Plan Review Details - Permit 19050358
| Plan Review Stops For Permit 19050358 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2019-06-24 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2019-06-24 |
Time |
12:56 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2019-06-24 |
Time |
12:56 |
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2019-06-24 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2019-06-24 |
Time |
07:07 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2019-06-24 |
Time |
06:51 |
Sent To |
I |
|
| Notes |
| 2019-06-24 06:51:30 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. CONTRACT FOR VALUE OF WORK, TO INCLUDE ALL MATERIALS | | | AND LABOR, WAS NOT PROVIDED AS PER LAST PLAN REVIEW | | | COMMENTS, AND/OR VALUE OF WORK WAS NOT INCREASED. | | | | | | FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING | | | PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE | | | TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL, | | | ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH, | | | RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES, | | | MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY | | | LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST | | | PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS | | | SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY | | | INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT | | | VALUATION SHALL BE SET BY THE BUILDING OFFICIAL. | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | CODES IN EFFECT: | | | | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE 2017 6TH ED. | | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | | 6TH EDITION | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | V/R, | | | | | | FRANK GIAQUINTO III | | | ELECTRICAL INSPECTOR | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | [email protected] | | | CELL: 561-657-1653 | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2019-05-27 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2019-05-27 |
Time |
11:15 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2019-05-27 |
Time |
11:15 |
Sent To |
I |
|
| Notes |
| 2019-05-27 11:15:35 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | FAC = FLORIDA ADMINISTRATIVE CODE | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. PER THE WPB AMENDMENTS TO THE FBC, PLAN (EACH SHEET | | | OF BOTH COPIES) IS REQUIRED TO BEAR THE NAME AND BE | | | SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR THE | | | DESIGN. THE SEAL MUST LEGIBLE AND CONTAIN THE | | | INFORMATION REQUIRED PER FAC 61G15-23.002. SOME OF THE | | | PAGES HAVE A SEAL THAT IS ILLEGIBLE, SOME SHEETS ARE | | | MISSING THE SIGNATURE/SEAL. SYSTEMS WITH A VALUE | | | GREATER THAN $5,000 REQUIRE AN ENGINEER STAMPED PLAN. | | | PROVIDE CORRECTION. WPB FBC 107.1, 107.2, 105.3.1.2(4); | | | FS 471, 481 | | | 2. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS | | | LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND | | | VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. WPB | | | FBC 109.3 | | | 3. THE NEC AND FBC SPECIFIED FOR DESIGN IS NOT THE | | | CURRENT CODE. PROVIDE CORRECTION. FBC PREFACE (ALSO SEE | | | CURRENT CODES ABOVE) | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY | | | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED | | | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD | | | SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2019-06-18 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2019-06-18 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2019-06-18 |
Time |
14:40 |
Sent To |
E |
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2019-05-22 |
|
|
Cont ID |
|
| Sent By |
sathomas |
Date |
2019-05-22 |
Time |
00:00 |
Rev Time |
0.00 |
| Received By |
sathomas |
Date |
2019-05-22 |
Time |
00:00 |
Sent To |
E |
|
| Notes |
| 2019-05-22 12:34:32 | PROVISO: | | | 1. SUBJECT TO FIELD VERIFICATION WITH RADIO TEST. | | | 2. BDA SYSTEM INSTALLATION SHALL COMPLY WITH THE 5TH | | | EDITION (2015) OF THE FLORIDA FIRE PREVENTION CODE, | | | INCLUDING NFPA 1 & 101, AND THE 7TH EDITION (2013) OF | | | NFPA 72. | | | | | | S. THOMAS | | | 561-804-4728 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2019-06-24 |
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
2019-06-24 |
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2019-06-24 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2019-06-24 |
Time |
07:07 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2019-06-12 |
Time |
15:42 |
Sent To |
|
|
| Notes |
| 2019-06-13 15:42:29 | RESUB ROUTED TO FIRE INBOX |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2019-05-27 |
Time |
|
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2019-05-07 |
Time |
13:28 |
Sent To |
|
|
| Notes |
| 2019-05-08 13:28:43 | ROUTED TO FIRE INBOX |
|
|
|