Plan Review Details - Permit 19050124
Plan Review Stops For Permit 19050124
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2019-11-26 Cont ID  
Sent By jwitmer Date 2019-11-26 Time 05:44 Rev Time 0.00
Received By jwitmer Date 2019-11-25 Time 10:09 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-08-26 Cont ID  
Sent By jwitmer Date 2019-08-26 Time 08:12 Rev Time 0.00
Received By jwitmer Date 2019-08-26 Time   Sent To  
Notes
2019-08-26 08:12:222017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19050124
 ADD: 2201 45TH STREET JFK NORTH
 CONT: DPR CONSTRUCTION
 TEL: 954-991-6200
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: MON. AUGUST 26, 2019
 ACTION: DENIED
  
 ********************************4X FEE / NOTICE!!!!!
 FLORIDA STATUTE 553.80(2)(B)
 **************************************************
 WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS?
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW.
  
 1) 2ND REQUEST. THE SUBMITTED PLANS MODULAR STRUCTURES
 FOR WILLIAM SCOTSMAN FOR A 36 FT. X 56 FT. MODULAR UNIT
 DOES NOT SHOW A 3RD PARTY REVIEW. GENERAL NOTE 20
 STATES THE RAISED SEAL SET OF PLANS ARE ON FILE IN THE
 THIRD PARTY AGENCY'S OFFICE AS DIRECTED BY DCA.
 IN THE DBPR WEBSITE FOR MANUFACTURED BUILDINGS THERE IS
 PLANS FOR WILLIAM SCOTSMAN AS THE MANUFACTURER (THERE
 ARE DIFFERENT QUALIFIERS, SPECIFY WHICH QUALIFIER) AND
 MODULAR PLANS DESIGN, CO. AS THE APPROVING AGENCY.
 PLEASE PROVIDE THE AGENCY PLAN APPROVAL NUMBER.
  
 IF THERE IS NO 3RD PARTY APPROVAL FOR THESE PLANS, THEY
 THEN ARE NOT APPROVED BY THE STATE AND WILL NEED TO BE
 UPDATED TO THE 2017 FBC-B AND EACH PAGE WILL NEED TO BE
 SIGNED AND SEALED ELECTRONICALLY.
 THE STATE PLAN ARE STILL AVAILABLE ON LINE AND CAN BE
 REVIEWED WHEN CONTACTING THE AGENCY.
 THE COVERSHEET LIST THOMAS L. MELTON AS THE CONSULTING
 ARCHITECT. PLEASE SHOW COMPLIANCE WITH THE FLORIDA
 ADMINISTRATIVE CODE. ARCHITECT DIGITAL SIGNING &
 SEALING PLANS. 61G1-16.005 PROCEDURES FOR DIGITALLY
 SIGNING AND SEALING AND FOR ELECTRONICALLY TRANSMITTING
 PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
 2) 2ND REQUEST. THE COVERSHEET STATES THIS BUILDING IS
 NOT TO BE PLACED IN A FLOOD ZONE. THE SITE PLAN SHOWS
 WHERE THE PROPOSED BUILDING IS TO BE PLACED IS IN AN AE
 FLOOD ZONE WITH A BFE OF 12.00 FT. NAVD88. PLEASE SHOW
 HOW COMPLIANCE WITH THE BOTTOM OF THE MANUFACTURED
 BUILDING WILL BE ABOVE THE BASE FLOOD PLUS THE
 ADDITIONAL 2 FEET REQUIRED BY THE CITY OF WEST PALM
 BEACH MUNI CODE SECTION ARTICLE XVII ORDINANCES ARTICLE
 XVII FLOOD PREVENTION & CONTROL.
  
 DURING THE PERMITTING OF THIS STRUCTURE THERE WILL BE
 REQUIRED (3) DIFFERENT FLOOD ZONE CERTIFICATES
 REQUIRED:
 (1) A FLOOD ZONE CERTIFICATE IS REQUIRED AS PART OF THE
 PLAN REVIEW DOCUMENTS WITH THE PROPOSED FINISH FLOOR
 HEIGHT. W. P. B. ADMINISTRATIVE CODE 107.3.5.1.1
 BUILDING MINIMUM PLAN REVIEW CRITERIA FOR COMMERCIAL
 BUILDINGS. (8) FLOOD REQUIREMENTS ELEVATIONS,
 ENCLOSURES, FLOOD DAMAGE-RESISTANT MATERIALS.
 (2) ONCE THE FIRST FLOOR SLAB IS POURED THE 2ND
 ELEVATION CERTIFICATE IS REQUIRED. W. P. B.
 ADMINISTRATIVE CODE 110.3 REQUIRED INSPECTIONS 1.2
 FLOOR/ SLAB INSPECTION. IN FLOOD HAZARD AREAS, UPON
 PLACEMENT OF THE LOWEST FLOOR, INCLUDING BASEMENT, AND
 PRIOR TO FURTHER VERTICAL CONSTRUCTION, THE ELEVATION
 CERTIFICATION, REQUIRED IN SECTION 1612.5, SHALL BE
 SUBMITTED TO THE BUILDING OFFICIAL.
 (3) BEFORE THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY
 OR A CERTIFICATE OF COMPLETION THE 3RD FLOOD ZONE
 CERTIFICATE IS REQUIRED WITH THE HEIGHT OF ALL EXTERIOR
 ATTENDANTS A/C PADS OR OTHER SLABS FOR GENERATORS.
 W. P. B. ADMINISTRATIVE CODE 110.3 REQUIRED INSPECTIONS
 (6) FINAL INSPECTION. TO BE MADE AFTER THE BUILDING IS
 COMPLETED AND READY FOR OCCUPANCY. 6.1. LOWEST FLOOR
 ELEVATION. IN FLOOD HAZARD AREAS, AS PART OF THE FINAL
 INSPECTION, A FINAL CERTIFICATION OF THE LOWEST FLOOR
 ELEVATION SHALL BE SUBMITTED TO THE AUTHORITY HAVING
 JURISDICTION.
  
 FEMA NEW FORM AVAILABLE JUNE 13/2016.
 OMB NO. 1660-0008
 EXPIRATION DATE: NOV. 30/2018
 HTTP://WWW.FEMA.GOV/BUSINESS/NFIP/ELVINST.SHTM
  
 3) COMPLIED.
  
 4) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-06-18 Cont ID  
Sent By jwitmer Date 2019-06-18 Time 14:03 Rev Time  
Received By jwitmer Date 2019-06-18 Time   Sent To  
Notes
2019-06-18 14:03:122017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19050124
 ADD: 2201 45TH STREET JFK NORTH
 CONT: DPR CONSTRUCTION
 TEL: 954-991-6200
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: MON. AUGUST 26, 2019
 ACTION: DENIED
  
  
 ************************4X FEE / NOTICE!!!!! FLORIDA
 STATUTE 553.80(2)(B)
 *******************************************
 WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS?
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW.
  
 1) 2ND REQUEST. THE SUBMITTED PLANS MODULAR STRUCTURES
 FOR WILLIAM SCOTSMAN FOR A 36 FT. X 56 FT. MODULAR UNIT
 DOES NOT SHOW A 3RD PARTY REVIEW. GENERAL NOTE 20
 STATES THE RAISED SEAL SET OF PLANS ARE ON FILE IN THE
 THIRD PARTY AGENCY?S OFFICE AS DIRECTED BY DCA.
 IN THE DBPR WEBSITE FOR MANUFACTURED BUILDINGS THERE IS
 PLANS FOR WILLIAM SCOTSMAN AS THE MANUFACTURER (THERE
 ARE DIFFERENT QUALIFIERS, SPECIFY WHICH QUALIFIER) AND
 MODULAR PLANS DESIGN, CO. AS THE APPROVING AGENCY.
 PLEASE PROVIDE THE AGENCY PLAN APPROVAL NUMBER.
  
 IF THERE IS NO 3RD PARTY APPROVAL FOR THESE PLANS, THEY
 THEN ARE NOT APPROVED BY THE STATE AND WILL NEED TO BE
 UPDATED TO THE 2017 FBC-B AND EACH PAGE WILL NEED TO BE
 SIGNED AND SEALED ELECTRONICALLY.
 THE STATE PLAN ARE STILL AVAILABLE ON LINE AND CAN BE
 REVIEWED WHEN CONTACTING THE AGENCY.
 THE COVERSHEET LIST THOMAS L. MELTON AS THE CONSULTING
 ARCHITECT. PLEASE SHOW COMPLIANCE WITH THE FLORIDA
 ADMINISTRATIVE CODE. ARCHITECT DIGITAL SIGNING &
 SEALING PLANS. 61G1-16.005 PROCEDURES FOR DIGITALLY
 SIGNING AND SEALING AND FOR ELECTRONICALLY TRANSMITTING
 PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
 2) 2ND REQUEST. THE COVERSHEET STATES THIS BUILDING IS
 NOT TO BE PLACED IN A FLOOD ZONE. THE SITE PLAN SHOWS
 WHERE THE PROPOSED BUILDING IS TO BE PLACED IS IN AN AE
 FLOOD ZONE WITH A BFE OF 12.00 FT. NAVD88. PLEASE SHOW
 HOW COMPLIANCE WITH THE BOTTOM OF THE MANUFACTURED
 BUILDING WILL BE ABOVE THE BASE FLOOD PLUS THE
 ADDITIONAL 2 FEET REQUIRED BY THE CITY OF WEST PALM
 BEACH MUNI CODE SECTION ARTICLE XVII ORDINANCES ARTICLE
 XVII FLOOD PREVENTION & CONTROL.
  
 DURING THE PERMITTING OF THIS STRUCTURE THERE WILL BE
 REQUIRED (3) DIFFERENT FLOOD ZONE CERTIFICATES
 REQUIRED:
 (1) A FLOOD ZONE CERTIFICATE IS REQUIRED AS PART OF THE
 PLAN REVIEW DOCUMENTS WITH THE PROPOSED FINISH FLOOR
 HEIGHT. W. P. B. ADMINISTRATIVE CODE 107.3.5.1.1
 BUILDING MINIMUM PLAN REVIEW CRITERIA FOR COMMERCIAL
 BUILDINGS. (8) FLOOD REQUIREMENTS ELEVATIONS,
 ENCLOSURES, FLOOD DAMAGE-RESISTANT MATERIALS.
 (2) ONCE THE FIRST FLOOR SLAB IS POURED THE 2ND
 ELEVATION CERTIFICATE IS REQUIRED. W. P. B.
 ADMINISTRATIVE CODE 110.3 REQUIRED INSPECTIONS 1.2
 FLOOR/ SLAB INSPECTION. IN FLOOD HAZARD AREAS, UPON
 PLACEMENT OF THE LOWEST FLOOR, INCLUDING BASEMENT, AND
 PRIOR TO FURTHER VERTICAL CONSTRUCTION, THE ELEVATION
 CERTIFICATION, REQUIRED IN SECTION 1612.5, SHALL BE
 SUBMITTED TO THE BUILDING OFFICIAL.
 (3) BEFORE THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY
 OR A CERTIFICATE OF COMPLETION THE 3RD FLOOD ZONE
 CERTIFICATE IS REQUIRED WITH THE HEIGHT OF ALL EXTERIOR
 ATTENDANTS A/C PADS OR OTHER SLABS FOR GENERATORS.
 W. P. B. ADMINISTRATIVE CODE 110.3 REQUIRED INSPECTIONS
 (6) FINAL INSPECTION. TO BE MADE AFTER THE BUILDING IS
 COMPLETED AND READY FOR OCCUPANCY. 6.1. LOWEST FLOOR
 ELEVATION. IN FLOOD HAZARD AREAS, AS PART OF THE FINAL
 INSPECTION, A FINAL CERTIFICATION OF THE LOWEST FLOOR
 ELEVATION SHALL BE SUBMITTED TO THE AUTHORITY HAVING
 JURISDICTION.
  
 FEMA NEW FORM AVAILABLE JUNE 13/2016.
 OMB NO. 1660-0008
 EXPIRATION DATE: NOV. 30/2018
 HTTP://WWW.FEMA.GOV/BUSINESS/NFIP/ELVINST.SHTM
  
 3) COMPLIED.
  
 4) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2019-12-04 Cont ID  
Sent By jpearson Date 2019-12-04 Time 15:45 Rev Time 0.00
Received By jpearson Date 2019-12-04 Time 15:45 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2019-08-26 Cont ID  
Sent By jpearson Date 2019-08-26 Time 15:24 Rev Time 0.00
Received By jpearson Date 2019-08-26 Time 15:24 Sent To  
Notes
2019-08-26 15:24:16CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE LOAD CALCULATION FOR 400 AMP SERVICE. THE
 PANEL SCHEDULE SHOWS 3 TRAILERS. SHEET 5 SHOWS THAT
 THERE ARE 2 PANELS, PANEL A AND PANEL B. IS THIS 2 OF
 THE 3 TRAILERS, OR IS THIS CONSIDERED ONE TRAILER
 BECAUSE IT IS JOINED TOGETHER? PROVIDE CLARIFICATION.
 NEC 215.2, 220, 408.30; WPB FBC 107.2.1
 2. RISER DIAGRAM DOES NOT SHOW WIRE SIZES TO TRAILER
 PANELS. PROVIDE CORRECTION. NEC 215.5, 310.159B)(16);
 WPB FBC 107.2.1
 3. RISER DIAGRAM SHOWS A SINGLE GROUND ROD AS A
 SUPPLEMENTAL GROUNDING ELECTRODE. THIS SUPPLEMENTAL
 GROUNDING ELECTRODE NEEDS TO BE AUGMENTED BY AN
 ADDITIONAL ELECTRODE AT LEAST 6 FEET AWAY OR PROVIDE
 EVIDENCE OF RESISTANCE TO GROUND OF 25 OHMS OR LESS.
 NEC 250.53(A)(2)
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-06-17 Cont ID  
Sent By jpearson Date 2019-06-17 Time 14:58 Rev Time 0.00
Received By jpearson Date 2019-06-17 Time 14:58 Sent To  
Notes
2019-06-17 14:58:42CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE LEGIBLE ELECTRICAL PLAN FOR REVIEW, SIGNED
 AND SEALED BY THE PERSON RESPONSIBLE FOR THE DESIGN.
 WPB FBC 107.2.1, 107.3.5; FS 471, 481
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2019-11-18 Cont ID  
Sent By pleduc Date 2019-11-18 Time   Rev Time 0.00
Received By pleduc Date 2019-11-18 Time 14:01 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2019-08-12 Cont ID  
Sent By pleduc Date 2019-08-12 Time   Rev Time 0.00
Received By pleduc Date 2019-08-12 Time 13:59 Sent To  
Notes
2019-08-12 14:00:22THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THE PREVIOUS FIRE COMMENTS WERE NOT SPECIFCALLY
 ADDRESSED AND RESTATED BELOW
  
  
 1) SHEET A 1 - THERE ARE INDICATIONS OF THREE SEPARATE
 TRAILERS CONNECTED AS ONE.
  
 PER NFPA 241 THIS SETUP DOES NOT MEET THE SEPARATION
 REQUIREMENTS.
  
 PER NFPA 241, 4.2 TEMPORARY OFFICES AND SHEDS; TABLE
 4.2.1 SEPARATION DISTANCES, FIRE SPRINKLERS ARE
 REQUIRED IN EACH TRAILER.
 4.2.1* SEPARATION DISTANCES BETWEEN BUILDINGS UNDER
 CONSTRUCTION AND CONSTRUCTION-RELATED STRUCTURES, SUCH
 AS TEMPORARY OFFICES, TRAILERS, SHEDS, AND OTHER
 FACILITIES FOR THE STORAGE OF TOOLS AND MATERIALS
 HAVING COMBUSTIBLE CONSTRUCTION OR CONTENTS, SHALL BE
 IN ACCORDANCE WITH TABLE 4.2.1.
  
 1) 20 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 30 FEET
 2) 30 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 35 FEET
 3) 40 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 40 FEET
 4) 50 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 45 FEET
 5) 60 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 50 FEET
 6) GREATER THAN 60 FEET EXPOSED LENGTH SHALL BE
 SEPARATED FROM ADJACENT STRUCTURES BY AT LEAST 60 FEET
 **A 75 PERCENT REDUCTION IN SEPARATION DISTANCES SHALL
 BE PERMITTED TO BE APPLIED, PROVIDED AUTOMATIC
 SPRINKLER PROTECTION IS USED IN THE EXPOSING STRUCTURE.
  
 NOTES:
 (1) WHERE THE SEPARATION DISTANCE BETWEEN TEMPORARY
 STRUCTURES IS LESS THAN THE MINIMUM SEPARATION
 DISTANCE, THEN THE EXPOSING WALL LENGTH SHALL BE
 CONSIDERED TO BE THE SUM OF THE INDIVIDUAL EXPOSING
 WALL LENGTHS OF THE TEMPORARY STRUCTURES.
 (2) A 75 PERCENT REDUCTION IN SEPARATION DISTANCES
 SHALL BE PERMITTED TO BE APPLIED, PROVIDED AUTOMATIC
 SPRINKLER PROTECTION IS USED IN THE EXPOSING STRUCTURE.
 (3) THE SEPARATION DISTANCES APPLY TO SINGLE-LEVEL
 STRUCTURES ONLY. THIS TABLE DOES NOT APPLY TO
 MULTILEVEL, UNSPRINKLERED STRUCTURES. A LEVEL, WHERE
 APPLYING THIS TABLE, IS 3600 MM (144 IN.).
  
 4.2.2* DETACHMENT BETWEEN TEMPORARY STRUCTURES,
 ADEQUATE TEMPORARY FIXED FIRE PROTECTION SYSTEMS, AND
 PORTABLE EQUIPMENT SHALL BE PROVIDED AS REQUIRED BY THE
 AUTHORITY HAVING JURISDICTION.
  
 PLEASE REVIEW AND CORRECT OF PROVIDE AT MINIMUM A NFPA
 13R FIRE SPRINKLER PROTECTION SYSTEM.
  
  
  
  
 *******************************************************
 *******************************************************
 ***********************
  
 ADDITIONAL COMMENTS:
  
 1A) SHEET A 1 - THERE IS AN INDICATION OF THREE
 TRAILERS ATTACHED; HOWEVER, SHEET 2 OF 8 THRU 8 OF 8
 INDICATES TWO TRAILERS WHICH MAY ADDRESS # 1 ABOVE.
  
 PLEASE CLARIFY AND CRORECT ALL PLAN SHEETS TO REFLECT
 ACTUAL PROJECT.
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2019-06-05 Cont ID  
Sent By pleduc Date 2019-06-05 Time   Rev Time 0.00
Received By pleduc Date 2019-06-05 Time 11:42 Sent To  
Notes
2019-06-05 11:49:59THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET A 1 - THERE ARE INDICATIONS OF THREE SEPARATE
 TRAILERS CONNECTED AS ONE.
  
 PER NFPA 241 THIS SETUP DOES NOT MEET THE SEPARATION
 REQUIREMENTS.
  
 PER NFPA 241, 4.2 TEMPORARY OFFICES AND SHEDS; TABLE
 4.2.1 SEPARATION DISTANCES, FIRE SPRINKLERS ARE
 REQUIRED IN EACH TRAILER.
 4.2.1* SEPARATION DISTANCES BETWEEN BUILDINGS UNDER
 CONSTRUCTION AND CONSTRUCTION-RELATED STRUCTURES, SUCH
 AS TEMPORARY OFFICES, TRAILERS, SHEDS, AND OTHER
 FACILITIES FOR THE STORAGE OF TOOLS AND MATERIALS
 HAVING COMBUSTIBLE CONSTRUCTION OR CONTENTS, SHALL BE
 IN ACCORDANCE WITH TABLE 4.2.1.
  
 1) 20 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 30 FEET
 2) 30 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 35 FEET
 3) 40 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 40 FEET
 4) 50 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 45 FEET
 5) 60 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 50 FEET
 6) GREATER THAN 60 FEET EXPOSED LENGTH SHALL BE
 SEPARATED FROM ADJACENT STRUCTURES BY AT LEAST 60 FEET
 **A 75 PERCENT REDUCTION IN SEPARATION DISTANCES SHALL
 BE PERMITTED TO BE APPLIED, PROVIDED AUTOMATIC
 SPRINKLER PROTECTION IS USED IN THE EXPOSING STRUCTURE.
  
 NOTES:
 (1) WHERE THE SEPARATION DISTANCE BETWEEN TEMPORARY
 STRUCTURES IS LESS THAN THE MINIMUM SEPARATION
 DISTANCE, THEN THE EXPOSING WALL LENGTH SHALL BE
 CONSIDERED TO BE THE SUM OF THE INDIVIDUAL EXPOSING
 WALL LENGTHS OF THE TEMPORARY STRUCTURES.
 (2) A 75 PERCENT REDUCTION IN SEPARATION DISTANCES
 SHALL BE PERMITTED TO BE APPLIED, PROVIDED AUTOMATIC
 SPRINKLER PROTECTION IS USED IN THE EXPOSING STRUCTURE.
 (3) THE SEPARATION DISTANCES APPLY TO SINGLE-LEVEL
 STRUCTURES ONLY. THIS TABLE DOES NOT APPLY TO
 MULTILEVEL, UNSPRINKLERED STRUCTURES. A LEVEL, WHERE
 APPLYING THIS TABLE, IS 3600 MM (144 IN.).
  
 4.2.2* DETACHMENT BETWEEN TEMPORARY STRUCTURES,
 ADEQUATE TEMPORARY FIXED FIRE PROTECTION SYSTEMS, AND
 PORTABLE EQUIPMENT SHALL BE PROVIDED AS REQUIRED BY THE
 AUTHORITY HAVING JURISDICTION.
  
 PLEASE REVIEW AND CORRECT OF PROVIDE AT MINIMUM A NFPA
 13R FIRE SPRINKLER PROTECTION SYSTEM.
  
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-12-17 Cont ID  
Sent By cpuell Date 2019-12-17 Time 16:31 Rev Time 0.00
Received By cpuell Date 2019-11-13 Time 16:15 Sent To  
Notes
2019-11-14 16:15:53B25

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-09-25 Cont ID  
Sent By lmarchan Date 2019-09-25 Time 09:39 Rev Time 0.00
Received By lmarchan Date 2019-08-09 Time 10:31 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-06-25 Cont ID  
Sent By lmarchan Date 2019-06-25 Time 11:37 Rev Time 0.00
Received By lmarchan Date 2019-06-04 Time 11:02 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2019-11-26 Cont ID  
Sent By jesmith Date 2019-11-26 Time 10:50 Rev Time 0.00
Received By jesmith Date 2019-11-26 Time 10:49 Sent To  
Notes
2019-11-26 10:50:42 
  
 PLUMBING COMMENTS: APPROVED
  
 WASTE TANK CAPACITY IS 250 GALLON PER DPR COMMENTS
 ATTACHED TO PLAN SHEET A-4.
 SEE PLAN SHEET 007 FOR LOCATION
  
  
 19050124 2201 45TH ST
  
  
  
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2019-08-27 Cont ID  
Sent By tklarge Date 2019-08-27 Time 09:09 Rev Time 0.00
Received By tklarge Date 2019-08-27 Time 08:55 Sent To  
Notes
2019-08-27 08:56:491)THERE ARE TWO DIFFERENT SETS OF PLANS FOR TWO
 DIFFERENT TRAILERS IN THIS SUBMITTAL. DELETE THE
 DRAWINGS THAT ARE NOT BEING USED FOR THIS PERMIT. WPB
 AMEND. TO FBC SEC. 107.2.1.
 2) INDICATE ON THE PLANS THE SIZE OF THE HOLDING TANK
 FOR THE SANITARY WASTE ON THE PLANS.IF THE TANK EXCEEDS
 300 GALLONS, A PERMIT FROM THE PALM BEACH COUNTY HEALTH
 DEPT. IS REQUIRED.
 3) PLANS ARE REQUIRED TO BE DIGITALLY SIGNED AND SEALED
 PER FL. ADMIN. CODE RULE 61G15-23.004.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-06-19 Cont ID  
Sent By tklarge Date 2019-06-19 Time 09:03 Rev Time 0.00
Received By tklarge Date 2019-06-19 Time 06:43 Sent To  
Notes
2019-06-19 08:51:261) NOTE THE SIZE OF THE HOLDING TANK FOR THE SANITARY
 WASTE ON THE PLANS.IF THE TANK EXCEEDS 300 GALLONS, A
 PERMIT FROM THE PALM BEACH COUNTY HEALTH DEPT. IS
 REQUIRED.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status N Date 2019-12-04 Cont ID  
Sent By jpearson Date 2019-12-04 Time 15:35 Rev Time 0.00
Received By jpearson Date 2019-12-04 Time 15:35 Sent To  
Notes
2019-12-04 15:35:05SWITCHED TO PAPER.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2019-08-26 Cont ID  
Sent By jpearson Date 2019-08-26 Time 15:13 Rev Time 0.00
Received By jpearson Date 2019-08-26 Time 15:13 Sent To  
Notes
2019-08-26 15:13:26PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN
 IS REQUIRED TO BE SIGNED AND SEALED BY THE PERSON
 RESPONSIBLE FOR THE DESIGN. A DIGITAL PLAN REQUIRES A
 DIGITAL SIGNATURE WITH THE PROPER THIRD PARTY
 VERIFICATION. SELF-CERTIFICATION IS NOT ACCEPTABLE.
 ADDITIONALLY, THE DIGITAL SIGNATURE MUST INCLUDE THE
 STATEMENT "SIGNED AND SEALED" AS PER FAC 61G15-23.004.
 PROVIDE CORRECTION. WPB FBC 107.1; FS 471/481

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2019-06-17 Cont ID  
Sent By jpearson Date 2019-06-17 Time 14:57 Rev Time 0.00
Received By jpearson Date 2019-06-17 Time 14:57 Sent To  
Notes
2019-06-17 14:57:19PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN
 IS REQUIRED TO BE SIGNED AND SEALED BY THE PERSON
 RESPONSIBLE FOR THE DESIGN. A DIGITAL PLAN REQUIRES A
 DIGITAL SIGNATURE WITH THE PROPER THIRD PARTY
 VERIFICATION. SELF-CERTIFICATION IS NOT ACCEPTABLE.
 ADDITIONALLY, THE DIGITAL SIGNATURE MUST INCLUDE THE
 STATEMENT "SIGNED AND SEALED" AS PER FAC 61G15-23.004.
 PROVIDE CORRECTION. WPB FBC 107.1; FS 471/481

Review Stop Z ZONING
Rev No 3 Status P Date 2019-12-17 Cont ID  
Sent By eschneid Date 2019-12-17 Time 16:20 Rev Time 0.50
Received By eschneid Date 2019-12-09 Time 16:38 Sent To  
Notes
2019-12-17 16:20:55PASSED W/PROVISOS
  
 1) NO TREES ARE PERMITTED TO BE REMOVED OR DAMAGED TO
 ACCOMMODATE THE INSTALLATION OF THE TRAILERS, TO
 INCLUDE THE STEPS, WALKWAYS, HOLDING TANK, POWER POLE,
 WATER LINE, ETC.
  
 2) A SEPARATE PARKING LOT RESTRIPING PERMIT TO INSTALL
 THE ADA COMPLIANT PARKING SPACE FOR THE TRAILER COMPLEX
 IS REQUIRED. THE PERMIT MUST BE APPROVED, THE SPACE
 INSTALLED AND PASS INSPECTION PRIOR TO THE FINAL
 INSPECTION AND USE OF THE TRAILER.
  

Review Stop Z ZONING
Rev No 2 Status F Date 2019-09-25 Cont ID  
Sent By eschneid Date 2019-09-25 Time 09:03 Rev Time 0.50
Received By eschneid Date 2019-09-05 Time 15:56 Sent To  
Notes
2019-09-25 09:03:49FAILED
  
 PROVIDE WRITTEN RESPONSE TO COMMENTS.
  
 1) THE RESPONSE LETTER FROM TOMMY COOK DATED AUGUST 9,
 2019, STATES THAT A DIFFERENT OFFICE TRAILER IS
 PROPOSED TO BE USED IN LIEU OF THE ORIGINALLY PROPOSED
 ONE; HOWEVER, THE ORIGINAL TRAILER PLANS, UPLOADED ON
 JUNE 5, 2019, ARE STILL INCLUDED WITH THE SUBMITTAL. IF
 THESE PLANS ARE NOT TO BE USED, THEN THE APPLICANT
 NEEDS TO GET THEM VOIDED OR REMOVED FROM THE SUBMITTAL
 PACKET. THE ZONING REVIEW BELOW IS BASED ON THE PLANS
 UPLOADED ON AUGUST 9, 2019, UNLESS OTHERWISE NOTED.
  
 2) REPEAT/UPDATED COMMENT: NONE OF THE PLANS SHOW THE
 TOTAL LENGTH OF THE TRAILERS, TO INCLUDE THE DIMENSION
 FOR THE TRAILER HITCHES. THE REQUIREMENT FOR THE
 TRAILER HITCH LENGTH DIMENSION WAS PROVIDED IN THE
 PREVIOUS COMMENTS.
  
 3) REPEAT/UPDATED COMMENT: THE TRAILER FLOOR PLAN
 MEASURES 23.33 FEET DEEP, WITH NO DIMENSION PROVIDED
 FOR THE OVERALL WIDTH (SEE COMMENT NO. 1); HOWEVER,
 BASED ON THE TITLE BLOCK THE TRAILERS ARE 59 FEET IN
 LENGTH PLUS THE TRAILER HITCH LENGTH. THE JOB TRAILER
 SITE PLAN SHEET, WHICH WAS NOT UPDATED FOR THE
 RESUBMITTAL, SHOWS THE TRAILERS BEING INSTALLED ON TOP
 OF ONE OF THE PARKING BAYS WHICH MEASURES 18 FEET BY 63
 FEET.
  
 A. THE JOB TRAILER SITE PLAN MUST USE THE MOST RECENT
 SURVEY FOR THE JFK NORTH MEDICAL CENTER AS THE BASE
 DRAWING AND ACCURATELY, TO SCALE, SHOW WHERE THE
 TRAILER IS TO BE INSTALLED. .
 B. THE REVISED JOB TRAILER SITE PLAN MUST INCLUDE THE
 ACTUAL SCALED DIMENSION FOR THE CONSTRUCTION TRAILER
 COMPLEX, TO INCLUDE ANY REQUIRED STEPS OR ADA RAMPS AND
 THE HOLDING TANK.
 C. THE CONSTRUCTION TRAILER COMPLEX MAY NOT BLOCK THE
 PARKING LOT MANEUVERING AISLES. BASED ON THE DEPTH OF
 THE TRAILER, PLUS THE STEPS/RAMPS REQUIRED BY COMMENT
 NO. 2B, IT DOES NOT APPEAR THAT THE DRIVE AISLE IN
 FRONT OF THE TRAILER WILL NOT MEET THE MINIMUM DRIVE
 AISLE WIDTH. YOU MUST PROVIDE DIMENSIONS ON THE PLANS.
 D. THE INSTALLATION OF THE CONSTRUCTION TRAILER COMPLEX
 IS NOT PERMITTED TO REMOVE OR DAMAGE ANY EXISTING TREES
 IN THE AREA. THIS MUST BE CLEARLY SHOWN ON THE
 RESUBMITTED PLANS, SO THE EXISTING TREES ADJACENT TO
 THE PARKING AISLE MUST BE SHOWN ON THE SITE PLAN.
  
 4) REPEAT COMMENT: THE TRAILER FLOOR PLAN AND
 ELEVATIONS SHOW DOORS ON THE NORTH SIDE OF THE
 TRAILERS. THE SITE PLAN MUST SHOW ANY REQUIRED STEPS
 (AND ADA RAMPS) AND WALKWAYS LEADING FROM THE DOORS -
 NO TREES ARE PERMITTED TO BE REMOVED TO ACCOMMODATE THE
 STEPS OR WALKWAYS.
  
 5) REPEAT COMMENT: THE TRAILER FLOOR PLAN AND
 ELEVATIONS SHOW A DOOR ON THE SOUTH SIDE OF THE
 TRAILERS. THE SITE PLAN MUST SHOW AND REQUIRED STEPS
 (AND ADA RAMPS) LEADING FROM THE DOORS. PLEASE NOTE
 THAT THE INSTALLATION OF STAIRS MAY NOT BLOCK THE
 EXISTING PARKING LOT AISLE.
  
 6) UPDATED COMMENT: SHOW THE LOCATION OF THE TEMPORARY
 POWER POLE WITH THE METER ON THE SITE PLAN.
  
 7) REPEAT COMMENT: THE TEMPORARY UNDERGROUND WATER LINE
 IS SHOWN INSTALLED DIRECTLY THROUGH EXISTING TREES,
 WHICH IS NOT PERMITTED. THE WATER LINE MUST USE THE
 EXISTING TREE PLAN AS A BASE AND BE INSTALLED IN A
 LOCATION TO AVOID DAMAGING THE ROOT SYSTEM OF THE
 EXISTING TREES.
  
 8) REPEAT COMMENT: IF THE BUILDING DIVISION DETERMINES
 THAT THE TRAILER COMPLEX IS REQUIRED TO HAVE ADA
 ACCESS, THEN A SEPARATE PARKING LOT RESTRIPING PERMIT
 TO INSTALL AN ADA COMPLIANT PARKING SPACE FOR THE
 TRAILER COMPLEX IS REQUIRED.
  
 9) REPEAT COMMENT: DESCRIBE THE METHOD BEING USED TO
 PHYSICALLY PLACE THE TRAILERS AT THE DESIGNATED
 LOCATION.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2019-06-25 Cont ID  
Sent By eschneid Date 2019-06-25 Time 11:30 Rev Time 0.50
Received By eschneid Date 2019-06-24 Time 16:58 Sent To  
Notes
2019-06-25 11:30:31FAILED
  
 PROVIDE WRITTEN RESPONSE TO COMMENTS.
  
 1) INCLUDE THE DIMENSION FOR THE TRAILER HITCHES ON THE
 FLOOR PLAN SHEET A1.
  
 2) THE TRAILER FLOOR PLAN MEASURES 35 FEET BY 56 FEET
 (NOT INCLUDING THE HITCHES). THE JOB TRAILER SITE PLAN
 SHEET SHOWS THE TRAILERS BEING INSTALLED ON TOP OF ONE
 OF THE PARKING BAYS WHICH MEASURES 18 FEET BY 63 FEET.
  
 A. THE JOB TRAILER SITE PLAN MUST USE THE MOST RECENT
 SURVEY FOR THE JFK NORTH MEDICAL CENTER AS THE BASE
 DRAWING.
 B. THE REVISED JOB TRAILER SITE PLAN MUST INCLUDE THE
 ACTUAL SCALED DIMENSION FOR THE CONSTRUCTION TRAILER
 COMPLEX, TO INCLUDE ANY REQUIRED STEPS OR ADA RAMPS AND
 THE HOLDING TANK.
 C. THE CONSTRUCTION TRAILER COMPLEX MAY NOT BLOCK THE
 PARKING LOT MANEUVERING AISLES.
 D. THE INSTALLATION OF THE CONSTRUCTION TRAILER COMPLEX
 IS NOT PERMITTED TO REMOVE OR DAMAGE ANY EXISTING TREES
 IN THE AREA.
  
 3) THE TRAILER FLOOR PLAN AND ELEVATIONS SHOW DOORS ON
 THE NORTH SIDE OF THE TRAILERS. THE SITE PLAN MUST SHOW
 ANY REQUIRED STEPS (AND ADA RAMPS) AND WALKWAYS LEADING
 FROM THE DOORS - NO TREES ARE PERMITTED TO BE REMOVED
 TO ACCOMMODATE THE STEPS OR WALKWAYS.
  
 4) THE TRAILER FLOOR PLAN AND ELEVATIONS SHOW A DOOR ON
 THE SOUTH SIDE OF THE TRAILERS. THE SITE PLAN MUST SHOW
 AND REQUIRED STEPS (AND ADA RAMPS) LEADING FROM THE
 DOORS. PLEASE NOTE THAT THE INSTALLATION OF STAIRS MAY
 NOT BLOCK THE EXISTING PARKING LOT AISLE.
  
 5) SHOW THE LOCATION OF THE ELECTRIC PANEL AND METER ON
 THE SITE PLAN.
  
 6) THE TEMPORARY UNDERGROUND WATER LINE IS SHOWN
 INSTALLED DIRECTLY THROUGH EXISTING TREES, WHICH IS NOT
 PERMITTED. THE WATER LINE MUST USE THE EXISTING TREE
 PLAN AS A BASE AND BE INSTALLED IN A LOCATION TO AVOID
 DAMAGING THE ROOT SYSTEM OF THE EXISTING TREES.
  
 7) IF THE BUILDING DIVISION DETERMINES THAT THE TRAILER
 COMPLEX IS REQUIRED TO HAVE ADA ACCESS, THEN A SEPARATE
 PARKING LOT RESTRIPING PERMIT TO INSTALL AN ADA
 COMPLIANT PARKING SPACE FOR THE TRAILER COMPLEX IS
 REQUIRED.
  
 8) DESCRIBE THE METHOD BEING USED TO PHYSICALLY PLACE
 THE TRAILERS AT THE DESIGNATED LOCATION.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  