Plan Review Details - Permit 19050171
Plan Review Stops For Permit 19050171
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-06-10 Cont ID  
Sent By pleduc Date 2019-06-10 Time   Rev Time 0.00
Received By pleduc Date 2019-06-10 Time 13:45 Sent To M
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2019-05-10 Cont ID  
Sent By pleduc Date 2019-05-10 Time   Rev Time 0.00
Received By pleduc Date 2019-05-10 Time 14:08 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-06-13 Cont ID  
Sent By hmoser Date 2019-06-13 Time 11:18 Rev Time 0.00
Received By hmoser Date 2019-06-06 Time 13:41 Sent To  
Notes
2019-06-07 13:41:25RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2019-05-29 Time   Rev Time 0.00
Received By lmarchan Date 2019-05-03 Time 16:27 Sent To  
Notes
2019-05-06 16:28:11ROUTED TO FIRE INBOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2019-06-13 Cont ID  
Sent By hmoser Date 2019-06-13 Time 11:17 Rev Time 0.00
Received By hmoser Date 2019-06-13 Time 10:29 Sent To I
Notes
2019-06-13 11:16:27PASS PROVISO
 1) SUBMIT MANUFACTURER'S SPECIFICATIONS AND
 INSTALLATION INSTRUCTIONS FOR OVEN AND DUCTWORK
 AT FIRST MECHANICAL INSPECTION. SECTION 304.1 FBC (M)
 2) LISTING ON OVEN SHALL BE UL2162 PER SECTION
 917 FBC (M)
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-05-29 Cont ID  
Sent By ccole Date 2019-05-29 Time 16:43 Rev Time 0.00
Received By ccole Date 2019-05-29 Time 16:17 Sent To I
Notes
2019-05-29 17:12:541ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19050171
 5/29/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE PIZZA OVEN SHALL BE UL 2162 LISTED AND LABELED-
 PROVIDE DOCUMENTATION INDICATING COMPLIANCE- SEE
 SECTIONS 917.1 AND 304.1 FBC M.
  
 2) THE GREASE EXHAUST DUCT SHALL BE UL 2221 LISTED AND
 LABELED BECAUSE IT IS PENETRATING A FLOOR/CEILING
 ASSEMBLY- SEE SECTIONS 506.3.121 AND 506.3.11.3 FBC M
 AND PROVIDE DOCUMENTATION INDICATING COMPLIANCE.
  
 3) INDICATE THE HEIGHT OF THE EXHAUST FAN DISCHAGE
 OUTLET ABOVE THE ROOF SURFACE- SECTION 506.3.13.1 FBC
 M.
  
 4) INDICATE HOW COMBUSTION AIR IS BEING PROVIDED TO THE
 PIZZA OVEN IN ACCORDANCE WITH SECTION 701.1 FBC M.
  
 5) A CLEANOUT IS REQUIRED WITHIN 10 FT. OF THE
 HORIZONTAL-TO-VERTICAL CHANGE IN DIRECTION- SECTION
 506.3.9 FBC M.
  
 6) SUBMIT MANUFACTURER'S SPECIFICATIONS AND
 INSTALLATION INSTRUCTIONS FOR THE OVEN AND DUCTWORK-
 SECTION 304.1 FBC M.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  