Plan Review Details - Permit 19050085
Plan Review Stops For Permit 19050085
Review Stop E ELECTRICAL
Rev No 3 Status P Date 2019-08-22 Cont ID  
Sent By jleahy Date 2019-08-22 Time 15:36 Rev Time 0.00
Received By jleahy Date 2019-08-22 Time 15:36 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2019-08-06 Cont ID  
Sent By jleahy Date 2019-08-06 Time 16:49 Rev Time 0.00
Received By jleahy Date 2019-08-06 Time 16:49 Sent To  
Notes
2019-08-06 16:50:51FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 NEED CUT SHEETS ON CABLES RISER AND PLENUM CABLE BEING
 USED? 110.3
  
 PLEASE SUBMIT A SIGNED CONTRACT FOR WORK INVOLVED.
  
 FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRIC, PLUMBING, MECHANICAL, INTERIOR
 FINISH, RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN
 FEES, MARKETING COSTS, OVERHEAD AND PROFIT;
 EXCLUDING ONLY LAND VALUE. VALUATION REFERENCES MAY
 INCLUDE THE LATEST PUBLISHED DATA OF NATIONAL
 CONSTRUCTION COST ANALYSIS SERVICES (MARSHALL-
 SWIFT, MEANS, ETC.), AS PUBLISHED BY INTERNATIONAL CODE
 CONGRESS. FINAL BUILDING PERMIT VALUATION SHALL BE SET
 BY THE BUILDING OFFICIAL.
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-06-05 Cont ID  
Sent By jleahy Date 2019-06-05 Time 15:09 Rev Time 0.00
Received By jleahy Date 2019-06-05 Time 15:09 Sent To  
Notes
2019-06-05 15:12:07FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
  
 NEED TO SHOW HOW YOU GET FROM POINT TO POINT IN
 BUILDING.
  
 RISER DOES NOT SHOW WHERE CABLES SHALL BE INSTALLED.
  
 NEEDS FIRE REVIEW.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-07-31 Cont ID  
Sent By pleduc Date 2019-07-31 Time   Rev Time 0.00
Received By pleduc Date 2019-07-31 Time 09:48 Sent To  
Notes
2019-07-31 15:44:55THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) ENSURE THE INSTALL COMPLIES WITH NFPA 72, CH 24,
 INCLUDING BUT NOT LIMITED TO
  
 24.5.2.5.2 COMPONENT ENCLOSURES. ALL REPEATER,
 TRANSMITTER, RECEIVER,
 SIGNAL BOOSTER COMPONENTS, AND BATTERY SYSTEM
 COMPONENTS
 SHALL BE CONTAINED IN A NEMA4- OR 4X-TYPE ENCLOSURE(S).
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2019-06-11 Cont ID  
Sent By J.Walker Date 2019-06-11 Time   Rev Time 0.00
Received By   Date 2019-05-28 Time   Sent To E
Notes
2019-06-11 15:16:13POSTED FAILED...
 WILL REQUIRE MORE DETAILS.
 EQUIPMENT MOUNTING LOCATIONS.
 WIRE CHASES AND / OR CONDUIT
 SECONDARY POWER SOURCE
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-08-22 Cont ID  
Sent By jleahy Date 2019-08-22 Time 15:36 Rev Time 0.00
Received By jleahy Date 2019-08-15 Time 12:35 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-08-12 Cont ID  
Sent By lmarchan Date 2019-08-12 Time 10:23 Rev Time 0.00
Received By lmarchan Date 2019-07-29 Time 10:18 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-06-12 Cont ID  
Sent By jleahy Date 2019-06-12 Time 16:43 Rev Time 0.00
Received By cthroop Date 2019-05-28 Time 14:32 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2019-08-22 Cont ID  
Sent By jleahy Date 2019-08-22 Time 15:36 Rev Time 0.00
Received By jleahy Date 2019-08-22 Time 15:36 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2019-08-12 Cont ID  
Sent By rmcdouga Date 2019-08-12 Time 09:23 Rev Time 0.00
Received By rmcdouga Date 2019-08-06 Time 16:51 Sent To  
Notes
2019-08-12 09:25:02SEE PREVIOUS REVIEW NOTES.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2019-06-05 Cont ID  
Sent By jleahy Date 2019-06-05 Time 15:15 Rev Time 0.00
Received By jleahy Date 2019-06-05 Time 15:15 Sent To  
Notes
2019-06-05 15:15:40NO ELECTRONIC SIGNATURE ON THESE PLANS.