| 2019-07-08 06:32:14 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. NOTE #1 ON PLAN SAYS "LIGHTING TO BE CONTROLLED BY |
| | DIGITAL TIME CLOCK OR PHOTOCELL". NOTE #1 MUST COMPLY |
| | WITH FBC EC 405.2.5. #2 EXTERIOR LIGHTING FOR BUILDING |
| | FACADE OR LANDSCAPE, MUST HAVE CONTROLS AUTOMATICALLY |
| | SET TO SHUT OFF LIGHTING PROGRAMMED FROM DAWN/DUSK. ALL |
| | TIME SWITCHES MUST HAVE MINIMUM 10HR BATTERY BACKUP. |
| | PLEASE COMPLY |
| | |
| | 2. LIGHING SCHEDULE SHOWS S1, S2, AND S3 TYPE LIGHTS, |
| | BUT ONLY TYPE S1 ARE SHOWN ON PLAN? PLEASE PROVIDE |
| | VERIFICATION. FBC 107.2.1 |
| | |
| | 3. PROVIDE CUT SHEETS SHOWING UL OR OTHER NRTL LISTINGS |
| | FOR ALL LIGHTING AND POLES. FBC 107.2.1 NEC 90.7,110.2, |
| | 110.3B |
| | |
| | 4. PROVIDE STRUCTURAL DETAIL FOR POLE BASES AND WIND |
| | LOADS. FBC 1609 |
| | |
| | 5. SATISFY ALL ZONING REQUIREMENTS. |
| | |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | CODES IN EFFECT: |
| | |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2017 6TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |