Plan Review Details - Permit 19050027
Plan Review Stops For Permit 19050027
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-08-08 Cont ID  
Sent By pvalenti Date 2019-08-08 Time 17:42 Rev Time 0.00
Received By pvalenti Date 2019-08-08 Time 17:42 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-06-06 Cont ID  
Sent By jgomez Date 2019-06-06 Time 13:21 Rev Time 0.00
Received By jgomez Date 2019-06-06 Time 09:16 Sent To  
Notes
2019-06-06 13:32:51BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 NOTE: ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
 SEC. 801.3 FBC-EXISTING BUILDING.
  
 1- LIFE SAFETY PLAN ON SHEET A-7:
  
 A) A SET OF DOUBLE DOORS IN THE CORRIDOR LEADING TO THE
 TWO EXITS WERE ELIMINATED TO ALLOW THE OPEN OFFICE
 #319. IT LOOKS LIKE THE COMMON PATH OF TRAVEL WILL
 EXCEED 100 FEET AS REQUIRED BY TABLE 1006.2.1
 FBC-BUILDING. PROVIDE THE COMMON PATH OF TRAVEL
 DISTANCE FROM THE MOST REMOTE POINT OF THE LAST
 WORKSTATION ON THIS NEW OPEN OFFICE AREA #319 AND FROM
 THE MOST REMOTE POINT OF THE NEW FILES ROOM #320.
  
 B) PROVIDE ALSO THE OVERALL TRAVEL DISTANCE FROM THE
 MOST REMOTE POINT OF THE LAST WORKSTATION ON THIS NEW
 NEW OPEN OFFICE AREA #319. AND FROM THE MOST REMOTE
 POINT OF THE NEW FILES ROOM #320. TABLE 1017.2
 FBC-BUILDING.
  
 C) SHOW ALL THE EXITS SIGNS AS REQUIRED BY SEC. 1013.1
 FBC-BUILDING FOR THE NEW OFFICE LAYOUT.
  
 D) REVISE CODE SECTIONS AND TABLES CITED ON THE LIFE
 SAFETY SUMMARY (SUITE #350) CHART SHOWN BELOW THE LIFE
 SAFETY FLOOR PLAN. THEY DO NOT CORRESPOND TO THE TABLES
 AND SECTIONS OF FBC-6TH EDITION.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE, INSERT CORRECTED PAGES INTO THE SUBMITTAL AND
 REMOVE/VOID THE PREVIOUSLY REVIEWED SHEETS.
 PLEASE DON'T STAPLE OLD DRAWINGS/DOCUMENTS . SUBMIT OLD
 DRAWINGS/DOCUMENTS FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2019-06-17 Cont ID  
Sent By jpearson Date 2019-06-17 Time 11:36 Rev Time 0.00
Received By jpearson Date 2019-06-17 Time 11:36 Sent To I
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-07-15 Cont ID  
Sent By pleduc Date 2019-07-15 Time   Rev Time 0.00
Received By pleduc Date 2019-07-15 Time 14:07 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2019-05-14 Cont ID  
Sent By pleduc Date 2019-05-14 Time   Rev Time 0.00
Received By pleduc Date 2019-05-14 Time 14:29 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-08-08 Cont ID  
Sent By pvalenti Date 2019-08-08 Time 17:43 Rev Time 0.00
Received By pvalenti Date 2019-07-11 Time 15:48 Sent To  
Notes
2019-08-08 08:48:21PETER VALENTI'S DESK
2019-07-12 15:48:18C16

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2019-06-17 Time   Rev Time 0.00
Received By lmarchan Date 2019-05-01 Time 13:12 Sent To  
Notes
2019-05-02 13:12:26C13

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2019-06-05 Cont ID  
Sent By jgomez Date 2019-06-05 Time 18:41 Rev Time 0.00
Received By jgomez Date 2019-06-05 Time 18:41 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2019-06-06 Cont ID  
Sent By ccole Date 2019-06-06 Time 15:33 Rev Time 0.00
Received By ccole Date 2019-06-06 Time 15:01 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-08-08 Cont ID  
Sent By jesmith Date 2019-08-08 Time 08:39 Rev Time 0.00
Received By jesmith Date 2019-08-06 Time 15:42 Sent To  
Notes
2019-08-08 08:39:13PLUMBING COMMEMTS: APPROVED

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-06-04 Cont ID  
Sent By thunt Date 2019-06-04 Time 13:07 Rev Time 0.00
Received By thunt Date 2019-06-04 Time 13:07 Sent To  
Notes
2019-06-04 13:08:54PLUMBING 1ST REVIEW**DENIED**
  
  
 1-PROVIDE CLEAR FLOOR SPACE AS REQUIRED IN
 FBC-ACC606.2, TURNING SPACE AS REQUIRED IN FBC-ACC 304,
 AND ACCESSIBLE ROUTE FBC-ACC 404 ON THE A SHEET NEW
 WORK FOR BOTH THE BREAK ROOM SINK AND CAF? SINK. BEING
 THAT THESE ARE 2 DIFFERENT SINKS BOTH SHALL APPLY WITH
 THE FLORIDA ACCESSIBILITY CODE.
  
 2-PROVIDE SANITARY ISOMETRIC DRAWING. SHT. P 01 REFERS
 UNDER KEY NOTE (NEW VENT LINE) BUT NO ISOMETRIC
 PROVIDE. FBC 107.3.5
  
 3- PROVIDE DIMENSIONS OF DOORWAYS AND PATHWAYS SHOWING
 MIN ACCESSIBLE PATH. FBC 107.3.5
  
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR
 BUILDING DIVISION
 CITY OF WEST PALM BEACH
 401 CLEMATIS STREET, 1ST FLOOR
 WEST PALM BEACH, FL 33401
 561-248-2703
 [email protected]
 [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2019-05-29 Cont ID  
Sent By jroach Date 2019-05-29 Time 16:25 Rev Time 0.00
Received By jroach Date 2019-05-29 Time 16:20 Sent To  
Notes
***NONE***