Plan Review Details - Permit 19050351
Plan Review Stops For Permit 19050351
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-06-13 Cont ID  
Sent By cthroop Date 2019-06-13 Time 16:47 Rev Time 0.00
Received By cthroop Date 2019-06-13 Time 16:42 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-05-22 Cont ID  
Sent By pvalenti Date 2019-05-22 Time 17:01 Rev Time 0.00
Received By pvalenti Date 2019-05-22 Time 16:10 Sent To  
Notes
2019-05-22 17:30:49***CORRECTIONS***
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1ST BUILDING PLAN REVIEW DENIED:
  
 FBC B 107.
  
 1. PROVIDE A WINDOW/DOOR SCHEDULE, ON PLANS, FOR
 WINDOWS AND DOORS. THE PLANS ARE NOT CLEAR AS TO WHAT
 EACH INDICATOR REPRESENTS (A, B, 1, 3, 4 ?).
  
 2. PRODUCT APPROVAL # 17-0504.01 (IMPACT RESISTANT
 ALUMINUM OUTSWING FRENCH DOOR) WAS SUBMITTED BUT THERE
 IS NO INDICATED LOCATION ON
 PLANS FOR THIS DOOR.
  
 3. PROVIDE DETAILS FOR THE INTERIOR WALL FRAMING,
 DRYWALL, AND CEMENT TYPE WALL BOARD FOR THE NEW SHOWER
 AREAS. PLEASE INCLUDE INSULATION (IF DESIRED),
 ANCHORING, AND FASTENING TYPES/PATTERNS.
  
 NOTE:
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL COMMENTS MAY
 RESULT IN NEW PLAN REVIEW COMMENTS.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2019-06-13 Cont ID  
Sent By jpearson Date 2019-06-13 Time 14:12 Rev Time 0.00
Received By jpearson Date 2019-06-13 Time 14:12 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2019-05-24 Cont ID  
Sent By jpearson Date 2019-05-24 Time 14:06 Rev Time 0.00
Received By jpearson Date 2019-05-24 Time 14:06 Sent To M
Notes
2019-05-24 14:05:44CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. THERE IS A CONFLICT WITH RISER DIAGRAM AND PANEL
 SCHEDULES. WHAT APPEARS TO BE A SUB-PANEL IS SHOWN AS
 100 AMP, 150 AMP, AND 200 AMP. WHICH IS IT? IS THIS
 PANEL NEW OR EXISTING, IT IS MARKED BOTH NEW AND
 EXISTING WHICH IS IMPOSSIBLE? WHAT WIRE SIZE IS TO BE
 INSTALLED FOR THIS PANEL. WHERE IS THIS FED FROM? IT
 SHOWS BEING CONNECTED TO THE MAIN PANEL, BUT THERE IS
 NO BREAKER IN THE MAIN PANEL FOR THIS. PROVIDE ACCURATE
 RISER DIAGRAM. NEC 215.5, 230, 250.50, 250.94, 408.30;
 FBC RE E3706.1, E3608.1, E3609.3; WPB FBC 107.2.1
 2. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL
 LOADS. PLAN SHOWS A TANKLESS WATER HEATER, BUT THE
 CALCULATION INCLUDES A STANDARD WATER HEATER. LOAD
 CALCULATION SHOULD BE IN THE FORMAT STIPULATED IN THE
 FBC RESIDENTIAL. THERE SHOULD BE AN OVERALL LOAD
 CALCULATION FOR THE SERVICE, AS WELL AS THE CALCULATION
 FOR ANY SUB-PANEL. NEC 220; FBC RE E3602.2
 3. SMOKE ALARMS MUST BE INSTALLED AT LEAST 3 FEET FROM
 BATHROOM DOOR, 3 FEET FROM CEILING FANS, AND 3 FEET
 FROM ANY MECHANICAL DUCT. PROVIDE CORRECTIONS. FBC RE
 R314.3(4), NFPA 72:29.8.3.4
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-05-29 Cont ID  
Sent By jpearson Date 2019-05-29 Time 07:18 Rev Time 0.00
Received By jpearson Date 2019-05-24 Time 09:50 Sent To  
Notes
2019-05-29 07:18:35THIS STOP WAS LOCKED AND COULD NOT BE EDITED, SEE
 REVIEW COMMENTS ON ELECTRICAL STOP 2.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-06-13 Cont ID  
Sent By cthroop Date 2019-06-13 Time 16:47 Rev Time 0.00
Received By cthroop Date 2019-06-03 Time 15:28 Sent To  
Notes
2019-06-04 15:28:22R18

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2019-05-27 Time   Rev Time 0.00
Received By lmarchan Date 2019-05-07 Time 14:16 Sent To  
Notes
2019-05-27 08:45:15THE FIRST ELECTRICAL STOP HAS BEEN LOCKED ON ACCIDENT
 AND NEEDS TO BE DELETED. I SENT A REQUEST TO IT ON
 5/24, BUT IT HAS NOT BEEN FIXED YET. JP
  
  
2019-05-08 14:16:29R05

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2019-05-25 Cont ID  
Sent By cmontell Date 2019-05-25 Time 07:39 Rev Time 0.00
Received By cmontell Date 2019-05-25 Time 07:39 Sent To E
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-06-11 Cont ID  
Sent By jesmith Date 2019-06-11 Time 11:02 Rev Time 0.00
Received By jesmith Date 2019-06-11 Time 10:36 Sent To  
Notes
2019-06-11 11:01:58APPROVED WITH PROVISO
 TANKLESS WATER HEATER SHALL BE APPROVED FOR EXTERIOR
 USE, PROVIDE MANUFACTURER SPECS FOR TANKLESS HEATER
 PRIOR TO FINAL INSPECTION.
  
 19050351 503 PALMETTO ST
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2019-05-09 Cont ID  
Sent By gjohnson Date 2019-05-09 Time 15:05 Rev Time 0.00
Received By gjohnson Date 2019-05-09 Time 14:53 Sent To  
Notes
***NONE***