Plan Review Details - Permit 19050305
Plan Review Stops For Permit 19050305
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2019-08-12 Cont ID  
Sent By jwitmer Date 2019-08-12 Time 12:40 Rev Time 0.00
Received By jwitmer Date 2019-08-12 Time 11:59 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-07-17 Cont ID  
Sent By jwitmer Date 2019-07-17 Time 11:08 Rev Time 0.00
Received By jwitmer Date 2019-07-15 Time 16:09 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-06-04 Cont ID  
Sent By jwitmer Date 2019-06-04 Time 14:30 Rev Time 0.00
Received By jwitmer Date 2019-06-04 Time 10:34 Sent To  
Notes
2019-06-04 14:30:072017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19050305
 ADD: 700 S. ROSEMARY AVE. SUITE: 116
 CONT:TBD/ TO BE DETERMINED
 TEL: ????????????????
 E-MAIL; [email protected] AMY HODGSON
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. JUNE 4, 2019
 ACTION: DENIED
  
 1) PLEASE NOTE NONE OF THE ARCHITECTURAL SHEETS
 SUBMITTED FOR THIS REVIEW HAVE A DIGITAL SIGNATURE.
 PLEASE SHOW COMPLIANCE WITH FLORIDA ADMINISTRATIVE CODE
 ARCHITECT DIGITAL SIGNING & SEALING PLANS:
 61G1-16.005 PROCEDURES FOR DIGITALLY SIGNING AND
 SEALING AND FOR ELECTRONICALLY TRANSMITTING PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
 2) THE COVERSHEET A0.1:
 2A). BUILDING CODE INFORMATION INDICATES THE PLANS WERE
 DEVELOPED UNDER THE 2014 FBC-B. PLEASE BE AWARE THAT
 STATEWIDE THE 2017 FBC FAMILY OF CODES WERE ADOPTED ON
 DEC. 31/ 2017. PLEASE UPDATE CODES AND RELEVANT CHANGES
 THAT WERE MADE.
  
 2B). UNDER THE HEADING OF OCCUPANCY CALCULATIONS THE
 RETAIL/ MERCANTILE IS USING AN OCCUPANT LOAD FACTOR OF
 30. PLEASE BE AWARE OF THE CHANGE IN THE 2017 FBC-B
 THAT ALL FLOORS ARE TO USE A LOADING FACTOR OF 60.
 PLEASE SEE 2017 FBC-B TABLE 1004.1.2. PLEASE UPDATE THE
 PLANS.
  
 2C. UNDER THE HEADING OF OCCUPANCY CALCULATIONS THE
 BUSINESS/ CLASSROOM WE ARE OK WITH THE USAGE OF 30 LOAD
 FACTOR, IT IS BETWEEN THE 20 FOR CLASSROOM & 50 FOR
 VOCATIONAL ROOMS, IT IS MORE RESTRICTIVE THAN THE LOAD
 FACTOR OF 50 FOR VOCATIONAL ROOMS.
  
 2D) UNDER THE BUILDING CODE INFORMATION THIS SHEET DOES
 NOT PROVIDE IF THIS PLAN WAS DESIGNED AS SEPARATED
 OCCUPANCY AND TABLE 508.4 OR IF THE PLAN WAS DESIGNED
 AS NONSEPARATED OCCUPANCIES UNDER 508.3 FBC-B. PLEASE
 ALSO NOTE THE STORAGE OCCUPANCY DOES NOT INDICATE IF
 THE STORAGE OCCUPANCY IS A S1 OR S2 OCCUPANCY. SHEET
 003-A.03 THE CODE PLAN DOES NOT SHOW OCCUPANCY
 SEPARATION.
  
 3) SHEET 003-A0.3 SHOWS EXIT ACCESS THROUGH A CORRIDOR
 106 TO AN EXIT FROM THE TENANT SPACE. THE PLAN IS
 SILENT AS TO WHAT TYPE OF EXIT ENCLOSURE THE OCCUPANTS
 ARE ENTERING? PLEASE SEE 2017 FBC-B402.8.6.1.
  
 4) NOA 17-0201.03 SERIES SMI-090 ALUMINUM WINDOW WALL
 SYSTEM L. M. I., SHEETS 007, 008 & 009. NONE OF THE
 DETAILS SHEETS HAVE BEEN MARKED UP TO SHOW CODE
 COMPLIANCE.
 IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE
 PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF
 RECORD AND BEFORE SUBMISSION TO THE BUILDING
 DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE
 IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING,
 MULLION SIZE, LENGTH IF UNREINFORCED OR REINFORCED
 INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE
 PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B 1405.13.1
 INSTALLATION. WINDOWS AND DOORS SHALL BE INSTALLED IN
 ACCORDANCE WITH APPROVED MANUFACTURER?S INSTRUCTIONS.
 FASTENER SIZE AND SPACING SHALL BE PROVIDED IN SUCH
 INSTRUCTIONS AND SHALL BE CALCULATED BASED ON MAXIMUM
 LOADS AND SPACING USED IN THE TESTS.
  
 5) NOA 17-0926.16 SUMMIT ALUMINUM ENTRANCE DOOR W/WO
 TRANSOM- L.M.I., SHEETS 010, 011, & 012. NONE OF THE
 DETAILS SHEETS HAVE BEEN MARKED UP TO SHOW CODE
 COMPLIANCE.
 IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE
 PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF
 RECORD AND BEFORE SUBMISSION TO THE BUILDING
 DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE
 IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING,
 MULLION SIZE, LENGTH IF UNREINFORCED OR REINFORCED
 INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE
 PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B 1405.13.1
 INSTALLATION. WINDOWS AND DOORS SHALL BE INSTALLED IN
 ACCORDANCE WITH APPROVED MANUFACTURER?S INSTRUCTIONS.
 FASTENER SIZE AND SPACING SHALL BE PROVIDED IN SUCH
 INSTRUCTIONS AND SHALL BE CALCULATED BASED ON MAXIMUM
 LOADS AND SPACING USED IN THE TESTS.
  
 6) SHEET 061-S1.1 UNDER THE HEADING GENERAL STRUCTURAL
 NOTES:
 6A) BUILDING CODE. THE BUILDING CODE DATA NEEDS TO BE
 UPDATED. THESE PLANS WERE LAST USED IN THE CITY OF
 JACKSONVILLE, WITH THEIR LOCAL AMENDMENTS, PLEASE
 UPDATE PLANS.
  
 6B) UNDER THE HEADING OF WIND, ONLY A PARTIAL WIND
 DESIGN DATA WAS INCLUDED. THE MEAN ROOF HEIGHT IS NOT
 GIVEN, NEGATIVE PRESSURES ARE ALWAYS TAKEN FROM THE
 MEAN ROOF HEIGHT.
  
 6C) THE STOREFRONT DESIGN WIND PRESSURE IS GIVEN AT 68
 PSF. THE PLAN DOES NOT STATE IF THIS PRESSURE IS IN
 VULT OR VASD. THE PLAN ALSO DOES NOT INCLUDE AT WHAT
 EFFECTIVE WIND AREA OR TRIBUTARY AREA THIS PRESSURE IS
 GOOD FOR NOR DOES THE PLAN INDICATE IF THIS FOR AN
 INTERIOR WALL ZONE (4) OR IF THE GIVEN PRESSURES IS FOR
 AN EXTERIOR OR END WALL ZONE(5). NON ENOUGH INFORMATION
 TO DETERMINE CODE COMPLIANCE. PLEASE PROVIDE PRESSURES
 IN CHART FORM 10 SQ. FT. 20 SQ. FT. 50 SQ. FT. 50 SQ.
 FT. & 100 SQ. FT. AND IN VASD SINCE THE PRODUCT
 APPROVAL PRESSURES ARE IN VASD.
 2017 FBC-B TABLE 1609.7(2) ADJUSTMENT FACTORS FOR
 HEIGHT & EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING. 1609.3.1 WIND SPEED CONVERSION VULT TO VASD.
  
 7) AT THE TIME OF EITHER THE STEEL FRAMING INSPECTION
 OR WINDOW BUCK INSPECTION PLEASE PROVIDE THE FOLLOWING:
 THE CONTRACTOR IS REQUIRED TO PROVIDE WELD PROCEDURE
 SPECIFICATIONS & WELDER OPERATOR PERFORMANCE
 QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED
 STANDARDS AT TIME OF INSPECTION. IN ACCORDANCE WITH THE
 AMERICAN WELDING SOCIETY.
 2017 FBC-B 2204.1 WELDING
 2017 FBC-B 2204.2 BOLTING.
  
 8A)(1) SHEET 014-A2.1 FLOOR AND FINISH PLAN THE TENANT
 WALLS THAT BACK UP TO THE EXIT PASSAGEWAY SHOW ON THE
 FLOOR PLAN 1 HOUR RATING WALL IDENTIFICATION TAGS A &
 E. THE PERIMETER WALL (EXIT PASSAGEWAY) SHOWS WALL
 TYPES A & A4 AS ONE HOUR RATED BUT SHEET 026-A9.1 DOES
 NOT SHOW THE A TYPE WALLS AS 1 HOUR RATED. 2017 FBC-B
 402.6.8.1, & 1024.3.
  
 8A)(2) SHEET 014-A2.1 FLOOR AND FINISH PLAN THE TENANT
 WALLS THAT BACK UP TO THE EXIT PASSAGEWAY SHOW ON THE
 FLOOR PLAN 1 HOUR RATING WALL IDENTIFICATION TAG E. THE
 PERIMETER WALL (EXIT PASSAGEWAY) SHOWS WALL TYPES E &
 E1 AS ONE HOUR RATED BUT SHEET 026-A9.1 DOES SHOW THE E
 TYPE WALLS AS 1 HOUR RATED BUT THERE IS NO UL RATING OR
 GYPSUM ASSOCIATION RATING SHOWN. 2017 FBC-B 402.6.8.1,
 & 1024.3.
 9) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2019-08-08 Cont ID  
Sent By jpearson Date 2019-08-08 Time 10:41 Rev Time 0.00
Received By jpearson Date 2019-08-08 Time 10:41 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2019-07-18 Cont ID  
Sent By jpearson Date 2019-07-18 Time 11:24 Rev Time 0.00
Received By jpearson Date 2019-07-18 Time 11:24 Sent To  
Notes
2019-07-18 11:24:15CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. NO ELECTRICAL ISSUES, BUT CANNOT APPROVE THE PLAN
 UNTIL THE SIGNATURE ISSUE IS RESOLVED. PLEASE SEE
 SIGNATURE COMMENTS. WPB FBC 107.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-05-30 Cont ID  
Sent By jpearson Date 2019-05-30 Time 14:10 Rev Time 0.00
Received By jpearson Date 2019-05-29 Time 15:07 Sent To  
Notes
2019-05-30 14:10:16CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS,
 DAS, LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD
 SYSTEMS, WALK IN COOLERS, SIGNS, SITE LIGHTING, AND
 SWIMMING POOLS (WHERE APPLICABLE) ARE NOT INCLUDED IN
 THE SCOPE OF THIS PLAN REVIEW. PROVIDE A BLOCK NOTE
 INDICATING THE REQUIRED SEPARATE PERMITS AND PLAN
 SUBMITTALS FOR ANY OF THESE SYSTEMS PRESENT. WPB FBC
 105.1, 107.2.1
 2. PROVIDE SHOW WINDOW OUTLETS PER CODE. NEC 210.62
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2019-08-06 Cont ID  
Sent By pleduc Date 2019-08-06 Time   Rev Time 0.00
Received By pleduc Date 2019-08-06 Time 10:31 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-06-26 Cont ID  
Sent By pleduc Date 2019-06-26 Time   Rev Time 0.00
Received By pleduc Date 2019-06-25 Time 09:12 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2019-05-13 Cont ID  
Sent By pleduc Date 2019-05-13 Time   Rev Time 0.00
Received By pleduc Date 2019-05-13 Time 15:18 Sent To  
Notes
2019-05-13 15:31:02THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) SHEET 0.1 - THERE IS AN INCORRECT REFERENCE TO THE
 CURRENT EDITION OF THE FLORIDA FIRE PREVENTION CODE AND
 NEC.
  
 PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE 6TH
 EDITION OF FLORIDA FIRE PREVENTION CODE WHICH INCLUDES
 THE 2015 EDITION OF NFPA 1 AND NFPA 101.
  
 ELECTRIC WORK SHALL COMPLY WITH NFPA 70, 2014 EDITION.
  
 PLEASE REVIEW AND ENSURE COMPLIANCE WITH THE APPLICABLE
 EDITIONS.
  
  
 2) SHEETS A 0.6 & M0.04 - THERE ARE INDICATIONS OF A
 MECAHINCAL HOOD AND FIRE SUPPRESSION SYSTEM.
  
 THE HOOD SYSTEM SHALL COMPLY WITH NFPA 96 AND SHALL BE
 SUBMITTED UNDER SEPARATE PERMIT AND SHOP DRAWINGS.
  
 PLEASE ENSURE THAT THE HOOD IS PERMITTED PROPERLY.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2019-08-13 Cont ID  
Sent By jesmith Date 2019-08-13 Time 15:46 Rev Time 0.00
Received By jesmith Date 2019-08-13 Time 15:45 Sent To  
Notes
2019-08-13 15:46:06FUEL GAS COMMEMTS: APPROVED
 ALL WORK PER CITY CODES SUBJECT TO FIELD INSPECTOR'S
 APPROVAL

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2019-07-09 Cont ID  
Sent By jesmith Date 2019-07-09 Time 13:53 Rev Time 0.00
Received By jesmith Date 2019-07-09 Time 13:25 Sent To  
Notes
2019-07-09 13:53:51CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 NFPA 30A
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
  
 2ND REVIEW
 PLUMBING COMMEMTS: DENIED
  
 1. PER WPB FBC 107.2.1, PROVIDE MATERIAL TYPE, SIZING
 AND SIZING CHART FOR ABOVE GROUND PIPING TO APPLIANCES
 PER WPB FBC 107.2.1.
 2. PER WPB FBC 107.2.1, PROVIDE MANUFACTURER?S SPEC FOR
 MP REGULATOR. PROVIDE DETAIL FOR VENTING OF SAID
 REGULATOR IF NOT EQUIPPED WITH AND LABELED FOR
 UTILIZATION WITH AN APPROVED VENT-LIMITING DEVICE
 INSTALLED IN ACCORDANCE WITH THE MANUFACTURER?S
 INSTRUCTIONS IN ACCORDANCE WITH FBC FG 410.3.
 3. PER WPB FBC 107.2.1, PROVIDE NOTE ON PLAN SHEET
 P3.03 AT THE GAS CONTROL VALVE ON THE GAS RISER DIAGRAM
 WHICH STATES ?REFER TO GAS VALVE DETAIL AND SCHEDULE ON
 PLAN SHEET FP1.02?
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  
 19050305 700 S ROSEMARY AVE # 116
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2019-05-16 Cont ID  
Sent By thunt Date 2019-05-16 Time 14:07 Rev Time 0.00
Received By thunt Date 2019-05-16 Time 14:07 Sent To  
Notes
2019-05-16 14:08:24GAS 1ST REVIEW**DENIED** NOTE - A COMPREHENSIVE REVIEW
 COULD NOT BE DONE AT THIS TIME AND ADDITIONAL PLAN
 REVIEW COMMENTS MAY BE GENERATED UPON THE RE-REVIEW OF
 SUBMITTED CORRECTIONS.
  
 1) SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE
 CORRUGATED STAINLESS STEEL TUBING IF APPLICABLE) FOR
 EACH PIPE SIZE. WPB AMENDMENTS TO FBC SEC.107.2.1.
  
 2) SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE,
 TERMINATION POINT, HEIGHT ABOVE THE ROOF AND ANCHORING
 DETAILS OF THE GAS VENT(S) PER 2017 FBC-FUEL GAS SECS.
 502 THRU 505
  
 3) SUBMIT COMBUSTION AIR CALCULATIONS FOR THE ADDED
 STOVE/ RANGES. WHERE COMBUSTION AIR IS PROVIDED BY THE
 BUILDING?S MECHANICAL VENTILATION SYSTEM, THE SYSTEM
 SHALL PROVIDE THE SPECIFIED COMBUSTION AIR RATE IN
 ADDITION TO THE REQUIRED VENTILATION AIR. 2017 FBC-FUEL
 GAS SEC.304.9.3
  
 4) PROVIDE SIZING CHARTS FOR ALL MATERIALS AND PRESSURE
 USE IN YOUR DESIGN. CSST SIZING TABLES NOT PROVIDED.
 SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES USED
 TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE
 PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM
 THE GAS CODE OR OTHER STANDARD THAT WERE USED IN THE
 DESIGN OF THIS GAS SYSTEM. REFER TO THE 2017 FBC-FUEL
 GAS SECS. 401.4, 401.8, 402.3, AND TABLES 402.4 (1)
 THRU 402.4 (37)
  
 5) SHOW THE LOCATION OF ALL MP (STEP-DOWN) REGULATORS.
 A LISTED SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY
 AHEAD OF EACH MP REGULATOR. 2017 FBC-FUEL GAS
 SEC.409.4,
  
 6) SHOW THE DISTANCE FROM THE 2 PSI REGULATOR TO THE
 APPLIANCE. COMPLY WITH 2017 FBC-FUEL GAS SEC. 402.4.1
 FOR THE PROPER PIPE SIZE AND BTU LOAD.
  
 7) SUBMIT MANUFACTURER'S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2017 FUEL GAS CODE SEC. 402.2, AND 301.3. GAS
 APPLIANCES SHALL BE LISTED AND LABELED.
  
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR
 BUILDING DIVISION
 CITY OF WEST PALM BEACH
 401 CLEMATIS STREET, 1ST FLOOR
 WEST PALM BEACH, FL 33401
 561-248-2703
 [email protected]
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-08-13 Cont ID  
Sent By shill Date 2019-08-13 Time 16:39 Rev Time 0.00
Received By shill Date 2019-08-02 Time 14:53 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-07-24 Cont ID  
Sent By lmarchan Date 2019-07-24 Time 16:46 Rev Time 0.00
Received By lmarchan Date 2019-06-24 Time 16:20 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2019-06-04 Time   Rev Time 0.00
Received By lmarchan Date 2019-05-08 Time 10:01 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2019-06-04 Cont ID  
Sent By jwitmer Date 2019-06-04 Time 14:29 Rev Time 0.00
Received By jwitmer Date 2019-06-04 Time 10:35 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2019-08-13 Cont ID  
Sent By pvalenti Date 2019-08-13 Time 09:01 Rev Time 0.00
Received By ccole Date 2019-08-13 Time 09:01 Sent To  
Notes
2019-08-13 09:02:463RD MECHANICAL REVIEW
 APPROVED BY CHRIS COLE (REMOTELY)

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2019-07-16 Cont ID  
Sent By ccole Date 2019-07-16 Time 10:51 Rev Time 0.00
Received By ccole Date 2019-07-16 Time 09:43 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-05-21 Cont ID  
Sent By ccole Date 2019-05-21 Time 15:55 Rev Time 0.00
Received By ccole Date 2019-05-21 Time 15:37 Sent To  
Notes
2019-05-21 16:19:011ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19050305
 5/21/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SEPARATE PERMITS ARE REQUIRED FOR THE KITCHEN HOOD
 AND FIRE SUPPRESSION SYSTEM- SECTION 107.2.1 WPB. THE
 REQUIRED ENGINEERING FOR INSTALLATION OF THE ROOTOP
 GREASE EXHAUST FAN, MUA, AND DUCTS MAY BE PROVIDED WITH
 THE PLANS AND PERMIT FOR THE HOOD.
  
 2) PROVIDE AN AIR BALANCE CALCULATION IN COMPLIANCE
 WITH SECTION 508.1.2 FBC M.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2019-08-13 Cont ID  
Sent By jesmith Date 2019-08-13 Time 15:18 Rev Time 0.00
Received By jesmith Date 2019-08-13 Time 14:08 Sent To  
Notes
2019-08-13 15:18:30PLUMBING COMMEMTS: APPROVED
 1. SEE RED-LINED PLUMBING COMMENTS/PROVISOS ON P3.01
 AND P3.03
 2. ALL WORK PER CITY CODES SUBJECT TO FIELD INSPECTOR?S
 APPROVAL

Review Stop P PLUMBING
Rev No 2 Status F Date 2019-07-09 Cont ID  
Sent By jesmith Date 2019-07-09 Time 12:42 Rev Time 0.00
Received By jesmith Date 2019-07-09 Time 07:57 Sent To  
Notes
2019-07-09 12:42:40CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 NFPA 30A
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
  
 2ND REVIEW
 PLUMBING COMMEMTS: DENIED
  
 SECOND REQUEST:
 1. NOT REQUIRED THE COFFEE AND CASHWRAP (BACKWRAP) SINK
 ARE NOT SHOWN AS ACCESSIBLE AND ARE BOTH LIST AS SNK-2
 (HS-2). PROVIDE CLEAR FLOOR SPACE AND COUNTER TOP
 DETAIL FOR BOTH SINKS, SHOWING MAX 34". FBC-ACC 606.2,
 606.3.
 NOTE THAT CLEAR FLOOR SPACE HAS BEEN PROVIDED FOR BOTH
 FIXTURES, BUT DETAIL 7/A9.5 EXCEEDS THE MAXIMUM 34?
 HEIGHT REQUIREMENTS FOR THE BACKWRAP SINK.
  
 2. NOT REQUIRED THE TWO COMPARTMENT SINK LOCATED IN THE
 CLASS ROOM KITCHEN SHALL BE ACCESSIBLE AS IT WOULD BE A
 COMMON USE SINK. PROVIDE CLEAR FLOOR SPACE AND MAX
 HEIGHT DETAIL MAX 34". FBC-ACC 606.2, 606.3
  
 3. THE INTERCEPTOR SHOWN AND NOTED ON PLAN SHEET P1.01
 HAS A CAPACITY THAT EXCEEDS THE MAXIMUM SIZE OF A
 CONCRETE GRAVITY TANK WHICH WOULD BE CONSTRUCTED IN
 ACCORDANCE WITH FAC 64E-6 (SEE CITY OF WPB PUBLIC
 UTILITIES DEPT. STD DETAIL GS-7), SO IT SHOULD BE A
 HYDRO MECHANICAL INTERCEPTOR AND BE SIZED AND
 CONSTRUCTED IN ACCORDANCE WITH PDI G101 (SEE CITY OF
 WPB PUBLIC UTILITIES DEPT. STD DETAIL GS-7.1). PROVIDE
 SPECS FOR EXISTING 2,025 GALLON INTERCEPTOR AND
 CALCULATIONS IN ACCORDANCE WITH THE APPLICABLE
 STANDARD, NOTING THE EXISTING LOAD UPSTREAM OF THE NEW
 WORK AND CALCULATIONS FOR THE NEW WORK. WPB FBC 107.3.5
  
  
 NEW COMMENTS
 1. RE: PLAN SHEET P3.01, DETAIL 1; A SEPARATE BACKFLOW
 PREVENTER IS REQUIRED FOR THE COLD WATER TO THE
 BUILDING FIXTURES AND FOR THE COLD WATER TO THE WATER
 SOFTENER PER FBC PL 608.3.
 2. RE: PLAN SHEET P3.01, DETAIL 7; RUNNING TRAP IS NOT
 ACCEPTABLE PER FBC PL 1002.1.
 A. VENT SHALL RISE VERTICALLY TO MINIMUM 6? ABOVE FLOOD
 LEVEL RIM OF TRAPPED FIXTURE BEFORE OFFSETTING
 HORIZONTALLY PER FBC PL 905.4.
 B. AIR GAP SHALL BE MINIMUM TWICE THE DIAMETER OF THE
 DRAIN PIPE PER FBC PL 802.2.1
 C. FLOOR SINK SHALL BE PROVIDED WITH A WATER SEAL TRAP
 PER FBC PL 802.2
 3. PER WPB FBC 107.2.1, PROVIDE DETAIL FOR DETAIL FOR
 TWO COMPARTMENT SINK SHOWING INDIRECT WASTE DISCHARGING
 SEPARATELY FROM EACH COMPARTMENT TO FLOOR SINK THROUGH
 AN AIR GAP IN ACCORDANCE WITH FBC PL 802.1.1.
 4. PER WPB FBC 107.2.1, PLEASE ADVISE AS TO THE PURPOSE
 OF THE FLOOR SINK LOCATED IN THE FLOOR SPACE BETWEEN
 THE MOP SINK AND THE DISHWASHER.
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  
 19050305 700 S ROSEMARY AVE # 116
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-05-16 Cont ID  
Sent By thunt Date 2019-05-16 Time 14:45 Rev Time 0.00
Received By thunt Date 2019-05-16 Time 10:15 Sent To  
Notes
2019-05-16 14:46:31 
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
  
 1) THE COFFEE AND CASHWRAP SINK ARE NOT SHOWN AS
 ACCESSIBLE AND ARE BOTH LIST AS SNK-2. PROVIDE CLEAR
 FLOOR SPACE AND COUNTER TOP DETAIL SHOWING MAX 34".
 FBC-ACC 606.2, 606.3
  
 2) THE 2 COMPARTMENT SINK LOCATED IN THE CLASS ROOM
 KITCHEN SHALL BE ACCESSIBLE AS IT WOULD BE A COMMON USE
 SINK. PROVIDE CLEAR FLOOR SPACE AND MAX HEIGHT DETAIL
 MAX 34". FBC-ACC 606.2, 606.3
  
 3) WATER HEATER DETAIL IS MISSING THE ANTISIPHON VALVE
 REQUIRED FOR BOTTOM FEED WATER HEATERS. FBC P 504.1
  
 4) PROVIDE HOW YOU SIZED THE INTERCEPTOR EITHER BY FAC
 64E-6 OR BY THE PDI G101? FBC P1003.1. AND WHAT
 MANUFACTURE AND MODEL YOU ARE CALLING FOR. FBC 107.3.5
  
 5) PROVIDE LOCATION ON PLAN OF WHERE GREASE INTERCEPTOR
 IS TO BE INSTALLED. FBC P 1003.2
  
 6) PROVIDE NOTE ON PLAN THAT BACKFLOW'S AND GREASE
 INTERCEPTOR REQUIRED A SEPARATE PERMIT. WPB AMEND 105.1
  
 7) PROVIDE INSTALLATION MANUAL/ SPECIFICATION SHEETS
 FOR THE SOFTENER SYSTEM AND GREASE INTERCEPTOR. FBC
 107.2.1
  
  
  
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR
 BUILDING DIVISION
 CITY OF WEST PALM BEACH
 401 CLEMATIS STREET, 1ST FLOOR
 WEST PALM BEACH, FL 33401
 561-248-2703
 [email protected]
 [email protected]
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2019-08-13 Cont ID  
Sent By shill Date 2019-08-13 Time 16:39 Rev Time 0.00
Received By shill Date 2019-08-13 Time 16:39 Sent To  
Notes
2019-08-08 10:41:33ELECTRICAL SHEETS OK.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2019-07-18 Cont ID  
Sent By jpearson Date 2019-07-18 Time 11:21 Rev Time 0.00
Received By jpearson Date 2019-07-18 Time 11:21 Sent To  
Notes
2019-07-18 17:57:34ARCH SHEETS OK (SIGNED BY ADOBESIGN OK PER FL BOARD OF
 ARCHITECTS
  
2019-07-18 11:21:05ELECTRICAL SHEETS: PER THE WPB AMENDMENTS TO THE FBC,
 EACH SHEET OF PLAN IS REQUIRED TO BE SIGNED AND SEALED
 BY THE PERSON RESPONSIBLE FOR THE DESIGN. A DIGITAL
 PLAN REQUIRES A DIGITAL SIGNATURE WITH THE PROPER THIRD
 PARTY VERIFICATION. SELF-CERTIFICATION IS NOT
 ACCEPTABLE FOR ENGINEERS. ADDITIONALLY, THE DIGITAL
 SIGNATURE MUST INCLUDE THE STATEMENT "SIGNED AND
 SEALED" AS PER FAC 61G15-23.004. ONLY THE SHEETS FROM
 THIS SUBMISSION ARE CORRECT, THE OTHER SHEETS HAVE NOT
 BEEN REPLACED. PROVIDE CORRECTION. WPB FBC 107.1; FS
 471/481
  
2019-07-17 11:09:382ND ARCHITECTURAL SIGNATURE TO BE COMPLETED BY S. HILL.
 J. WITMER 7/17/2019
2019-07-09 13:24:34PLUMBING/GAS DRAWINGS DIGITAL SIGNATURE IS NOT ISSUED
 IN A MANNER WHICH IS ACCEPTABLE TO EITHER FBPE OR
 FLORIDA BOARD OF PROFESSIONAL ENGINEERS. THIS TYPE OF
 SELF CERTIFICATION IS NOT INTENDED TO BE USED FOR
 PROFESSIONAL PURPOSES.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2019-05-16 Cont ID  
Sent By thunt Date 2019-05-16 Time 11:39 Rev Time 0.00
Received By thunt Date 2019-05-16 Time 11:39 Sent To  
Notes
2019-05-16 11:38:56MEP'S AND STRUCTURAL PLANS OK . NONE OF THE
 ARCHITECTURAL ARE DIGITALLY SIGNED AS REQUIRED BY F.A.C
 61G1-16.005.
  
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR
 BUILDING DIVISION
 CITY OF WEST PALM BEACH
 401 CLEMATIS STREET, 1ST FLOOR
 WEST PALM BEACH, FL 33401
 561-248-2703
 [email protected]
 [email protected]
  
  

Review Stop Z ZONING
Rev No 3 Status P Date 2019-08-06 Cont ID  
Sent By eschneid Date 2019-08-06 Time 13:48 Rev Time 0.25
Received By eschneid Date 2019-08-06 Time 13:15 Sent To  
Notes
2019-08-06 13:15:31IF ROOFTOP EQUIPMENT IS VISIBLE AFTER INSTALL,
 SCREENING WILL BE REQUIRED PRIOR TO FINAL 104
 INSPECTION.

Review Stop Z ZONING
Rev No 2 Status P Date 2019-07-24 Cont ID  
Sent By eschneid Date 2019-07-24 Time 16:42 Rev Time 0.50
Received By eschneid Date 2019-07-24 Time 16:07 Sent To  
Notes
2019-07-24 16:43:21IF ROOFTOP EQUIPMENT IS VISIBLE AFTER INSTALL,
 SCREENING WILL BE REQUIRED PRIOR TO FINAL 104
 INSPECTION.

Review Stop Z ZONING
Rev No 1 Status F Date 2019-05-24 Cont ID  
Sent By eschneid Date 2019-05-24 Time 11:09 Rev Time 1.00
Received By eschneid Date 2019-05-24 Time 08:33 Sent To  
Notes
2019-05-24 11:11:29FAILED
  
 1) THERE IS NEW ROOFTOP EQUIPMENT PROPOSED AS PART OF
 THIS INTERIOR BUILD OUT. IN ACCORDANCE WITH THE
 CITYPLACE DRI, PLEASE PROVIDE VERIFICATION THAT ALL
 ROOFTOP MECHANICAL EQUIPMENT, INCLUDING BUT NOT LIMITED
 TO SUCH ITEMS AS PUBLIC AND PRIVATE UTILITY SERVICE
 CONNECTIONS; HEATING, VENTILATING, AND AIR CONDITIONING
 SYSTEMS; COMMUNICATIONS DEVICES; AND RELATED EQUIPMENT,
 SHALL BE SCREENED FROM PUBLIC VIEW THROUGH ANY
 COMBINATION OF LANDSCAPING, WALLS AND EQUIPMENT
 LOCATION. PLEASE PROVIDE PLANS OR OTHER EVIDENCE THAT
 THE NEW ROOFTOP MECHANICAL EQUIPMENT WILL BE SCREENED
 FROM PUBLIC VIEW.
  
 2) THE EXTERIOR SIGNAGE REQUIRES SEPARATE PERMIT WITH
 PLANS.
  
 3) OTHER THAN THE INFORMATION REQUIRED BY COMMENT NO.
 1, THE PLANS COMPLY WITH ZONING REQUIREMENTS.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
 [email protected]
  