND SEALS PER FS 668.003.
  
  
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2019-06-04 Cont ID  
Sent By cthroop Date 2019-06-04 Time 16:51 Rev Time 0.00
Received By cthroop Date 2019-05-30 Time 13:46 Sent To  
Notes
2019-06-04 16:55:07ADDRESS: 110 FLAGLER LANE TYPE: BLD-RES NEW SFR
  
 BUILDING PLAN REVIEW - DIGITAL SIGNATURES
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 DIGITAL SIGNATURES ARE INVALID.
  
 1. DIGITAL SIGNATURES/SEALS ARE NOT IN ACCORDANCE WITH
 FS 471, FS 481 AS NOTED. NEW SHEETS SUBMITTED IN THE
 NEXT REVIEW CYCLE REQUIRE REVIEW.
  
 2. UPLOAD VIA THE PROJECTDOX PORTAL WITH DIGITAL
 SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE
 THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT.
  
 THE SUBMITTED DOCUMENT IS SIGNED AND SEALED AS A PAPER
 DOCUMENT, THERE IS NO ELECTRONIC SIGNATURE TO THIS
 DOCUMENT. THE DESIGN PROFESSIO0NALS HAVE 2 OPTIONS,
 EITHER COMPLY WITH FLORIDA ADMINISTRATIVE CODE
 61G15-23.005 PROCEDURES FOR SIGNING AND SEALING
 ELECTRONICALLY TRANSMITTED PLANS, SPECIFICATIONS,
 REPORTS OR OTHER DOCUMENTS OR SUBMIT 2 ORIGINAL PAPER
 DOCUMENT SIGNED AND SEALED.
  
  
  
  
  

Review Stop Z ZONING
Rev No 5 Status P Date 2019-10-04 Cont ID  
Sent By llouie Date 2019-10-04 Time   Rev Time 0.00
Received By llouie Date 2019-10-04 Time   Sent To  
Notes
2019-10-04 11:52:05SEPARATE PERMITS AND REVIEWS REQUIRED FOR: LANDSCAPING,
 HARDSCAPES (I.E. DRIVEWAY AND WALKWAYS, ETC.),
 GENERATOR AND PRIVACY WALL.

Review Stop Z ZONING
Rev No 4 Status P Date 2019-09-16 Cont ID  
Sent By llouie Date 2019-09-16 Time   Rev Time 0.00
Received By llouie Date 2019-09-16 Time   Sent To  
Notes
2019-09-16 10:10:07SEPARATE PERMITS AND REVIEWS REQUIRED FOR: LANDSCAPING,
 HARDSCAPES (I.E. DRIVEWAY AND WALKWAYS, ETC.),
 GENERATOR AND PRIVACY WALL.

Review Stop Z ZONING
Rev No 3 Status F Date 2019-08-23 Cont ID  
Sent By llouie Date 2019-08-23 Time   Rev Time 0.00
Received By llouie Date 2019-08-23 Time   Sent To  
Notes
2019-08-23 13:47:00** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) LOT DIMENSIONS PROVIDED IN THE SITE PLAN DOES NOT
 MATCH THE DIMENSIONS PROVIDED IN THE SURVEY. THE
 DIMENSIONS SHOULD MATCH. PLEASE ADDRESS FOR
 CONSISTENCY.
  
 2.) STEPS AT THE NORTH END OF THE PROPERTY CANNOT BE
 LOCATED BEYOND THE PROPERTY LINE WITHOUT THE APPROVAL
 OF THE ENGINEERING SERVICES DEPARTMENT AS IT IS LOCATED
 WITHIN THE RIGHT-OF-WAY.
  
 3.) WHAT IS THE HEIGHT OF THE PROPOSED PERIMETER WALL?
 THE HEIGHT SHALL BE NOTATED IN THE SITE PLAN. PLEASE
 NOTE THAT THE HEIGHT OF THE WALL CANNOT EXCEED 4 FT. IN
 HEIGHT WITHIN THE FIRST 25 FT. OF FLAGLER DRIVE AND 6
 FT. IN HEIGHT ALONG THE SIDE AND REAR PROPERTY LINES.
 [ZLDR S.94-302(B)] [7/30/19 REPEAT COMMENT].
  
 4.) THE PROPOSED WALL SHALL NOT IMPEDE UPON SIGHT
 VISIBILITY AT THE INTERSECTION OF FLAGLER DRIVE AND
 FLAGLER LANE. PLEASE DEMONSTRATE COMPLIANCE BY
 ILLUSTRATING THAT THE PROPOSED WALL DOES NOT ENCROACH
 WITHIN A 20 FT. SIGHT VISIBILITY TRIANGLE. [ZLDR
 S.94-305(E)]
  
 5.) SHOW CALCULATIONS TO DEMONSTRATE THAT THERE IS AT
 LEAST 1,000 SQ. FT. (OR 75%) OF LANDSCAPED AREA WITHIN
 THE REQUIRED FRONT YARD (AREA WITHIN THE FIRST 25 FT.
 OF NORTH FLAGLER DRIVE). [ZLDR S.94-482(A)]
  
 6.) DIMENSIONS FOR THE PROPOSED DRIVEWAY ARE MISSING
 FROM THE SITE PLAN. THE PROPOSED DRIVEWAY SHALL BE
 SETBACK AT LEAST 3 FT. FROM THE PROPERTY LINE AND
 CANNOT EXCEED 20 FT. IN WIDTH AT THE PROPERTY LINE.
 [ZLDR S.94-312(1) AND ZLDR S.94-482(D)] [7/30/19 REPEAT
 COMMENT]
  
 7.) SHOW SETBACK DIMENSIONS FROM THE PROPOSED SWIMMING
 POOL TO THE PROPERTY LINE. SETBACK DIMENSIONS SHALL
 COMPLY WITH THE REQUIREMENTS OF ZLDR S.94-304(D).
  
 8.) PROPOSED A/C PAD (SHOWN IN THE SURVEY/SITE PLAN) AT
 THE NORTHEAST END OF THE PROPOSED RESIDENCE SEEMS TO BE
 IN CONFLICT WITH THE PROPOSED AREA FOR WASTE CONTAINER
 STORAGE (SHOWN IN THE ARCHITECTURAL SITE PLAN). PLEASE
 ADDRESS FOR CONSISTENCY.
  
 9.) REQUESTED INFORMATION ON THE ENTRANCE FEATURE HAS
 NOT BEEN PROVIDED (I.E. IS IT RAISED OR IS IT FLUSHED,
 ETC.). A PRELIMINARY DETAIL SHALL BE PROVIDED TO
 DETERMINE IF THE ENTRANCE FEATURE IS IN COMPLIANCE WITH
 THE ZLDRS. [7/30/19 REPEAT COMMENT]
  
 10.) SOME STRUCTURES SHOWN IN THE ARCHITECTURAL
 ELEVATIONS (I.E. PROPOSED LOCATION OF THE GENERATOR) DO
 NOT MATCH LOCATION IN THE SITE PLAN. PLEASE ADDRESS FOR
 CONSISTENCY.
  
  
 NOTES:
  
 * SEPARATE PERMITS AND REVIEWS REQUIRED FOR:
 LANDSCAPING, HARDSCAPES (I.E. DRIVEWAYS AND WALKWAYS,
 GENERATOR, ACCESSORY SCREEN ENCLOSURE (I.E. FOR
 GENERATOR AND WASTE CONTAINERS, ETC.).
  
 * REVISIONS TO THE PLANS MAY RESULT IN ADDITIONAL
 COMMENTS.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  
 * ZONE: SF7
  

Review Stop Z ZONING
Rev No 2 Status F Date 2019-07-30 Cont ID  
Sent By llouie Date 2019-07-30 Time   Rev Time 0.00
Received By llouie Date 2019-07-30 Time   Sent To  
Notes
2019-07-30 09:10:41** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) A SURVEY OF THE PROPERTY WAS NOT PROVIDED WITH THE
 PERMIT SUBMITTAL. PLEASE PROVIDE AS IT IS A REQUIRED
 DOCUMENT. [6/3/2019 REPEAT COMMENT]
  
 2.) LOT DIMENSIONS FROM THE SURVEY SHALL BE PROVIDED IN
 THE SITE PLAN ON ALL SIDES FOR CONSISTENCY. [6/3/2019
 REPEAT COMMENT]
  
 3.) THE CHIMNEY SHALL NOT EXCEED THE DISTRICT HEIGHT
 REQUIREMENTS BY 10%. PLEASE SHOW DIMENSIONS IN THE
 ELEVATIONS. THE HEIGHT OF THE CHIMNEY STILL DOES NOT
 SEEM TO COMPLY WITH THE HEIGHT REQUIREMENT. [6/3/2019
 REPEAT COMMENT]
  
 4.) THERE SEEMS TO BE SOME EXTERIOR SCREENING PROPOSED
 FOR WASTE CONTAINERS, EMERGENCY GENERATOR, POOL
 EQUIPMENT, ETC.,). PLEASE PROVIDE A DETAIL OF THE
 PROPOSED SCREENING (I.E. HEIGHT, ETC.). [6/3/2019
 REPEAT COMMENT]
  
 5.) HEIGHT OF THE SITE WALL AND A DETAIL SHALL BE
 PROVIDED. THE WALL CANNOT EXCEED 4 FT. IN HEIGHT WITHIN
 THE FIRST 25 FT. OF THE FRONT PROPERTY LINE, AND 6 FT.
 WITHIN THE REQUIRED SIDE AND REAR SETBACK. THE HEIGHT
 OF THE WALL SHALL BE MEASURED FROM THE LOWEST POINT AT
 GRADE TO THE HIGHEST POINT OF THE WALL. [ZLDR
 S.94-302(B.)]
  
 6.) HOW WIDE IS THE PROPOSED DRIVEWAY? PLEASE NOTE THAT
 A SINGLE DRIVEWAY SHALL NOT EXCEED 20 FT. IN WIDTH AT
 THE PROPERTY LINE. SHOW DIMENSIONS FOR COMPLIANCE.
 [ZLDR S.94-312(1)(C.)]
  
 7.) IS THE ENTRANCE FEATURE RAISED OR IS IT FLUSHED
 WITH THE SURFACE?
  
 NOTES:
  
 * SEPARATE PERMITS AND REVIEWS REQUIRED FOR:
 LANDSCAPING, HARDSCAPES (I.E. DRIVEWAY AND WALKWAY),
 GENERATOR, ACCESSORY SCREEN ENCLOSURE (I.E. FOR
 GENERATOR AND WASTE CONTAINERS), FIREPIT, ETC.
  
 * REVISION MAY RESULT IN ADDITIONAL COMMENTS.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  
 * ZONE: SF7
  
  

Review Stop Z ZONING
Rev No 1 Status F Date 2019-06-03 Cont ID  
Sent By llouie Date 2019-06-03 Time   Rev Time  
Received By llouie Date 2019-06-03 Time   Sent To  
Notes
2019-06-03 16:29:00** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) A SURVEY OF THE PROPERTY WAS NOT PROVIDED WITH THE
 PERMIT SUBMITTAL. PLEASE PROVIDE AS IT IS A REQUIRED
 DOCUMENT.
  
 2.) LOT DIMENSIONS FROM THE SURVEY SHALL BE PROVIDED IN
 THE SITE PLAN FOR CONSISTENCY.
  
 3.) THE SITE PLAN HAS A LOT OF OVERLAPPING WHICH MAKES
 IT DIFFICULT TO READ THE DIMENSIONS AND OTHER PERTINENT
 INFORMATION. PLEASE ENSURE THAT THERE IS NO TEXT
 OVERLAP. ADDITIONALLY, THE LANDSCAPING SHOULD NOT BE
 PROVIDED IN THE SITE PLAN, AS ANY EXISTING/PROPOSED
 LANDSCAPING FOR THE PROJECT SHALL BE REVIEWED AS A
 SEPARATE LANDSCAPE PERMIT PRIOR TO THE ISSUANCE OF THIS
 PERMIT.
  
 4.) SHOW THE SETBACK DISTANCE OF ALL PROPOSED
 STRUCTURES (I.E. SWIMMING POOL, DRIVEWAYS, A/C UNIT
 PAD, ETC.) TO THE PROPERTY LINES TO ENSURE ALL
 STRUCTURES WILL MEET THE MINIMUM SETBACK DISTANCES PER
 THE ZONING AND LAND DEVELOPMENT REGULATIONS (ZLDRS).
  
 5.) THE MAXIMUM HEIGHT OF THE BUILDING SHALL NOT EXCEED
 30 FT. THE HEIGHT OF THE BUILDING SHALL BE MEASURED
 FROM GRADE OF THE OUTSIDE WALL TO THE MID-HEIGHT LEVEL
 BETWEEN THE EAVES AND THE RIDGE FOR GABLE, HOP AND
 GAMBREL ROOFS. [ZLDR S.94-72(A)(3)]
  
 6.) THE CHIMNEY SHALL NOT EXCEED THE DISTRICT HEIGHT
 REQUIREMENTS BY 10%. PLEASE SHOW DIMENSIONS IN THE
 ELEVATIONS. [ZLDR S.94-306]
  
 7.) THERE SEEMS TO BE SOME EXTERIOR SCREENING PROPOSED
 FOR THE WASTE CONTAINERS, EMERGENCY GENERATOR, POOL
 EQUIPMENT, ETC.). PLEASE PROVIDE A DETAIL OF THE
 PROPOSED SCREENING (I.E. HEIGHT, SETBACK FROM PROPERTY
 LINES, ETC.). SUCH FEATURE SHALL ALSO BE ILLUSTRATED IN
 THE ELEVATIONS.
  
 8.) FLOOR PLANS DO NOT MATCH THE ELEVATIONS. PLEASE
 REVIEW AND ADDRESS FOR CONSISTENCY.
  
 9.) A CIRCULAR DRIVEWAY SHALL NOT EXCEED 10 FT. IN
 WIDTH AT THE PROPERTY LINE FOR EACH DRIVEWAY OPENING.
 PLEASE PROVIDE DIMENSIONS FOR COMPLIANCE WITH THE
 ZLDRS. [ZLDR S.94-312(1)]
  
 10.) PLEASE ENSURE THAT ALL COMPONENTS OF PROPOSED
 DRIVEWAY COMPLY WITH THE SETBACK DIMENSIONS OF THE
 ZLDRS BY DENOTING THE SETBACK(S) DISTANCE FROM THE
 DRIVEWAY TO THE PROPERTY LINE IN THE SITE PLAN (I.E.
 PORTION OF THE VEHICULAR TURNAROUND).
  
 11.) STRUCTURAL OVERHANGS (I.E. EAVES, ROOF OVERHANGS,
 ETC.) SHALL NOT EXTEND MORE THAN 3 FT. INTO ANY
 REQUIRED SETBACK. PLEASE SHOW DIMENSIONS FOR COMPLIANCE
 WITH THIS REQUIREMENT. [ZLDR S.94-305(B)(2)]
  
 NOTES:
  
 * SEPARATE PERMITS AND REVIEWS REQUIRED FOR:
 LANDSCAPING, HARDSCAPES (I.E. DRIVEWAY AND WALKWAYS),
 GENERATOR, ACCESSORY SCREEN ENCLOSURE (I.E. FOR
 GENERATOR AND WASTE CONTAINERS), FIREPIT, ETC.
  
 * REVISION MAY RESULT IN ADDITIONAL COMMENTS.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  
 * ZONE: SF7
  