Plan Review Details - Permit 19050248
Plan Review Stops For Permit 19050248
Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-05-23 Cont ID  
Sent By cthroop Date 2019-05-23 Time 16:43 Rev Time 0.00
Received By cthroop Date 2019-05-16 Time 09:31 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-05-14 Cont ID  
Sent By cthroop Date 2019-05-14 Time 16:32 Rev Time 0.00
Received By cthroop Date 2019-05-14 Time 14:13 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-05-06 Cont ID  
Sent By cthroop Date 2019-05-06 Time 13:10 Rev Time 0.00
Received By cthroop Date 2019-05-06 Time 12:12 Sent To  
Notes
***NONE***

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 3 Status P Date 2019-05-23 Cont ID  
Sent By cthroop Date 2019-05-23 Time 16:43 Rev Time 0.00
Received By cthroop Date 2019-05-17 Time 11:39 Sent To  
Notes
2019-05-17 11:56:42ON CT'S DESK.
 PENDING REVIEW WITH ROBERT BROWN, CBO, HERE ARE THE
 POTENTIAL ISSUES WITH THE ENGINEERED FLOOD VENT
 SUBMITTED FOR REVIEW; CRAWL SPACE DOOR SYSTEMS FLOOD
 VENTS MODEL 816CS.
 1. ORIGINAL SIGNATURE AND SEAL OF DESIGN PROFESSIONAL.
 2. DESIGN CALCULATIONS. AVAILABLE FROM CRAWL SPACE DOOR
 SYSTEMS ([email protected])
 3. STATEMENT OF IMPACT RATING.
 4. DESIGN PRESSURE LIMITATIONS.
 5. QUALITY ASSURANCE TESTING.
 6. PERFORMANCE STANDARDS USED IN EVALUATION. (ASTM,
 ASCE, TAS)
 7. FLORIDA CODE COMPLIANCE.
 8. REFERENCE DATA (TESTING)
 9. INSTALLATION INSTRUCTIONS.
 10. DESIGN PRESSURES.
 11. DESCREPENCY BETWEEN FINISH FLOOR ELEVATION OF
 GARAGE(FF ELEV. -2.0 FEET) ON PLANS AND EC (4.20 FEET
 NAV88).
 12. SECTION A9 (C) NET AREA OF OPENINGS - SURVEYOR TO
 STATE TOTAL SQ/INCHES AND PROVIDE COMMENT IN SECTION D
 OF EC.
 13. SECTION A9 (D) ENGINEERED OPENINGS? SELECT BOTH YES
 AND NO AND PROVIDE CLARIFICATION COMMENT IN SECTION D
 OF EC.
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 2 Status F Date 2019-05-14 Cont ID  
Sent By cthroop Date 2019-05-14 Time 16:27 Rev Time 0.00
Received By cthroop Date 2019-05-14 Time 14:13 Sent To  
Notes
2019-05-14 16:32:22NFIP REVIEW - ELEVATION CERTIFICATE
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 2ND REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE A REVISION TO PLAN PAGE A-1.0 UNDER PERMIT
 #17100298. SHOW SIZE AND PLACEMENT OF REQUIRED FLOOD
 VENTS.
  
 2. PROVIDE A PROPERLY COMPLETED ELEVATION CERTIFICATE.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 1 Status F Date 2019-05-06 Cont ID  
Sent By cthroop Date 2019-05-06 Time 13:10 Rev Time 0.00
Received By cthroop Date 2019-05-06 Time 12:12 Sent To  
Notes
2019-05-06 14:03:09ELEVATION CERTIFICATE REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. REFERENCE SECTION A6 OF ELEVATION CERTIFICATE (EC)
 AND ITEM A6 (PAGE 1 OF 9) OF THE INSTRUCTIONS FOR
 COMPLETING THE ELEVATION CERTIFICATE.
 ADDITIONAL PICTURES ARE REQUIRED BASED ON THE
 INSTALATION OF FLOOD OPENINGS AND STRUCTURE IS
 MULTI-STORY.
  
 2. REFERENCE SECTION A9 (A), (B) & (C) OF THE ELEVATION
 CERTIFICATE.
 A9 (A) STATES SQUARE FOOTAGE OF GARAGE IS 512 SQ/FT.
 APPROVED GROUND FLOOR PLAN STATES SQUARE FOOTAGE OF
 GARAGE IS 462 SQ/FT. PLEASE CLARIFY.
 A9 (B) STATES NUMBER OF PERMANENT FLOOD OPENINGS
 INSTALLED ABOVE ADJACENT GRADE IS 2. APPROVED GROUND
 FLOOR PLAN INDICTES 4 NON-ENGINEERED FLOOD OPENINGS
 SHALL BE INSTALLED ABOVE GARAGE FINISH FLOOR WITH A NET
 OPENING OF 128 SQ/INCHES FOR A TOTAL OF 512 SQ/INCHES.
 IF THE INTERIOR GRADE ELEVATION IS USED, NOTE THIS IN
 THE COMMENTS AREA OF SECTION D. PLEASE CLARIFY.
 A9(C) STATES NET AREA OF FLOOD OPENINGS IN A9 (B) IS
 512 SQ/INCHES. APPROVED GROUND FLOOR PLAN STATES 4
 OPENINGS WILL PROVIDE 512 SQ/INCHES OF FLOOD OPENING.
 PLEASE CLARIFY.
  
 3. PROVIDE DETAIL OF THE NON-ENGINEERED FLOOD OPENINGS.
 4. PROVIDE PICTURES OF INSTALLED FLOOD VENTS.
 5. PROVIDE PICTURES OF MECHANICAL EQUIPMENT.
  
 ALL PHOTOS SHALL BE IN COLOR
  
  