Plan Review Details - Permit 19050125
Plan Review Stops For Permit 19050125
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2019-09-20 Cont ID  
Sent By dbattles Date 2019-09-20 Time 15:05 Rev Time 0.00
Received By dbattles Date 2019-09-20 Time 15:05 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-09-06 Cont ID  
Sent By dbattles Date 2019-09-06 Time 10:38 Rev Time 0.00
Received By dbattles Date 2019-09-06 Time 10:38 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-06-19 Cont ID  
Sent By jgomez Date 2019-06-19 Time 16:58 Rev Time 0.00
Received By jgomez Date 2019-06-19 Time 10:37 Sent To  
Notes
2019-06-19 14:18:34BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
  
 06/25/19 NEW COMMENT:
 THERE ARE SEVERAL BUILDINGS ON THIS PROPERTY. PERMIT
 APPLICATION IDENTIFIES THIS BUILDING AS 801 CHARLOTTE
 AVE. THIS ADDRESS IS INCORRECT. ODD NUMBERS SHOULD BE
 ON THE OTHER SIDE OF THE STREET. REVISE AS REQUIRED.
 PLEASE PROVIDE EXACT ADDRESS FOR BUILDING WHERE WORK IS
 TAKING PLACE. REVISE ADDRESS ON ALL DRAWINGS. ADDRESS
 WAS CHANGED TO 810 CHARLOTTE AVE IN OUR SYSTEM. PLEASE
 COORDINATE WITH US TO BEST IDENTIFY THE BUILDING WHERE
 WORK IS TAKING PLACE. . SEC. 107.2.1 CITY AMENDMENTS.
  
  
 NOTE: SEC. 801.3 FBC-EXISTING BUILDING. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1- ARCHITECT OF RECORD TO SIGN AND SEAL ALL
 PLANS/DOCUMENTS AS REQUIRED BY CHAPTER 481 F.S. WHEN
 SUBMITTING PLANS/DOCUMENTS FOR PUBLIC RECORDS.
  
 2- MEN'S AND WOMEN'S RESTROOMS USED TO HAVE TOILET
 COMPARTMENTS WITH WATER CLOSET AND LAVATORY. PROPOSED
 RESTROOMS SEEM TO BE LESS ACCESSIBLE THAN WHAT IT WAS
 BEFORE. FIRST FLOOR WOMEN'S RESTROOM AND BOTH RESTROOMS
 ON THE SECOND FLOR DON'T HAVE THE TOILET COMPARTMENT
 WITH A LAVATORY. SHOW COMPLIANCE WITH SEC. 604.8.1.6
 AND SEC. 604.8.1.7 FBC ACCESSIBILITY. NOTE: SEE ALSO,
 ADVISORY 604.8.1.6 AND 604.8.1.7 FBC-ACCESSIBILITY.
  
 3-1ST FLOOR PLAN ON SHEET A-1.0:
 A)ENTRANCE TO THE SHOWER'S AREA IN THE MEN'S RESTROOM
 DOESN'T COMPLY WITH THE CLEAR WIDTH REQUIRED BY SEC.
 403.5.1 FBC-ACCESSIBILITY. REVISE AS REQUIRED. PLAN
 SHOWS 2'6". REVISE AS REQUIRED.
  
 B)PROVIDE THE CLEAR DIMENSION TO ENTER THE MEN'S LOCKER
 AREA. SEC. 403.5.1 FBC-ACCESSIBILITY.
  
 C)THE DOORS ON THE FOYER AREA OF BOTH RESTROOMS DON'T
 COMPLY WITH THE DOORS IN SERIES DISTANCE REQUIRED BY
 SEC. 404.2.6 FBC-ACCESSIBILITY. REVISE AS REQUIRED.
  
 D) MEN'S SHAVING STATION. SHOW COMPLIANCE WITH COUNTER
 WORK SURFACE. SEC. 902 FBC-ACCESSIBILITY AND MIRROR
 SEC. 603.3 FBC-ACCESSIBILITY.
  
 E) WOMEN'S MAKE UP STATION. SHOW COMPLIANCE WITH
 COUNTER WORK SURFACE. SEC. 902 FBC-ACCESSIBILITY AND
 MIRROR SEC. 603.3 FBC-ACCESSIBILITY.
  
 F)HANDICAPPED BENCH IN THE MENS' RESTROOM:
 (1)DON'T SEEM TO PROVIDE PRIVACY. SEC. 803.1
 FBC-ACCESSIBILITY. SEE ADVISORY FOR SEC. 803.1
 FBC-ACCESSIBILITY.
  
 (2) THE HANDICAPPED BENCH CLEAR FLOOR SPACE REQUIRED BY
 SEC. 903.2 FBC-ACCESSIBILITY IS BLOCKING THE
 ACCESS/EGRESS FROM SHOWER AREA.
  
 (3)PROVIDE SPECS FOR BENCH AS REQUIRED BY SEC. 903.4
 FBC-ACCESSIBILITY. SHOW COMPLIANCE WITH ALL THE
 REQUIREMENTS OF SEC. 903 FOR BENCHES.
  
 NOTE: CLARIFY WOMEN DON'T HAVE ANY SPECS FOR
 HANDICAPPED BENCH. SEC. 803.4 FBC-ACCESSIBILITY.
  
 G) MEN'S LOOKERS AREA DON'T HAVE TURNING SPACE. SEC.
 803.2 FBC-ACCESSIBILITY
  
 H) THE MENS' RESTROOM ENTRY DOOR LOCATED BY THE URINALS
 AREA DON'T COMPLY WITH THE MANEUVERING CLEARANCE
 REQUIRED BY SEC. 404.2.4 FBC-ACCESSIBILITY ON THE PULL
 SIDE OF THE DOOR. NEED 18" MIN. REVISE AS REQUIRED.
  
 I)THERE IS A NOTE BY THE LOCKERS AREA STATING "SEE DTL.
 IN SHEET A.4.0" FOR THE LOCKER DETAILS. THERE IS NOT
 SHEET A-4.0. REVISE AS REQUIRED. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE, INSERT CORRECTED PAGES INTO THE SUBMITTAL AND
 REMOVE/VOID THE PREVIOUSLY REVIEWED SHEETS. PLEASE
 DON'T STAPLE OLD DRAWINGS/DOCUMENTS . SUBMIT OLD
 DRAWINGS/DOCUMENTS FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-08-15 Cont ID  
Sent By jpearson Date 2019-08-15 Time 08:43 Rev Time 0.00
Received By jpearson Date 2019-08-15 Time 08:43 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2019-06-17 Cont ID  
Sent By jpearson Date 2019-06-17 Time 14:51 Rev Time 0.00
Received By jpearson Date 2019-06-17 Time 14:17 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-08-15 Cont ID  
Sent By pleduc Date 2019-08-15 Time   Rev Time 0.00
Received By pleduc Date 2019-08-15 Time 14:11 Sent To  
Notes
2019-08-15 14:12:08THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) SHEET LS 1.0 - THERE IS AN INDICATION OF A EXISTING
 FIRE SPRINKLER SYSTEM WITH REMOVAL OF WALLS AND
 RECONSTRUCTION.
  
 ANY REMOVAL OF WALLS, NEW WALLS OR A RECONSTRUCTION OF
 AREAS REQUIRES A REVIEW OF THE FIRE SPRINKLER
 PROTECTION.
  
 ANY AND ALL WORK ON THE FIRE SPRINKLER SYSTEM SHALL BE
 DONE UNDER SEPARATE SHOP DRAWINGS AND BY CERTIFIED FIRE
 SPRINKLER CONTRACTORS.
  
 PLEASE ENSURE COMPLIANCE.
  
 PETER LEDUC
 FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2019-05-13 Cont ID  
Sent By pleduc Date 2019-05-13 Time   Rev Time 0.00
Received By pleduc Date 2019-05-13 Time 12:06 Sent To  
Notes
2019-05-13 12:09:08THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) SHEET LS 1.0 - THERE IS AN INDICATION OF A EXISTING
 FIRE SPRINKLER SYSTEM WITH REMOVAL OF WALLS AND
 RECONSTRUCTION.
  
 ANY REMOVAL OF WALLS, NEW WALLS OR A RECONSTRUCTION OF
 AREAS REQUIRES A REVIEW OF THE FIRE SPRINKLER
 PROTECTION.
  
 ANY AND ALL WORK ON THE FIRE SPRINKLER SYSTEM SHALL BE
 DONE UNDER SEPARATE SHOP DRAWINGS AND BY CERTIFIED FIRE
 SPRINKLER CONTRACTORS.
  
 PLEASE ENSURE COMPLIANCE.
  
 PETER LEDUC
 FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-09-23 Cont ID  
Sent By tklarge Date 2019-09-23 Time 11:02 Rev Time 0.00
Received By tklarge Date 2019-09-17 Time 14:07 Sent To  
Notes
2019-09-18 14:08:02RESUB ROUTED TO JESMITH

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-09-06 Cont ID  
Sent By dbattles Date 2019-09-06 Time 10:38 Rev Time 0.00
Received By dbattles Date 2019-08-13 Time 14:49 Sent To  
Notes
2019-08-14 14:49:16C11

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-06-19 Cont ID  
Sent By jgomez Date 2019-06-19 Time 17:12 Rev Time 0.00
Received By jgomez Date 2019-05-02 Time 16:10 Sent To I
Notes
2019-05-02 16:10:24C14

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2019-06-19 Cont ID  
Sent By jgomez Date 2019-06-19 Time 17:12 Rev Time 0.00
Received By jgomez Date 2019-06-19 Time 17:12 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2019-08-27 Cont ID  
Sent By rmcdouga Date 2019-08-27 Time 11:43 Rev Time 0.00
Received By rmcdouga Date 2019-08-27 Time 11:43 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2019-07-16 Cont ID  
Sent By ccole Date 2019-07-16 Time 07:29 Rev Time 0.00
Received By ccole Date 2019-07-16 Time 07:28 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-06-06 Cont ID  
Sent By ccole Date 2019-06-06 Time 13:20 Rev Time 0.00
Received By ccole Date 2019-06-06 Time 12:16 Sent To  
Notes
2019-06-06 13:25:371ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19050125
 6/6/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 COMMENT IN PROGRESS- DO NOT EMAIL OR PRINT
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 BUILDING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2019-09-23 Cont ID  
Sent By tklarge Date 2019-09-23 Time 11:02 Rev Time 0.00
Received By tklarge Date 2019-09-23 Time 06:30 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2019-08-27 Cont ID  
Sent By jesmith Date 2019-08-27 Time 11:04 Rev Time 0.00
Received By jesmith Date 2019-08-27 Time 11:03 Sent To  
Notes
2019-08-27 11:04:23CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 NFPA 54 = NATIONAL FUEL GAS CODE
 NFPA 58 = LIQUIFIED PETROLEUM GAS CODE
 NFPA 96 = STANDARD FOR VENTILATION CONTROLAND FIRE
 PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017
 NFPA 99 = HEALTH CARE FACILITIES CODE
 NFPA 99B = STANDARD FOR HYPERBARIC FACILITIES
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
  
 2ND REVIEW
 PLUMBING COMMEMTS: DENIED
  
 1. REGARDING THE SECOND FLOOR WOMEN?S RESTROOM; PER FBC
 PL 905.3 AND 904.5.4, VERY DRY VENT CONNECTING TO A
 HORIZONTAL DRAIN SHALL CONNECT ABOVE THE CENTERLINE OF
 THE HORIZONTAL DRAIN PIPE AND SHALL RISE VERTICALLY TO
 A POINT NOT LESS THAN 6 INCHES (152 MM) ABOVE THE FLOOD
 LEVEL RIM OF THE HIGHEST TRAP OR TRAPPED FIXTURE BEING
 VENTED. THE DRY VENT IN THIS SITUATION IS OFFSETTING
 HORIZONTALLY BELOW THE FLOOR AS OPPOSED TO RISING
 VERTICALLY TO THE POINT OF 6? ABOVE THE FLOOD LEVEL RIM
 OF THE HIGHEST FIXTURE BEING SERVED. PER WPB FBC
 107.2.1, CORRECT ON BOTH P1.0 AND P2.0.
  
 2. REGARDING THE FIRST FLOOR MEN?S RESTROOM; PER FBC PL
 905.3 AND 904.5.4, EVERY DRY VENT CONNECTING TO A
 HORIZONTAL DRAIN SHALL CONNECT ABOVE THE CENTERLINE OF
 THE HORIZONTAL DRAIN PIPE AND SHALL RISE VERTICALLY TO
 A POINT NOT LESS THAN 6 INCHES (152 MM) ABOVE THE FLOOD
 LEVEL RIM OF THE HIGHEST TRAP OR TRAPPED FIXTURE BEING
 VENTED. THE DRY VENT IN THIS SITUATION IS A CIRCUIT
 VENT FOR THE THREE WATER CLOSETS ON THE VENTED BRANCH
 WHICH EXTENDS HORIZONTALLY BELOW THE FLOOR TO THE
 NEAREST WALL BEFORE RISING VERTICALLY AS OPPOSED TO
 CONNECTING ABOVE THE CENTERLINE OF THE DRAIN, RISING
 VERTICALLY TO THE POINT OF 6? ABOVE THE FLOOD LEVEL RIM
 OF THE HIGHEST FIXTURE BEING SERVED. PER WPB FBC
 107.2.1, CORRECT ON BOTH P1.0 AND P2.0.
  
 3. PER FBC ACC 604.7, TOILET PAPER DISPENSERS SHALL
 COMPLY WITH 309.4 AND SHALL BE 7 INCHES (180 MM)
 MINIMUM AND 9 INCHES (230 MM) MAXIMUM IN FRONT OF THE
 WATER CLOSET MEASURED TO THE CENTERLINE OF THE
 DISPENSER. SEE RED LINED PROVISO ON PLAN SHEET
 A-2.0/DETAIL 15.
  
 4. PER FBC ACC 604.2, THE WATER CLOSET SHALL BE
 POSITIONED WITH A WALL OR PARTITION TO THE REAR AND TO
 ONE SIDE. THE CENTERLINE OF THE WATER CLOSET SHALL BE
 16 INCHES (405 MM) MINIMUM TO 18 INCHES (455 MM)
 MAXIMUM FROM THE SIDE WALL OR PARTITION. SEE RED LINED
 PROVISO ON PLAN SHEET A-2.0/DETAIL 5.
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  
 19050125 810 CHARLOTTE AVE
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-06-04 Cont ID  
Sent By thunt Date 2019-06-04 Time 16:07 Rev Time 0.00
Received By thunt Date 2019-06-04 Time 13:15 Sent To  
Notes
2019-06-04 16:09:26PLUMBING 1ST REVIEW**DENIED**
  
 1-ALL SHEETS SHALL BE SIGNED BY DESIGN PROFESSIONAL.
 ONLY THE MEP?S ARE SIGNED AND SEALED. F.S 471, 481
  
 2- WHERE THE DEVELOPED LENGTH OF THE HOT WATER SYSTEM
 IS OVER 50? A RECIRCULATING SYSTEM SHALL INSTALLED INTO
 THE SYSTEM. FBC-P 607.2
  
 3- PROVIDE LOCATION AND ACCESS FOR TRAP PRIMER DEVICES.
 IT APPEARS THAT THE TRAP PRIMER DEVICE WILL BE IN THE
 WALL BETWEEN THE 2 SHOWERS AND NOT SERVICEABLE. FBC
 107.2.1
  
 4-ALL THE TOILET LESS THE 1ST FLOOR MEN?S ARE DRY
 VENTED ON BOTH FLAT AND ISOMETRIC DRAWING. FBC-P 912.2
  
 5- SHT. P1.0 AND A2.0 SHOW THE ACCESSIBLE SHOWER VALVES
 LOCATED ON THE INCORRECT WALL. FBC-ACC 608.5
  
 6- PROVIDE MEASUREMENT FOR MIRRORS BEING MAX 40? FROM
 THE REFLECTIVE SURFACE. FBC-ACC 603.3
  
 7-ADD NOTE THAT ALL HAND SINKS SHALL BE TEMPERED TO MAX
 110F BY AN APPROVED ASSE 1070 DEVICE. FBC-P 607.1.2
  
 8- SHOW DETAIL SIDE GRAB BAR AS 54? OVERALL AND REAR
 GRAB BAR AS 36? OVERALL AND MOUNT 12? FROM CENTER OF
 TOILET TOWARDS THE SIDE WALL. FBC-ACC 604.5
  
 9- 1ST FLOOR FEMALE AND 2ND FLOOR MEN?S AND WOMEN?S
 RESTROOM?S ARE MISSING THE LAVATORY IN THE TOILET
 COMPARTMENT. WHERE A TOILET ROOM / COMPARTMENT IS
 PROVIDED IT SHALL COMPLY WITH FBC-ACC 213** (CORRECTED
 FROM 231 ON 6/25/19), 604.8.1.6
  
 10- SHT A2.09 DETAIL # 3, 15, 17 SHT A2.1 DETAIL 26 AND
 28 SHOW THE HEIGHT OF THE LAVATORIES TO BE 48?. MAX
 PERMITTED IS 34? FBC-ACC 606.3 AND AS YOU CALL YOU ON
 SHT. A3.0. PLEASE CORRECT OR CLARIFY.
  
 11- ADD NOTE ALL HOT WATER PIPING AND RETURN PIPING
 SHALL BE INSULATED PER TABLE C404.6 OF THE FBC-ENERGY
 CODE. FBC-P 607.2.1, 607.5
  
 12- THE 2ND FLOOR MEN?S RESTROOM SHOWS 2 URINALS. ONE
 SHALL BE ACCESSIBLE. PROVIDE CLEAR FLOOR SPACE ON SHT.
 A-1.1. FBC-ACC 213, 605.3
  
  
 TIM HUNT
 PLUMBING INSPECTOR/ PLUMBING PLANS EXAMINER
 BUILDING DIVISION
 CITY OF WEST PALM BEACH
 561-248-2703
 [email protected]
 [email protected]
  
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2019-09-06 Cont ID  
Sent By dbattles Date 2019-09-06 Time 10:38 Rev Time 0.00
Received By dbattles Date 2019-09-06 Time 10:14 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2019-06-19 Cont ID  
Sent By jgomez Date 2019-06-19 Time 17:12 Rev Time 0.00
Received By jgomez Date 2019-06-19 Time 17:11 Sent To  
Notes
2019-06-19 17:12:43ARCHITECTURAL PLANS NEED TO BE SIGNED AND SEALED.
 CHAPTER 481 F.S.
2019-06-04 16:10:38ONLY THE MEP'S ARE SIGNED AND SEALED. ALL SHEETS SHALL
 BE SIGNED F.S 471, 481

Review Stop Z ZONING
Rev No 1 Status N Date 2019-06-19 Cont ID  
Sent By hdanfort Date 2019-06-19 Time 17:08 Rev Time 0.00
Received By jgomez Date 2019-06-19 Time 17:08 Sent To  
Notes
2019-06-19 17:11:26TALKED TO ANGELLA JONES-VANN.
 INTERIOR BATHROOM RENOVATIONS ONLY. JG.