| 2019-05-15 12:12:50 | THRESHOLD PLAN REVIEW |
| | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | BUILDING PLANS EXAMINER, PX3169 |
| | 1&2 FAMILY PLANS EXAMINER, SFP306 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | 1ST REVIEW |
| | RESULTS: DENIED |
| | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| | BELOW. |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | 1. TEMPORARY MEMBRANE STRUCTURES (TENTS) |
| | 2017 FBC CHAPTER 31 |
| | SPECIAL CONSTRUCTION |
| | |
| | SECTION 3103 |
| | TEMPORARY STRUCTURES |
| | |
| | 2. CONFORMANCE PER SECTION 3103.1.1 |
| | TEMPORARY STRUCTURES AND USES SHALL CONFORM TO THE |
| | STRUCTURAL STRENGTH, FIRE SAFETY, MEANS OF EGRESS, |
| | ACCESSIBILITY, LIGHT, VENTILATION AND SANITARY |
| | REQUIREMENTS OF THIS CODE AS NECESSARY TO ENSURE PUBLIC |
| | HEALTH, SAFETY AND GENERAL WELFARE. |
| | A. STRUCTURAL STRENGTH PER FBC CHPT. 16 ? FOR |
| | STRUCTURES WITH SPANS OF 30 FEET OR GREATER. |
| | B. FIRE SAFETY ? PROVIDE FLAME SPREAD TEST REPORTS PER |
| | NFPA 701 FOR EACH TENT |
| | C. MEANS OF EGRESS 1) OPEN SIDES ? NO LIFE SAFETY PLAN |
| | REQUIRED. |
| | 2) CLOSED SIDES ? PROVIDE LIFE SAFETY PLAN |
| | A) STATE OCCUPANT LOAD. |
| | B) IDENTIFY MEANS OF EGRESS. |
| | C) IDENTIFY PATH OF TRAVEL ? 100 FT. OR LESS TO |
| | EXIT. |
| | D) PROVIDE FLOOR LAYOUT OF EVENT. |
| | D. ACCESSIBILITY 1) IDENTIFY ACCESSIBLE ROUTE ON SITE |
| | PLAN |
| | E. LIGHT 1) OPEN SIDES ? N/A |
| | 2) CLOSED SIDES ? PER SEC. 1008.2.1 > 1 FOOT CANDLE |
| | F. VENTILATION 1) OPEN SIDES ? N/A |
| | 2) CLOSED SIDES ? PER SEC. 1203 |
| | G. SANITARY 1) IDENTIFY EXISTING PERMANENT FACILITIES |
| | ON SITE PLAN |
| | 2) PROVIDE PORTABLE FACILITIES PER TABLE 2902. |
| | |
| | 3. FOR TEMPORARY MEMBRANE STRUCTURES (TENTS) WITH A |
| | SPAN OF 40 FEET OR GREATER IN ANY DIRECTION: |
| | |
| | A. PROVIDE DETAILS OF STRUCTURAL CONNECTIONS. INCLUDE |
| | BASEPLATE/TIEDOWN DETAILS. |
| | B. PROVIDE STRUCTURAL EVALUATION OF STRUCTURE. |
| | |
| | THESE DOCUMENTS SHALL BE REVIEWED, SIGNED AND SEALED BY |
| | A DESIGN PROFESSIONAL. |
| | |
| | NO EXCEPTIONS |
| | |
| | _______________________________________________________ |
| | _________ |
| | |
| | ***ADDITIONAL REQUIREMENTS |
| | FOR TEMPORARY MEMBRANE STRUCTURES (TENTS) WITH AN |
| | ?ASSEMBLY OCCUPANCY CLASSIFICATION AS DEFINED IN THE |
| | FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT. IN |
| | AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500 |
| | PERSONS?. |
| | |
| | FLORIDA STATUTE 553.79 ?THREHOLD STRUCTURE? SHALL APPLY |
| | |
| | A. PROVIDE THRESHOLD INSPECTOR AGREEMENT ? WILL BE |
| | PROVIDED TO APPLICANT |
| | B. PROVIDE THRESHOLD INSPECTION PLAN |
| | C. PROVIDE AFFIDAVIT ?CERTIFICATE OF CODE COMPLIANCE? |
| | _______________________________________________________ |
| | _______________ |
| | |
| | |
| | |
| | |
| | |