| 2019-06-19 14:18:34 | BUILDING REVIEW COMMENTS |
| | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| | |
| | |
| | 06/25/19 NEW COMMENT: |
| | THERE ARE SEVERAL BUILDINGS ON THIS PROPERTY. PERMIT |
| | APPLICATION IDENTIFIES THIS BUILDING AS 801 CHARLOTTE |
| | AVE. THIS ADDRESS IS INCORRECT. ODD NUMBERS SHOULD BE |
| | ON THE OTHER SIDE OF THE STREET. REVISE AS REQUIRED. |
| | PLEASE PROVIDE EXACT ADDRESS FOR BUILDING WHERE WORK IS |
| | TAKING PLACE. REVISE ADDRESS ON ALL DRAWINGS. ADDRESS |
| | WAS CHANGED TO 810 CHARLOTTE AVE IN OUR SYSTEM. PLEASE |
| | COORDINATE WITH US TO BEST IDENTIFY THE BUILDING WHERE |
| | WORK IS TAKING PLACE. . SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | |
| | NOTE: SEC. 801.3 FBC-EXISTING BUILDING. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1- ARCHITECT OF RECORD TO SIGN AND SEAL ALL |
| | PLANS/DOCUMENTS AS REQUIRED BY CHAPTER 481 F.S. WHEN |
| | SUBMITTING PLANS/DOCUMENTS FOR PUBLIC RECORDS. |
| | |
| | 2- MEN'S AND WOMEN'S RESTROOMS USED TO HAVE TOILET |
| | COMPARTMENTS WITH WATER CLOSET AND LAVATORY. PROPOSED |
| | RESTROOMS SEEM TO BE LESS ACCESSIBLE THAN WHAT IT WAS |
| | BEFORE. FIRST FLOOR WOMEN'S RESTROOM AND BOTH RESTROOMS |
| | ON THE SECOND FLOR DON'T HAVE THE TOILET COMPARTMENT |
| | WITH A LAVATORY. SHOW COMPLIANCE WITH SEC. 604.8.1.6 |
| | AND SEC. 604.8.1.7 FBC ACCESSIBILITY. NOTE: SEE ALSO, |
| | ADVISORY 604.8.1.6 AND 604.8.1.7 FBC-ACCESSIBILITY. |
| | |
| | 3-1ST FLOOR PLAN ON SHEET A-1.0: |
| | A)ENTRANCE TO THE SHOWER'S AREA IN THE MEN'S RESTROOM |
| | DOESN'T COMPLY WITH THE CLEAR WIDTH REQUIRED BY SEC. |
| | 403.5.1 FBC-ACCESSIBILITY. REVISE AS REQUIRED. PLAN |
| | SHOWS 2'6". REVISE AS REQUIRED. |
| | |
| | B)PROVIDE THE CLEAR DIMENSION TO ENTER THE MEN'S LOCKER |
| | AREA. SEC. 403.5.1 FBC-ACCESSIBILITY. |
| | |
| | C)THE DOORS ON THE FOYER AREA OF BOTH RESTROOMS DON'T |
| | COMPLY WITH THE DOORS IN SERIES DISTANCE REQUIRED BY |
| | SEC. 404.2.6 FBC-ACCESSIBILITY. REVISE AS REQUIRED. |
| | |
| | D) MEN'S SHAVING STATION. SHOW COMPLIANCE WITH COUNTER |
| | WORK SURFACE. SEC. 902 FBC-ACCESSIBILITY AND MIRROR |
| | SEC. 603.3 FBC-ACCESSIBILITY. |
| | |
| | E) WOMEN'S MAKE UP STATION. SHOW COMPLIANCE WITH |
| | COUNTER WORK SURFACE. SEC. 902 FBC-ACCESSIBILITY AND |
| | MIRROR SEC. 603.3 FBC-ACCESSIBILITY. |
| | |
| | F)HANDICAPPED BENCH IN THE MENS' RESTROOM: |
| | (1)DON'T SEEM TO PROVIDE PRIVACY. SEC. 803.1 |
| | FBC-ACCESSIBILITY. SEE ADVISORY FOR SEC. 803.1 |
| | FBC-ACCESSIBILITY. |
| | |
| | (2) THE HANDICAPPED BENCH CLEAR FLOOR SPACE REQUIRED BY |
| | SEC. 903.2 FBC-ACCESSIBILITY IS BLOCKING THE |
| | ACCESS/EGRESS FROM SHOWER AREA. |
| | |
| | (3)PROVIDE SPECS FOR BENCH AS REQUIRED BY SEC. 903.4 |
| | FBC-ACCESSIBILITY. SHOW COMPLIANCE WITH ALL THE |
| | REQUIREMENTS OF SEC. 903 FOR BENCHES. |
| | |
| | NOTE: CLARIFY WOMEN DON'T HAVE ANY SPECS FOR |
| | HANDICAPPED BENCH. SEC. 803.4 FBC-ACCESSIBILITY. |
| | |
| | G) MEN'S LOOKERS AREA DON'T HAVE TURNING SPACE. SEC. |
| | 803.2 FBC-ACCESSIBILITY |
| | |
| | H) THE MENS' RESTROOM ENTRY DOOR LOCATED BY THE URINALS |
| | AREA DON'T COMPLY WITH THE MANEUVERING CLEARANCE |
| | REQUIRED BY SEC. 404.2.4 FBC-ACCESSIBILITY ON THE PULL |
| | SIDE OF THE DOOR. NEED 18" MIN. REVISE AS REQUIRED. |
| | |
| | I)THERE IS A NOTE BY THE LOCKERS AREA STATING "SEE DTL. |
| | IN SHEET A.4.0" FOR THE LOCKER DETAILS. THERE IS NOT |
| | SHEET A-4.0. REVISE AS REQUIRED. SEC. 107.2.1 CITY |
| | AMENDMENTS. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | PLEASE, INSERT CORRECTED PAGES INTO THE SUBMITTAL AND |
| | REMOVE/VOID THE PREVIOUSLY REVIEWED SHEETS. PLEASE |
| | DON'T STAPLE OLD DRAWINGS/DOCUMENTS . SUBMIT OLD |
| | DRAWINGS/DOCUMENTS FOR REFERENCE. |
| | |