| 2019-05-24 14:05:44 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. THERE IS A CONFLICT WITH RISER DIAGRAM AND PANEL |
| | SCHEDULES. WHAT APPEARS TO BE A SUB-PANEL IS SHOWN AS |
| | 100 AMP, 150 AMP, AND 200 AMP. WHICH IS IT? IS THIS |
| | PANEL NEW OR EXISTING, IT IS MARKED BOTH NEW AND |
| | EXISTING WHICH IS IMPOSSIBLE? WHAT WIRE SIZE IS TO BE |
| | INSTALLED FOR THIS PANEL. WHERE IS THIS FED FROM? IT |
| | SHOWS BEING CONNECTED TO THE MAIN PANEL, BUT THERE IS |
| | NO BREAKER IN THE MAIN PANEL FOR THIS. PROVIDE ACCURATE |
| | RISER DIAGRAM. NEC 215.5, 230, 250.50, 250.94, 408.30; |
| | FBC RE E3706.1, E3608.1, E3609.3; WPB FBC 107.2.1 |
| | 2. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL |
| | LOADS. PLAN SHOWS A TANKLESS WATER HEATER, BUT THE |
| | CALCULATION INCLUDES A STANDARD WATER HEATER. LOAD |
| | CALCULATION SHOULD BE IN THE FORMAT STIPULATED IN THE |
| | FBC RESIDENTIAL. THERE SHOULD BE AN OVERALL LOAD |
| | CALCULATION FOR THE SERVICE, AS WELL AS THE CALCULATION |
| | FOR ANY SUB-PANEL. NEC 220; FBC RE E3602.2 |
| | 3. SMOKE ALARMS MUST BE INSTALLED AT LEAST 3 FEET FROM |
| | BATHROOM DOOR, 3 FEET FROM CEILING FANS, AND 3 FEET |
| | FROM ANY MECHANICAL DUCT. PROVIDE CORRECTIONS. FBC RE |
| | R314.3(4), NFPA 72:29.8.3.4 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD |
| | SHEETS. |
| | |
| | SINCERELY, |
| | |
| | JOHN PEARSON |
| | ELECTRICAL PLANS EXAMINER |
| | 561-805-6746 |
| | [email protected] |
| | |